9525.00-IPBS MOTIVAIR CHILLER REPLACEMENTS
DES MOINES, IA
300 4th St
West Des Moines, IA
50265
515-724-7938
info@kclengineering.com
100% CONSTRUCTION
DOCUMENTS SUBMITTAL
SHEET INDEX
SHEET NUMBER
TS
M000
MD101
M101
M301
M501
E000
E101
S001
S101
SHEET DESCRIPTION
TITLE SHEET
MECHANICAL GENERAL NOTES & SYMBOLS
FLOOR PLAN HVAC DEMOLITION
FLOOR PLAN HVAC
MECHANICAL DETAILS
MECHANICAL SCHEDULES
ELECTRICAL GENERAL NOTES, SYMBOLS AND DEMO PLAN
ELECTRICAL POWER
STRUCTURAL NOTES & DETAILS
PARTIAL ROOF FRAMING PLAN
MEP ENGINEER
KCL ENGINEERING
300 4th Street
West Des Moines, Iowa 50265
CHAD BASS, PE
Mechanical Engineer
phone: 515-205-1397
cbass@kclengineering.com
CONSTRUCTION MANAGER
BOYD JONES
11204 NW Aurora Avenue
Urbandale, IA 50322
ROB GREINER
Construction Project Manager
phone: 515-650-7777
rgreiner@boydjones.biz
STRUCTURAL ENGINEER
KPFF CONSULTING ENGINEERS
604 Locust Street
Suite 202
Des Moines, IA 50309
NATHAN KRESS
Structural Engineer
phone: 515-279-3900
Nathan.Kress@kpff.com
PROFESSIONA
CHAD D.
BASS
21397
I OWA
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSCED
PROFESSIONAL ENGINEER UNDER THE LAWS OF IOWA.
CHAD D. BASS, P.E.
21397
REG. NO.
MY LICENSE RENEWAL DATE IS DECEMBER 31, 2026.
DATE
PAGES OR SHEETS COVERED BY THIS SEAL:
MECHANICAL DRAWINGS AS LISTED ABOVE
PROFESSIONA
ERIK
HEYNEN
P24706
I OWA
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSCED
PROFESSIONAL ENGINEER UNDER THE LAWS OF IOWA.
ERIK HEYNEN,
P.E.
P24706
REG. NO.
MY LICENSE RENEWAL DATE IS DECEMBER 31, 2026.
PAGES OR SHEETS COVERED BY THIS SEAL:
DATE
ELECTRICAL DRAWINGS AS LISTED ABOVE.
PROFESSIONA
NATHAN T.
KRESS
21136
I OWA
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSCED
PROFESSIONAL ENGINEER UNDER THE LAWS OF IOWA.
NATHAN T. KRESS
21136
REG. NO.
MY LICENSE RENEWAL DATE IS DECEMBER 31, 2027.
PAGES OR SHEETS COVERED BY THIS SEAL:
STRUCTURAL DRAWINGS AS LISTED ABOVE.
(DATE)
© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.
Project No:
9525.00
Date:
07/06/2026
CONSTRUCTION
DOCUMENTS
#
Revision
Date
Drawing Name:
TITLE SHEET
Drawing #:
TS
MECHANICAL – DEMOLITION NOTES
1.
MECHANICAL DEMOLITION DRAWINGS SHOWING EXISTING CONDITIONS HAVE BEEN
PREPARED BASED ON NON-DESTRUCTIVE FIELD OBSERVATION AND AS-BUILT DRAWINGS
PROVIDED BY THE OWNER. FIELD VERIFY EXISTING SYSTEMS BEFORE BEGINNING WORK.
NOTIFY ARCHITECT/ENGINEER IF EXISTING CONDITIONS ARE MATERIALLY DIFFERENT THAN
THOSE SHOWN ON THE PLANS.
2.
BE FAMILIAR WITH EXISTING MECHANICAL SYSTEMS THAT WILL BE AFFECTED BY THE
DEMOLITION WORK. OBTAIN PERMISSION FROM THE OWNER'S REPRESENTATIVE TO SHUT
OFF SERVICES OR SYSTEMS THAT AFFECT AREAS BEYOND THE LIMITS OF THE IMMEDIATE
DEMOLITION AREA. INFORM THE OWNER’S REPRESENTATIVE OF THE REASON FOR AND
DURATION OF THE SHUTDOWN. MINIMIZE IMPACT TO OTHER AREAS. PROCEED WITH THE
SHUT-DOWN AFTER PERMISSION FROM THE OWNER IS GRANTED.
3.
REMOVE PIPING, HANGERS, DUCTWORK, GRILLES, REGISTERS, DIFFUSERS, ETC. THAT ARE
INDICATED TO BE REMOVED IN A TIMELY MANNER IN ACCORDANCE WITH THE GENERAL
DEMOLITION SPECIFICATIONS. COORDINATE WITH THE OWNER AND OTHER CONTRACTORS.
4.
UNLESS EQUIPMENT TO BE REMOVED IS NOTED AS OWNER’S SALVAGE, DISPOSE OF
EQUIPMENT AND/OR MATERIALS INDICATED TO BE REMOVED PROMPTLY.
5.
REMOVE ALL ABANDONED PIPING AND DUCTWORK THAT IS EXPOSED OR ACCESSIBLE
WITHOUT WALL OR CEILING DEMOLITION.
HVAC - NOTES
1.
COORDINATE WORK WITH ALL OTHER TRADES AS DESCRIBED IN MECHANICAL GENERAL
NOTE #1.
2.
INSTALL ALL EQUIPMENT PER MANUFACTURER'S RECOMMENDATIONS. INSTALL SYSTEM TO
MEET ALL CITY AND STATE CODES AND REQUIREMENTS.
3.
CONTINUE PIPE INSULATION THROUGH WALLS, FLOORS, AND CEILING PENETRATIONS
UNBROKEN. SEAL AROUND INSULATION AT WALL PENETRATIONS.
MECHANICAL - GENERAL NOTES
1.
COORDINATE MECHANICAL AND ELECTRICAL WORK WITH ALL OTHER TRADES. BEGIN
INSTALLATION AND ROUGH-IN AFTER COORDINATION WITH ALL TRADES ASSOCIATED WITH
THE INSTALLATION IS COMPLETE. COORDINATE BUILDING STRUCTURE, ARCHITECTURAL
ASSEMBLIES, SHEET METAL, ALL PIPING SYSTEMS, LIGHT FIXTURES, CONDUITS, CABLE
TRAYS, ETC. REFER TO ALL GENERAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND
SPECIFICATIONS FOR THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR REWORK
ASSOCIATED WITH FAILURE TO COORDINATE.
2.
INCORPORATE MECHANICAL SPECIFICATIONS, DRAWINGS, STATE AND LOCAL CODES INTO
WORK.
3.
EACH TRADE IS RESPONSIBLE FOR MAKING PENETRATIONS WHERE REQUIRED IN EXISTING
WALLS, FLOORS, CEILINGS, AND ROOFS. MAKE PENETRATIONS NEAT. PATCH, CONCEAL, OR
CAULK OVERCUT.
4.
COVER EXPOSED WALL PENETRATIONS WITH ESCUTCHEONS OR SHEET METAL AS
APPROPRIATE.
5.
CAULK ALL CONCEALED AND EXPOSED PIPING AND DUCT WALL PENETRATIONS TO PREVENT
NOISE TRANSFER BETWEEN SPACES.
6.
CREATE OPENINGS IN THE BUILDING THAT ARE REQUIRED TO REMOVE EXISTING ITEMS AND
TO BRING IN NEW EQUIPMENT. PATCH ALL OPENINGS CREATED AND FINISHED WITH
MATERIALS TO MATCH EXISTING CONDITIONS. INCLUDE THIS WORK IN BID.
7.
ON COMPLETION OF THE INSTALLATION, COOPERATE WITH THE OWNER TO PROVIDE
TESTING, ADJUSTING, AND BALANCING TO OBTAIN PROPER OPERATION OF ALL EQUIPMENT
AND SYSTEMS. PROVIDE ALL FACILITIES AND EQUIPMENT AND COMPLETE ALL TESTS
REQUIRED FOR ADJUSTMENTS AND BALANCING TO ESTABLISH THE PROPER PERFORMANCE
OF EQUIPMENT.
8.
PROVIDE WARRANTIES FOR ALL EQUIPMENT AND INSTALLATION PER THE CONTRACT
DOCUMENTS. CONDITIONING REFRIGERATION SYSTEMS SHALL BE WARRANTED FOR A
MINIMUM OF 5 YEARS, PARTS ONLY, NON-PRORATED, FROM THE DATE OF OCCUPANCY OR
SUBSTANTIAL COMPLETION, OR WHICHEVER OCCURS FIRST. THE WARRANTY SHALL COVER
COMPRESSORS, EVAPORATORS, CONDENSER COILS, HIGH AND LOW SIDE PIPING, AND
PIPING SPECIALTIES INCLUDING EXPANSION AND SOLENOID VALVES, RELIEF VALVES, FILTER-
DRYER, AND SIGHT GLASSES. PRESSURE GAUGES AND PRESSURE SWITCHES ARE NOT
UNDER THE EXTENDED WARRANTY EXCEPT FOR LOSS OF REFRIGERANT AND
CONSEQUENTIAL DAMAGE TO THE SYSTEM WHICH WILL BE AN EXTENDED WARRANTY
OBLIGATION. ALL DEFECTS THAT BECOME APPARENT WITHIN THE WARRANTY PERIOD SHALL
BE REPAIRED BY THE MECHANICAL CONTRACTOR AS DIRECTED BY THE ENGINEER THROUGH
THE OWNER’S REPRESENTATIVE. WARRANTY DOES NOT OBLIGATE THE MECHANICAL
CONTRACTOR TO REPAIR DAMAGE RESULTING FROM THE OWNER’S ACCIDENT, IMPROPER
OPERATION, OR FAILURE TO PROVIDE MAINTENANCE. WARRANTY COVERS DEFECTIVE
MATERIAL AND INSTALLATION. REFER TO SPECIFICATIONS FOR ADDITIONAL DETAILS AND
OTHER WARRANTY INFORMATION.
PROJECT PHASING INTENT: ONE CHILLER AND ONE PUMP AT A TIME
SHOULD REMOVED/REPLACED TO ENSURE THE FACILITY CHILLED WATER
SYSTEM REMAINS OPERATIONAL AT ALL TIMES. THERE IS ALSO A DX
CRAC UNIT THAT SERVES AS A BACK UP TO THE CHILLED WATER SYSTEM.
MECHANICAL ABBREVIATIONS
ABSOR
ACU
AD
AFF
AFG
AHU
AV
BOT
BTU
BTUH
BV
CA
CB
CENT
CFM
CI
CL
COND
CO
CONC
CONTR
CP
CU
CUH
CWP
DDC
DN
DR
DS
EA
EAT
EC
EDBT
EEW
EF
EJ
EQUIP
ESE
EST
EWBT
EWC
EWT
EX
EXH
EXP
FAI
FCU
FD
FDC
FLEX
FLR
FPM
FPS
FS
FSEC
ABSORPTION
AIR CONDITIONING UNIT
ACCESS DOOR OR AREA DRAIN
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AIR VENT
BOTTOM
BRITISH THERMAL UNIT
BTU PER HOUR
BALL VALVE
COMPRESSED AIR
CATCH BASIN
CENTRIFUGAL
CUBIC FEET PER MINUTE
CAST IRON
CENTER LINE
CONDENSATE
CLEAN OUT
CONCRETE
CONTRACTOR
CONDENSATE PUMP/CIRC. PUMP
COPPER
CABINET UNIT HEATER
CIRCULATING WATER PUMP
DIRECT DIGITAL CONTROLS
DOWN
DRAIN
DOWNSPOUT
EXHAUST AIR
EXHAUST AIR TEMPERATURE
ELECTRICAL CONTRACTOR
ENTERING DRY BULB
TEMPERATURE
EMERGENCY EYE WASH
EXHAUST FAN
EXPANSION JOINT
EQUIPMENT
EMERGENCY SHOWER/EYEWASH
EXTERNAL STATIC PRESSURE
ENTERING WET BULB
TEMPERATURE
ELECTRIC WATER COOLER
ENTERING WATER
TEMPERATURE
EXISTING
EXHAUST
EXPANSION
FRESH AIR INTAKE
FAN COIL UNIT
FLOOR DRAIN
FIRE DEPARTMENT CONNECTION
FLEXIBLE
FLOOR
FEET PER MINUTE
FEET PER SECOND
FLOOR SINK
FOOD SERVICE EQUIPMENT CONSULTANT
FT
FTG
GA
GAL
GALV
GC
GW
GPH
GPM
HR
HTG
HB
ISP
JR
LAV
LDBT
LWT
LWBT
MB
MBH
MC
MECH
MH
NTS
OA
OD
PC
PSI
PRV
PRV
PV
PVC
RA
RD
RH
RTU
RV
RVT
SK
SA
SH
SO
ST
TCC
TYP
UH
UR
UV
VA
VTR
WB
WC
WHA
WH
FINTUBE
FOOTING
GAGE
GALLON
GALVANIZED
GENERAL CONTRACTOR
GREASE WASTE
GALLONS PER HOUR
GALLONS PER MINUTE
HOUR
HEATING
HOSE BIBB
INTERNAL STATIC PRESSURE
JANITOR RECEPTOR
LAVATORY
LEAVING DRY BULB
TEMPERATURE
LEAVING WATER
TEMPERATURE
LEAVING WET BULB
TEMPERATURE
MOP BASIN
1000 BTUH
MECHANICAL CONTRACTOR
MECHANICAL
MANHOLE
NOT TO SCALE
OUTSIDE AIR
OVERFLOW ROOF DRAIN
PLUMBING CONTRACTOR
POUNDS PER SQUARE INCH
POWER ROOF VENTILATOR
PRESSURE REDUCING VALVE
PRESSURE VENT
POLYVINYL CHLORIDE
RETURN AIR
ROOF DRAIN
RELATIVE HUMIDITY
ROOF TOP UNIT
RELIEF VALVE
ROOF VENT TERMINATION
SINK
SUPPLY AIR
SHOWER
STORM OVERFLOW
STORM
TEMPERATURE CONTROL
CONTRACTOR
TYPICAL
UNIT HEATER
URINAL
UNIT VENTILATOR
VENTILATION AIR
VENT THROUGH ROOF
WALL BOX – CONDENSATE
WATER CLOSET
WATER HAMMER ARRESTOR
WATER HEATER
PIPE FITTINGS
SINGLE LINE
ELBOW
ELBOW - DOUBLE BRANCH
ELBOW - OUTLET DOWN
ELBOW - OUTLET UP
ELBOW - LONG RADIUS
ELBOW - SHORT RADIUS
45° ELBOW
TEE - VENT
TEE - SANITARY
TEE - OUTLET DOWN
TEE - OUTLET UP
TEE - SIDE OUTLET DOWN
TEE - SIDE OUTLET UP
CROSS - VENT
CROSS - SANITARY
LATERAL
TEE - SINGLE SWEEP
"COMBO WYE"
REDUCER - CONCENTRIC
REDUCER - ECCENTRIC
CAPPED CONNECTION
FLANGED CONNECTION
DOUBLE LINE
ELBOW
ELBOW - DOUBLE BRANCH
ELBOW - OUTLET DOWN
ELBOW - OUTLET UP
ELBOW - LONG RADIUS
ELBOW - SHORT RADIUS
45° ELBOW
TEE - VENT
TEE - SANITARY
TEE - OUTLET DOWN
TEE - OUTLET UP
TEE - SIDE OUTLET DOWN
TEE - SIDE OUTLET UP
CROSS - VENT
CROSS - SANITARY
LATERAL
TEE - SINGLE SWEEP
"COMBO WYE"
REDUCER - CONCENTRIC
REDUCER - ECCENTRIC
CAPPED CONNECTION
FLANGED CONNECTION
**NOTE: ALL SYMBOLS MAY NOT APPLY TO THIS PROJECT**
GENERAL SYMBOLS
EXISTING = HALFTONE LINEWORK
NEW = DARK LINEWORK
DEMO = DASHED DARK LINEWORK
BELOW GRADE = LONG DASHED DARK LINEWORK
NEW CONNECTION POINT
POINT OF DISCONNECT
KEYNOTE
XXX
EQUIPMENT IDENTIFICATION TAG
X
1 SIM DETAIL DRAWING REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE
A101
SHEET REFERENCE
SIM
1
SECTION CUT REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE
A101
SHEET REFERENCE
A101 1 INTERIOR ELEVATION DRAWING REFERENCE TAG
PIPING LEGEND - MECHANICAL
CWR
CWS
CD
PC
CR
CS
EA
HCR
HCS
HWR
HWS
LWR
LWS
RS
RHG
RL
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSATE DRAIN
PUMPED CONDENSATE
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
EXHAUST PIPE - PVC
HOT/CHILLED WATER RETURN
HOT/CHILLED WATER SUPPLY
HYDRONIC RETURN
HYDRONIC SUPPLY
LOOP WATER RETURN
LOOP WATER SUPPLY
REFRIGERANT GAS
REFRIGERANT HOT GAS
REFRIGERANT LIQUID
© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.
300 4th St
West Des Moines, IA
50265
515-724-7938
info@kclengineering.com
Project No:
9525.00
Date:
07/06/2026
CONSTRUCTION
DOCUMENTS
#
Revision
Date
Drawing Name:
MECHANICAL
GENERAL NOTES &
SYMBOLS
Drawing #:
M000
GENERAL NOTES:
A.
REFER TO M000 FOR GENERAL NOTES & SYMBOLS.
B.
REFER TO M301 FOR MECHANICAL DETAILS AND CONTROLS.
300 4th St
West Des Moines, IA
50265
515-724-7938
info@kclengineering.com
REMOVE PUMPS AND
INTERTIA BASES.
PREPARE PIPING FOR
NEW CONNECTION.
AIR COOLED CU
(EXIST)
AIR COOLED CU
(EXIST)
EXISTING REF PIPING TO REMAIN (E).
REMOVE EXISTING EXTERIOR PIPING INSULATION AND
EXTERIOR JACKET FROM REFRIGERANT PIPING
FOR CONDENSING UNIT.
6" CWR (E)
6" CWS (E)
REMOVE ALL EXISTING EXTERIORINSULATION AND
PREPARE PIPING FOR NEW INSULATION AND JACKET.
(TYP. ALL CWS/CWR PIPING ON ROOF AND DOWN TO BUFFER TANK.)
AIR COOLED CU
(EXIST)
RTU
(EXIST)
RTU
(EXIST)
3" CWR (E)
3" CWS (E)
3" CWR (E)
3" CWS (E)
AIR COOLED CHILLER
(DEMO)
ROOF HATCH
(E)
AIR COOLED CHILLER
(DEMO)
REMOVE EXISTING CHILLER
CURBS AND PATCH ROOF TO
MATCH EXISTING.
(TYP.)
ALL ROOF WORK SHOULD
MAINTAIN EXISTING ROOF
WARRANTY. EXISTING ROOF
WARRANTY CONTACT IS KOOPMAN
ROOFING (641-621-0131).
N
1 LEVEL 2 HVAC DEMOLITION PLAN
1/8" = 1'-0"
BUFFER TANK
(EXIST)
© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.
Project No:
9525.00
Date:
07/06/2026
CONSTRUCTION
DOCUMENTS
#
Revision
Date
Drawing Name:
FLOOR PLAN HVAC
DEMOLITION
Drawing #:
MD101
GENERAL NOTES:
A.
REFER TO M000 FOR GENERAL NOTES & SYMBOLS.
B.
REFER TO M301 FOR MECHANICAL DETAILS AND CONTROLS.
300 4th St
West Des Moines, IA
50265
515-724-7938
info@kclengineering.com
C
C
MECHANICAL / EQUIP.
1
CONTROL
5
EQUIP. ROOM
6
CONDENSERS
2
EXPANSION TANK
(E)
AIR
SEPARATOR
(E)
EMERGENCY GENERATOR
3
MECHANICAL / EQUIP.
4
AHU
(E)
AHU
(E)
D
CWP
2
CWP
1
PROVIDE NEW INSULATION
AND JACKET FOR EXTERIOR
REF LINES. REFER TO HVAC
PIPING AND INSULATION SCHEDULE,
MECHANICAL SPECIFICATIONS
FOR ADDITIONAL INFORMATION.
6" CWS (E)
6" CWR (E)
AIR COOLED CU
(E)
RTU
(E)
D
3" CWR
3" CWS
ROOF HATCH
(E)
AIR COOLED CU
(E)
AIR COOLED CU
(E)
EXISTING REF PIPING TO REMAIN (E).
PROVIDE NEW INSULATION
AND JACKET FOR EXTERIOR
CWS/CWR LINES. REFER TO HVAC
PIPING AND INSULATION SCHEDULE,
MECHANICAL SPECIFICATIONS
FOR ADDITIONAL INFORMATION.
(TYP. ALL CWS/CWR LINES ON ROOF
AND TO BUFFER TANK.)
RTU
(E)
3" CWR (E)
3" CWS (E)
3" CWR (E)
3" CWS (E)
CH
N.O.
CH
1
2
N.C.
N.C.
ALL ROOF WORK SHOULD
MAINTAIN EXISTING ROOF
WARRANTY. EXISTING ROOF
WARRANTY CONTACT IS KOOPMAN
ROOFING (641-621-0131).
B
B
N.C.
BUFFER TANK
(E)
3-WAY VALVE
DC
1
N
2 LEVEL 2 HVAC PLAN
1/8" = 1'-0"
© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.
Project No:
9525.00
Date:
07/06/2026
CONSTRUCTION
DOCUMENTS
#
Revision
Date
Drawing Name:
FLOOR PLAN HVAC
Drawing #:
M101
BACNET CONNECTION
AI-CHILLER SETPOINT
DI-CHILLER ALARM
DO-CHILLER ENABLE
(ADDITIONAL STANDARD
CHILLER POINTS THRU
BACNET CONNECTION)
(TYP. 2)
CHILLER
CONTROL
PANEL
3"CWS
3"CWR
80 GPM
(35 TONS)
TO AHU-1
CHILLED
WATER COILS
WITH 3-WAY
VALVES (E)
80 GPM
4"CWS
4"CWR
80 GPM
AIR
SEPARATOR (E)
80 GPM
(35 TONS)
TO AHU-2
CHILLED
WATER COILS
WITH 3-WAY
VALVES (E)
GLYCOL FEED
STATION (E)
AUTOMATIC AIR VENT
(TYP.)
4"CWS
EXPANSION
TANK
67 TOTAL GALLONS,
34 GALLONS ACCEPTANCE.
MANUAL AIR
VENT
DI - CWP-1
PUMP STATUS
THERMOMETER
(TYP.)
4"CWS
4"CWR
4"CWS
CWP-1
170 GPM
PRIMARY
PUMP
TRIPLE DUTY
VALVE (TYP.)
CWP-2
170 GPM
PRIMARY DI - CWP-2
PUMP
PUMP STATUS
BYPASS FILTER. 100 MICRON
STARTUP, 20 MICRON FINAL.
BYPASS
FILTER
100 MICRON (E)
40 MESH
STRAINER
4"CWR
TO PUMP
VFD'S PROVIDED BY TCC,
POWERED BY EC.
AO-VFD SPEED
DI-VFD ALARM
DO-VFD ENABLE
POWER WIRING BY EC
CONTROL WIRING BY TCC
(TYP. 2)
PUMP VFD
3"CWS
EXTERIOR
WALL
220 GPM
N.O.
CH-1
80 TON AIR
COOLED
3"CWS
220 GPM
LOCKED CLOSED VALVE
6"CWR
4" DECOUPLE
LINE
CH-2
80 TON AIR
COOLED
3"CWR
N.C.
3"CWR
N.C.
CHILLER WATER PUMP OPERATION:
WHEN THE COOLING SYSTEM IS MANUALLY ENABLED AT THE DDC, THE CHILLED WATER PUMP SHALL BE ENABLED AND SHALL RUN CONTINUOUSLY. PUMP SPEED SHALL BE
ESTABLISHED BY THE TAB CONTRACTOR. SYSTEM HAS FULLY REDUNDANT CHILLERS/PRIMARY PUMPS THAT SHOULD BE USED IN ALTERNATING SCHEDULE DETERMINED
BY THE OWNER.
CHILLER OPERATION:
THE CHILLER SHALL BE CONTROLLED BY THE LOCAL CONTROLLER. THE CHILLER CONTROLLER WILL MODULATE AND ADJUST COMPRESSOR STAGING, CONDENSER FAN
OPERATION, HOT GAS BYPASS CONTROL TO ACHIEVE CHILLED WATER SUPPLY SETPOINT, THE DRY COOLER WILL BE CONTROLLED BY THE DDC. WHEN THE COOLING
SYSTEM IS MANUALLY ENABLED AT THE DDC, THE FOLLOWING SEQUENCE WILL OCCUR:
•
CHILLED WATER PUMP WILL START
•
CHILLED WATER FLOW SWITCH WILL BE SET
•
CHILLED WATER SETPOINT WILL BE SET TO 44F (ADJ.).
•
AFTER A 10 MIN. WAIT, CHILLER WILL BE ENABLED.
WHEN THE COOLING SYSTEM IS MANUALLY DISABLED AT THE DDC, THE FOLLOWING SEQUENCE WILL OCCUR:
•
AFTER A 10 MIN. WAIT, CHILLER WILL BE DISABLED.
•
AFTER A 20 MIN. WAIT, CHILLED WATER PUMP TO BE STOPPED.
ADDITIONAL COOLING MODE:
•
IF CHILLED WATER SETPOINT IS NOT ABLE TO BE MAINTAINED FOR 20 MIN. (ADJ.) WITH ENABELED CHILLER FULLY LOADED, THEN REDUNDANT CHILLER SHALL BE
ENABLED AND BOTH CHILLERS SHALL MODULATE TO MAINTAIN SETPOINT. AFTER CHILLED WATER SETPOINT HAS BEEN MAINTAINED FOR 30 MIN., REDUNDANT
CHILLER SHALL BE DISABLED AND RETURN TO ALTERNATING SCHEDULE.
LOW TEMPERATURE OPERATION:
•
IF O.A. TEMP IS BELOW 25F (ADJ.) FOR 15 MIN. (ADJ.) THEN DRY COOLER 3-WAY VALVE AND FANS SHALL MODULATE TO MAINTAIN SETPOINT.
WHEN O.A. TEMP RISES ABOVE 28F (ADJ.) FOR 1 HOUR (ADJ.), MODULATE 3-WAY VALVE BETWEEN BYPASS AND FULL FLOW THROUGH DRY COOLER AS REQUIRED TO
MAINTAIN SETPOINT.
EXISTING BUFFER TANK BYPASS VALVE CONTROL. PROVIDE ABILITY ON USER INTERFACE TO MANUALLY OPEN BYPASS VALVE FOR BUFFER TANK. NORMAL OPERATION IS
TO HAVE CLOSED.
EXISTING ISOLATION CONTROL VALVES SHALL REMAIN AND BE USED AS NEEDED TO ISOLATE EACH CHILLER IF SERVICE IS NEEDED. CHILLERS CAN ALSO BE ISOLATED
MANUALLY VIA MANUAL VALVES.
TRENDS
ALL POINTS SHALL BE HISTORICALLY TRENDED. TREND POINTS EVERY 15 MIN OVER A 365 DAY PERIOD OF TIME.
FLOW METER SHOWN SHALL BE USED TO VERIFY FLOW AND CALCULATE APPROXIMATE CURRENT TONNAGE ON USER INTERFACE.
ALARMS AND INTERLOCK SAFETIES:
THE FOLLOWING SHALL SHUT DOWN THE ENABLED CHILLER AND PUMP AND SHALL INDICATE AN ALARM CONDITION. DDC SHALL ENABLE REDUNDANT CHILLER AND PUMP:
- PUMP STATUS CAN NOT BE VERIFIED WITH CURRENT RELAY (AUTO RESET)
- FLOW SWITCH CAN NOT BE VERIFED (AUTO RESET)
THE FOLLOWING SHALL DISABLE THE ENABLED PUMP AND SHALL INDICATE AN ALARM CONDITION. DDC SHALL ENABLE REDUNDANT PUMP.
- PUMP STATUS CAN NOT BE VERIFIED WITH CURRENT RELAY (AUTO RESET)
ALARMS
THE FOLLOWING SHALL INDICATE AN ALARM CONDITION:
- A GENERAL VFD ALARM
- A GENERAL CHILLER ALARM
- CHILLED WATER SUPPLY TEMPERATURE IS > OR < 5°F FROM SETPOINT FOR MORE THAN 10 MIN.
COOLING SYSTEM REPORT GENERATION:
BAS SHALL MONITOR THE FOLLOWING POINT ON 5 MIN. (ADJ.) INTERVALS WITH SIGNAL TREND. THE TREND SHALL RUN FOR A 365 DAY (ADJ.)
DURATION AT WHICH POINT THE NEWEST VALUES SHALL OVERWRITE THE OLDEST VALUES:
•
DATE
•
TIME
•
GLOBAL OUTSIDE AIR TEMP. (F)
•
SYSTEM CHILLED WATER SUPPLY TEMP (F)
•
SYSTEM CHILLED WATER SUPPLY TEMP SETPOINT (F)
•
SYSTEM CHILLED WATER RETURN TEMP (F)
•
SYSTEM CHILLED WATER FLOW RATE (GPM)
•
COOLING SYSTEM LOAD (TONS)
•
OPERATIONAL STATUS OF CHILLER, CHILLED WATER PUMP.
THIS INFORMATION SHALL BE ACCESSIBLE TO VIEW IN NEITHER TABULAR OR GRAPHICAL FORM ON THE BAS.
ONCE PER MONTH THE BAS SHALL RECORED THE LARGEST COOLING SYSTEM LOAD (IN TONS) WHICH OCCURED DURING THAT MONTH,
THE DATE, TIME, OUTSIDE AIR TEMPERATURE, CHILLED WATER SUPPLY AND RETURN TEMPERATURES WHICH COINCIDED WITH THAT EVENT
SHALL ALSO BE RECORDED. THIS INFORMATION SHALL BE STORED TO A MEMORY LOCATION ON THE BAS OPERATOR INTERFACE THAT IS MAINTAINED
(NOT AUTOMATICALLY OVERWRITTEN).
DC-1
DRY COOLER
AI-3-WAY VALVE MODULATION
3" CWS/CWR
CHILLED
WATER BUFFER
TANK (E)
(1,000 GAL.)
GRADE
1 CHILLED WATER SYSTEM PIPING AND CONTROLS DIAGRAM
NOT TO SCALE
CONTROL DIAGRAM SYMBOLS
SD
TS
FZ
ES
DPS
SP
DP
N.O.
N.C.
TS
VT
M
NC
NO
AI
AO
DI
DO
ADJ
VFD
DUCT DETECTOR (BY OTHERS)
TEMPERATURE SENSOR (AVERAGING)
FREEZE STAT
ENTHALPY SENSOR
DIFFERENTIAL PRESSURE SENSOR
STATIC PRESSURE SENSOR
DEW POINT SENSOR
NORMALLY OPEN (POWERED CLOSED)
NORMALLY CLOSED (POWERED OPEN)
TEMPERATURE SENSOR AS INDICATED
VELOCITY TRANSMITTER
24V DAMPER/VALVE MOTOR
NORMALLY CLOSED
NORMALLY OPEN
ANALOG INPUT
ANALOG OUTPUT
DIGITAL INPUT
DIGITAL OUTPUT
ADJUSTABLE
VARIABLE FREQUENCY DRIVE
2 CONTROL DIAGRAM GENERAL NOTES & SYMBOLS
NTS
GENERAL CONTROL NOTES:
TEMPERATURE CONTROL CONTRACTOR TO PROVIDE A COMPLETE
CONTROL SYSTEM, INCLUDING SENSORS, RELAYS, WIRING, CONDUIT,
CONTROLLERS, AND OTHER COMPONENTS. INSTALL ALL CONTROL
COMPONENTS PER MANUFACTURER'S RECOMMENDATIONS. TCC TO
INSTALL ALL MFR PROVIDED CONTROLS COMPONENTS FURNISHED
LOOSE FROM FACTORY.
ALL DIFFERENTIAL / STATIC PRESSURE TRANSMITTERS ARE TO BE
HARDWIRED BACK TO THEIR CONTROLLERS IN LIEU OF BEING
TRANSMITTED OVER THE COMMUNICATION NETWORK.
ALL AVERAGING SENSORS (LOW LIMIT, MAT, ETC) SHALL HAVE ONE
LINEAL FOOT OF SENSOR PER SQUARE FOOT OPENING AND WITHIN 6"
OF ALL EDGES OF OPENINGS.
ALL SENSORS ARE TO BE SUPPLIED WITH APPROPRIATE RANGES TO
ACCOMPLISH STATED CONTROL SEQUENCES.
ALL SAFETY SENSORS (FREEZE STATS) SHALL BE HARD WIRED TO
STOP FANS, CLOSE OUTSIDE DAMPERS, AND RELIEF DAMPERS.
TCC TO PROVIDE A FULL GRAPHICS CONTROL PACKAGE AS PART OF
PROJECT.
ALL VFD'S ARE TO COME WITH SURGE PROTECTION. REFER TO DIV 26
VFD SPECIFICATION.
DIAGRAMS ARE SCHEMATIC. PROVIDE ADDITIONAL POINTS WHERE
REQUIRED TO MEET SEQUENCE OF CONTROL.
COORDINATE WITH EC ON REQUIRED POWER REQUIREMENTS AND
LOCATIONS.
UNLESS STATED OTHER, ELECTRICAL CONTRACTOR IS TO PROVIDE
ALL LINE VOLTAGE POWER AND CONDUIT FOR CONTROL SYSTEM AND
ALL CODE REQUIRED HARD WIRED POINTS FOR INTERACTION WITH
FIRE ALARM SHUTDOWN.
MECHANICAL CONTRACTOR IS RESPONSIBLE FOR INSTALLING ALL
CONTROL VALVES, DAMPERS, AND DAMPER ACTUATORS.
BACNET PROTOCOL SHALL BE IP/MSTP.
CONTROLS SHALL BE BY JCI CONTROLS (NO EQUALS). CONTROLS
SHALL MATCH EXISTING FACILITY STANDARDS FOR DYNAMIC
GRAPHICS, TRENDING, ETC.
© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.
NEW PUMP WITH INERTIA
BASE WITH ISOLATORS TO BE
LOCATED ON EXSITING PAD.
FIELD VERIFY ALL FINAL
EQUIPMENT DIMENSIONS
PRIOR TO RELASING
SUBMITTALS FOR REVIEW.
INSULATE ALL PUMP SURFACES INCLUDING VOLUTE
AND SUCTION DIFFUSER
TRIPLE DUTY VALVE
FLEX CONNECTOR (TYP. OF 2)
GAUGE ISOLATION VALVE
PUMP
ANCHOR BOLTS SET
IN BASE AT TIME OF
POUR
UNHOUSED SPRING
ISOLATORS W/ 2"
DEFLECTION
CONCRETE FILLED
INERTIA BASE W/ WEIGHT
EQUAL TO OR GREATER
THAN PUMP ASSEMBLY
3 END SUCTION PUMP WITH INERTIA BASE DETAIL
NTS
BUTTERFLY
VALVE
PRESSURE GAUGE
SUCTION DIFFUSER
REMOVE STARTUP
STRAINER
AFTER STARTUP
OF SYSTEM.
GROUT BASE
FULL OF
CONCRETE.
300 4th St
West Des Moines, IA
50265
515-724-7938
info@kclengineering.com
Project No:
9525.00
Date:
07/06/2026
CONSTRUCTION
DOCUMENTS
#
Revision
Date
Drawing Name:
MECHANICAL DETAILS
Drawing #:
M301