TSS Ductless System Installation at EWR ATCT (Newark, N.J.)
| Location: |
New Jersey |
| Posted: |
Nov 17, 2025 |
| Due: |
Dec 1, 2025 |
| Agency: |
TRANSPORTATION, DEPARTMENT OF |
| Type of Government: |
Federal |
| Category: |
- Z - Maintenance, Repair or Alteration of Real Property
|
| Solicitation No: |
TSS_Ductless_System_Installation_EWR_ATCT |
| Publication URL: |
To access bid details, please log in. |
TSS Ductless System Installation at EWR ATCT (Newark, N.J.)
Active
Contract Opportunity
Notice ID
TSS_Ductless_System_Installation_EWR_ATCT
Department/Ind. Agency
TRANSPORTATION, DEPARTMENT OF
Sub-tier
FEDERAL AVIATION ADMINISTRATION
Office
697DCK REGIONAL ACQUISITIONS SVCS
Looking for contract opportunity help?
General Information
-
Contract Opportunity Type: Sources Sought (Original)
-
Original Published Date: Nov 17, 2025 12:09 pm CST
-
Original Response Date: Dec 01, 2025 12:00 pm CST
-
Inactive Policy: 15 days after response date
-
Original Inactive Date:
Dec 16, 2025
-
Initiative:
Classification
-
Original Set Aside: Total Small Business Set-Aside (FAR 19.5)
-
Product Service Code: Z1BA - MAINTENANCE OF AIR TRAFFIC CONTROL TOWERS
-
NAICS Code:
-
238220 - Plumbing, Heating, and Air-Conditioning Contractors
-
Place of Performance:
Newark
,
NJ
07114
USA
Description
Mechanical
-
Install (3) indoor wall-mounted units, along with all refrigerant and drain piping.
-
Install (1) 6-ton heat pump. Unit to be anchored to exterior concrete wall via on L-bracket steel frame.
-
Coordinate core penetrations through concrete wall for piping, electrical, and drain lines. Installation to include all wall waterproofing.
-
Provide and insulate all refrigerants and condensate piping above ceiling
-
Test and charge system to verify operation.
Electrical
-
Install new dedicated 208V, 3-phase power circuit
-
Provide NEMA 4X, 60A non-fused stainless steel disconnect at outdoor unit
-
Provide power and control conduit and wiring to/from all units
-
Penetrate concrete wall.
-
Provide penetration and conduit through roof deck. Patch and flash roof as required to maintain new roof warranty through Carlisle Roof installer.
Controls
-
Integrate mini-split system into the existing FAA Schneider Electric EcoStruxure DDC system via BACnet
-
Provide and install one IP-IO module at VAV-17 for coordinated backup cooling enable/disable
-
Submit point list, graphics, and control narrative to COR for approval.
-
Program unit set points, and update AHU-3 supply air setpoints
-
Support commissioning of system to validate operation.
Structural & Interior
-
Concrete core penetration for pipes and conduits
-
Provide support framing for all units and steel plates as shown in drawing.
-
Provide support for pipes and conduits.
-
Work to include wall restoration and painting.
Attachments/Links
Contact Information
Contracting Office Address
-
AAQ-500, FAA SW REGIONAL OFFICE 10101 HILLWOOD PKWY
-
FORT WORTH , TX 76177
-
USA
Secondary Point of Contact
History
-
Nov 17, 2025 12:09 pm CSTSources Sought (Original)
Daily notification on new contract opportunities
With GovernmentContracts, you can:
- Find more opportunities and win more business
- Receive daily alerts for all new bid opportunities
- Get contract opportunities matched to your business
ONE WEEK FREE TRIAL
* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.