Z2DA--Install Compressor for SPS Cabinets 552-25-501

Location: Federal
Posted: Jun 2, 2026
Due: Jun 19, 2026
Agency: VETERANS AFFAIRS, DEPARTMENT OF
Type of Government: Federal
Category:
  • Z - Maintenance, Repair or Alteration of Real Property
Solicitation No: 36C25026Q0468
Publication URL: To access bid details, please log in.
Follow
Z2DA--Install Compressor for SPS Cabinets 552-25-501
Active
Contract Opportunity
Notice ID
36C25026Q0468
Related Notice
Department/Ind. Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-tier
VETERANS AFFAIRS, DEPARTMENT OF
Office
250-NETWORK CONTRACT OFFICE 10 (36C250)
Looking for contract opportunity help?

APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.

APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.

The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).

General Information View Changes
  • Contract Opportunity Type: Solicitation (Updated)
  • Updated Published Date: Jun 02, 2026 07:37 am EDT
  • Original Published Date: Apr 14, 2026 12:05 pm EDT
  • Updated Date Offers Due: Jun 19, 2026 05:00 pm EDT
  • Original Date Offers Due: May 21, 2026 05:00 pm EDT
  • Inactive Policy: Manual
  • Updated Inactive Date: Jul 19, 2026
  • Original Inactive Date: Aug 19, 2026
  • Initiative:
    • None
Classification
  • Original Set Aside:
  • Product Service Code: Z2DA - REPAIR OR ALTERATION OF HOSPITALS AND INFIRMARIES
  • NAICS Code:
    • 236220 - Commercial and Institutional Building Construction
  • Place of Performance:
Description View Changes
RFI s and VA Responses on 552-25-501 Install Compressor for SPS Cabinets

Are the ceilings in Surgery hallway and the Surgery room where the cabinets are to be mounted on hard ceilings or accessible drop ceilings.

VA Response: Hard ceilings.

Are the ceilings in Endoscopy where the cabinets are to be mounted hard ceilings or accessible drop ceilings.

VA Response: Drop ceilings.

Can we obtain pictures of these areas?

VA Response: Yes (Images 1-5 attached).

Does the chase have any access panels, or will it need to be opened through drywall?

VA Response: The chase will need to be opened through the drywall.

For the containment in surgery we are assuming that needs to be solid wall (Edge Guard type) walls and not simply plastic sheets, please confirm.

VA Response: Countermined. Please refer to the ICRA attached to this solicitation.
Also, negative air is to be supplied, can this exhaust through Hepa filters to the hall? If direct exhaust of the filters is needed how can this be accomplished?
VA Response: Negative air shall be exhausted to the exterior of the building, per Level IV control measures described the provided ICRA.
Will the work in the surgical area be after hours? Also, the work in the scope room on the first floor, is that after hours?

VA Response: As per paragraph 1 General 1.2 of the SOW, All work shall be coordinated and scheduled through the VA COR in accordance with Division 1 of the VA Standard Specification found in the TIL. All work shall be conducted during normal business hours (Monday to Friday, 0700-1700), excluding federal holidays, unless prior approval is obtained from the CO. However, some work will be approved for after hours to reduce interruptions in patient care. The contractor shall submit an RFI for approval from the CO and COR prior to after-hours work being performed.

This appears to be an ICRA category B project in the surgical areas, can you confirm?

VA Response: Activity Category determined to be D not B.

Will core drilling be necessary to get the piping from the basement to the 1st floor scope room. Is this supposed to occur inside the wall? What if there is no access in the wall?

VA Response: Please refer to drawings for areas that piping penetrates through the flooring.

What should the terminations of the pipe to connect to the Endodry cabinets be? Typically, we see a basic ball the size of the piping with a threaded connection for the cabinets.

VA Response: Please refer to specs section 22 63 00 for valve requirements.

The term medical and instrument air are used in the SOW. We are assuming the air just needs to meet the clean air standards and not necessarily be classified as a medical gas. A medical gas would require multiple additional master alarm points which aren't mentioned in the scope. Please confirm. We do use a medical compressor company to supply compressors (that technically meets the provisions of Instrument air.

VA Response: Highlighted in blue below.
1.1 ... suitable medical air compressor
2.1 ... instrument air compressor. The installation must comply with the current 2024 NFPA99 Standards for medical gas systems.
The fresh air intake is not required for instrument error; the scope seems to indicate a fresh air intake is needed, please clarify.

VA Response: Please follow requirements specified in the scope of work.

Are we responsible to hire third party verifier/tester for final inspection?

VA Response: Yes, the contractor is responsible for hiring third party verifier/tester for final inspection.

Is a bid bond required for this project? Please specify the bonding requirements for this project; I see conflicting information.

VA Response: A bid bond is not required since this solicitation is a Request for Quotes and not an Invitation for Bids. See the Bonding Information section in the RFQ Important Bidder Information regarding requirements for performance and payment bonds.
Attachments/Links
Contact Information
Contracting Office Address
  • VISN 10 CONSOLIDATED CONTRACTING 4100 WEST 3RD STREET
  • DAYTON , OH 45428
  • USA
Primary Point of Contact
Secondary Point of Contact


History

Related Document

Apr 9, 2026[Presolicitation (Original)] Z2DA--Install Compressor for SPS Cabinets 552-25-501
Apr 14, 2026[Solicitation (Original)] Z2DA--Install Compressor for SPS Cabinets 552-25-501
May 8, 2026[Solicitation (Updated)] Z2DA--Install Compressor for SPS Cabinets 552-25-501
Daily notification on new contract opportunities

With GovernmentContracts, you can:

  • Find more opportunities and win more business
  • Receive daily alerts for all new bid opportunities
  • Get contract opportunities matched to your business
ONE WEEK FREE TRIAL

See also

...: 238310 - Drywall and Insulation Contractors Place of Performance: Description Construction Magnitude...

INTERIOR, DEPARTMENT OF THE

Bid Due: 8/04/2026

* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.