| Question | Date Asked | Answer | Date Answered |
| Please advise if you are accepting bids for material only (VFDs and motors). | 2/2/2026 12:23:51 PM | No, please provide bids that include material and installation as well as integration in to the Siemen’s Desigo Optic control software. | 2/3/2026 4:40:52 PM |
| Is it possible to provide the available technical information for the existing chilled water air handling units, including the model numbers, serial numbers, and any associated equipment data? Additionally, can you provide details on the variable inlet valves and static pressure sensors currently in place? | 2/5/2026 12:15:17 PM |
Please see technical information below and attachment.
• Air Handler #1 does not have a static pressure sensor • Air hander #2 has static pressure sensor • Air Handler #8 has static pressure sensor • Air Hander #1: • Make – McQuay • Model – LSL117DH • Serial 3XA01585-04 • Manuf. Date - 1992 • Air Hander #2: • Make – McQuay • Model – LSL122DV • Serial – 3XA01586-04 • Manuf. Date - 1992 • Air Handler #8: • Make – McQuay • Model – LSL122CH • Serial – 620577-030 • Manuf. Date - 1996 |
2/9/2026 11:15:27 AM |
| I do not see a NEMA rating listed for the drives. Can you provide what rating will be required for these? Will a bypass be required? | 2/11/2026 8:37:47 AM | The enclosure should be UL type 1 enclosure and a bypass is required. | 2/18/2026 8:36:41 AM |
| Is there a site visit scheduled for the above-referenced solicitation? If so, please provide the date, time, and address. | 2/12/2026 3:53:18 PM | A non-mandatory site visit has been set up for Tuesday, February 24, 2026 at 11:00 AM. The location is 1701 West Carroll Street, Kissimmee, FL, 34741. | 2/18/2026 8:41:40 AM |
| We have noticed that the integration protocol being used for Siemens is PROFIBUS. Can you please confirm are you using the same protocol or any other, if any other protocol bein used, please confirm the name of the protocol. | 2/13/2026 5:21:31 AM | Siemens uses BACnet. | 2/18/2026 8:37:41 AM |
|
Need the following information regarding the existing motors: 1. The RPM of the motors or clear pictures of the data plates.
2. The motor specifications (e.g., TEFC or ODP, and whether they are Severe duty, Corro duty, or Explosion proof rated). |
2/13/2026 1:09:21 PM |
Please see response below and attachment.
#1 – 15HP, 1750 RPM, Encl. DP, Duty CONT #2 – 7.5HP, 1745 RPM, Encl. DP, Duty CONT #3 – 7.5HP, 1755 RPM, Encl. DP, Duty CONT |
2/18/2026 8:39:10 AM |
| Code | Description |
| [031-67] | HVAC Equipment, Accessories and Supplies (Not Otherwise Classified) |
| [220-14] | Energy Computerized Control Systems for HVAC, Lighting, Utilities, etc. Combination |
| [910-17] | Energy Computerized Control System (HVAC, Lighting, Utilities, etc) Installation, Maintenance and Repair Services |
| [936-48] | Industrial Equipment (Not Construction and Repair, or HVAC) Maintenance and Repair |
| [967-2] | Air Conditioning, Heating, and Ventilating Equipment (HVAC) Manufacturing Services |
| [845-25] | Hydrostatic Pressure Testers: Dead Weight Testers, Hydrostatic Test Pumps, etc. |
| Publication | Date |

With GovernmentContracts, you can:
...suspension; Rear double A-arm independent suspension; minimum 11 inch ground clearance. Minimum 63 ...
DEPT OF DEFENSE
Bid Due: 6/05/2026
...independent suspension; minimum 11 inch ground clearance. Minimum 63 hp. Fuel capacity minimum ...
DEPT OF DEFENSE
Bid Due: 6/05/2026