30 CES - Pad Mount Transformers (1 of 2)

Location: California
Posted: May 14, 2025
Due: May 30, 2025
Agency: DEPT OF DEFENSE
Type of Government: Federal
Category:
  • 61 - Electric Wire, and Power and Distribution Equipment
Solicitation No: FA461025Q0041
Publication URL: To access bid details, please log in.
Follow
30 CES - Pad Mount Transformers (1 of 2)
Active
Contract Opportunity
Notice ID
FA461025Q0041
Related Notice
Department/Ind. Agency
DEPT OF DEFENSE
Sub-tier
DEPT OF THE AIR FORCE
Office
FA4610 30 CONS PK
Looking for contract opportunity help?

APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.

APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.

The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).

General Information
  • Contract Opportunity Type: Combined Synopsis/Solicitation (Original)
  • Original Published Date: May 14, 2025 03:24 pm PDT
  • Original Date Offers Due: May 30, 2025 01:00 pm PDT
  • Inactive Policy: 15 days after date offers due
  • Original Inactive Date: Jun 14, 2025
  • Initiative:
    • None
Classification
  • Original Set Aside: Total Small Business Set-Aside (FAR 19.5)
  • Product Service Code: 6120 - TRANSFORMERS: DISTRIBUTION AND POWER STATION
  • NAICS Code:
    • 335311 - Power, Distribution, and Specialty Transformer Manufacturing
  • Place of Performance:
    CA 93437
    USA
Description

Funds are not presently available for this contract. The Government’s obligation under this contract is contingent upon the availability of appropriated funds from which payment for contract purposes can be made. No legal liability on the part of the Government for any payment may arise until funds are made available to the Contracting Officer for this contract and until the Contractor receives notice of such availability, to be confirmed in writing by the Contracting Officer.

Five (5) phase pad-mounted transformers shall have the following voltage ratings:

•112.5 KVA, 208Y/120, 12 kV

•150 KVA, 480Y/277, 12 kV

•300 KVA, 480Y/277, 12 kV

•500 KVA, 480Y/277, 12.47 kV

•750 KVA, 480Y/277, 12 kV

In addition, the five phase pad-mounted transformers shall meet VSFB electrical requirements below:

•All stainless-steel construction (includes tank, cabinet, base, radiators, fasteners, hinges, etc.),stainless-steel grade shall be 304L or 316L (if available).

•"Pentahead" cabinet locking mechanism/device.

•Dead-Front construction (HV-200A load break elbows with shield adapters).

•Externally clamped LV bushings with threaded copper stud for full load current below 2,100.amperes - NEMA spades shall be provided per ANSI hole requirements.

•Radial feed or Loop feed

•Frequency: 60Hz.

•Windings: HV/LV copper

•Mineral Oil-filled (Non-PCB): Type FR-3 Fluid.

•Standard impedance.

•Mild steel high-voltage/low-voltage compartment barriers.

•Cooling fins.

•Proper grounding provisions.

•Dial type gauges for oil temperature, liquid level and pressure/vacuum.

•Bay-O-Net fuses & current-limiting fuses: properly sized - additionally, the transformer shouldbe equipped with three spare fuses.

•Two-position "ON/OFF" load break primary switch

•5-position tap changer: (-5%, -2 ½ %, 0, +2 ½ %, +5%)

•Automatic pressure relief device mounted on the terminal compartment.

•Oil drain valve with sampling device, and an oil-fill/oil-level plug.

•Nameplate and NEMA safety labels: include a "UL Listed" symbol on ratings label andnameplate.

•Compliant with 2016 DOE Efficiency Standard.

•Four (4) lifting lugs.

•Entire exterior of the pad-mount transformer and terminal components shall be painted with aMunsell-Green, outdoor color-finish.

•Guaranteed to have an average coil winding temperature of 65°C rise over an average ambient airtemperature of 30°C when operated at rated voltage and load conditions.

•Provide DGA test to verify conformance to performance requirements as outlined in the latestrevisions of ANSI C57.12.00 and ANSI C57.12.90.


Attachments/Links
Contact Information
Contracting Office Address
  • ADMINISTRATIVE ONLY NO REQUISITIONS 1515 ICELAND AVE RM 150
  • VANDENBERG SFB , CA 93437-5212
  • USA
Primary Point of Contact
Secondary Point of Contact
History
  • May 14, 2025 03:24 pm PDTCombined Synopsis/Solicitation (Original)
Daily notification on new contract opportunities

With GovernmentContracts, you can:

  • Find more opportunities and win more business
  • Receive daily alerts for all new bid opportunities
  • Get contract opportunities matched to your business
ONE WEEK FREE TRIAL

See also

...for an Eaton 93PM, 30 kVA Uninterruptible Power Supply (UPS) system and associated ...

HEALTH AND HUMAN SERVICES, DEPARTMENT OF

Bid Due: 6/09/2026

* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.