J061--Automatic Transfer Switch Testing and Imaging

Location: Virginia
Posted: Sep 10, 2025
Due: Sep 17, 2025
Agency: VETERANS AFFAIRS, DEPARTMENT OF
Type of Government: Federal
Category:
  • J - Maintenance, Repair, and Rebuilding of Equipment
Solicitation No: 36C24125Q0856
Publication URL: To access bid details, please log in.
Follow
J061--Automatic Transfer Switch Testing and Imaging
Active
Contract Opportunity
Notice ID
36C24125Q0856
Related Notice
Department/Ind. Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-tier
VETERANS AFFAIRS, DEPARTMENT OF
Office
241-NETWORK CONTRACT OFFICE 01 (36C241)
Looking for contract opportunity help?

APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.

APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.

The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).

General Information
  • Contract Opportunity Type: Combined Synopsis/Solicitation (Original)
  • Original Published Date: Sep 10, 2025 09:30 am EDT
  • Original Date Offers Due: Sep 17, 2025 03:00 pm EDT
  • Inactive Policy: Manual
  • Original Inactive Date: Nov 16, 2025
  • Initiative:
    • None
Classification
  • Original Set Aside: Total Small Business Set-Aside (FAR 19.5)
  • Product Service Code: J061 - MAINT/REPAIR/REBUILD OF EQUIPMENT- ELECTRIC WIRE AND POWER DISTRIBUTION EQUIPMENT
  • NAICS Code:
    • 811310 - Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance
  • Place of Performance:
    VA Boston Healthcare System (BHS) West Roxbury West Roxbury , 02132
    USA
Description
Description

This is a combined synopsis/solicitation for commercial products and commercial services prepared in accordance with the format in Federal Acquisition Regulation (FAR) subpart 12.6, Streamlined Procedures for Evaluation and Solicitation for Commercial Products and Commercial Services, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation document will not be issued.

This solicitation is issued as an RFQ. The solicitation document and incorporated provisions and clauses are those in effect through the most current Federal Acquisition Circular. The most current Federal Acquisition Circular (FAC) 2024-03 can be found at Acquisition.gov.

This solicitation is set-aside for Small Business (SB).

The associated North American Industrial Classification System (NAICS) code for this procurement is 811310 Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance, with a small business size standard of $12.5 million.

The FSC/PSC is J061 Maint/Repair/Rebuild Of Equipment - Electric Wire and Power Distribution Equipment.

The Boston Healthcare System, West Roxbury Division is seeking a contractor to perform Automatic Transfer Switch (ATS) Testing and Imaging.

All interested companies shall provide quotations for the following:

Supplies/Services

Line Item
Description
Quantity
Unit of Measure
Unit Price
Total Price
0001
Base Year: Annual Automatic Transfer Switch Testing and Imaging
1
YR
1001
Option Year 1: Annual Automatic Transfer Switch Testing and Imaging
1
YR
2001
Option Year 2: Annual Automatic Transfer Switch Testing and Imaging
1
YR
3001
Option Year 3: Annual Automatic Transfer Switch Testing and Imaging
1
YR
4001
Option Year 4: Annual Automatic Transfer Switch Testing and Imaging
1
YR

Total

$
Statement of Work
Automatic Transfer Switch (ATS) Testing and Imaging

1.0 Scope of Work

The contractor will perform annual Automatic Transfer Switch testing and imaging at the Boston Healthcare System, West Roxbury Division. Contractor is responsible for all labor, materials, tools and special equipment required to perform the work.

Period of Performance
Contract shall be a base year plus 4 option years.

All Transfer Switch Testing shall occur during off hours (10:00 PM 7:00 AM)

Place of Performance
Boston Healthcare System, West Roxbury
1400 VFW Parkway
West Roxbury, MA 02132

2.0 Performance Requirements

INFRARED THERMAL IMAGING

Thermal infrared imaging of both the normal and emergency power poles shall be done during annual testing. The transfer/bypass switch shall be in the emergency position for 30 minutes, prior to the imaging pictures taken to allow for any temperature rise. Reports of anomalies shall include a color photograph of the switch being tested & a color thermal imaging print. The report information shall be similar to test report a attached and made part of this standard. Both the transfer switch & bypass contacts shall be scanned.

The following standards, as applicable, shall be part of the testing requirements:
NFPA-70 (national electric code)
NFPA-70B (electrical equipment maintenance) nfpa-70e (electrical safety in the workplace) nfpa-99 (health care facilities)
NFPA-101 (life safety code)
NFPA-110 (emergency and standby power systems) nfpa-20 (stationary pumps for fire protection) ansi/neta-mts (maintenance testing specifications) ma elevator regulations (524 cmr)

TESTING REQUIREMENTS

In-phase monitors (sync check relays)

In-phase monitors shall be checked for calibration and shall be set for + or 7 degrees maximum. Relay output contacts shall be tested, Dead bus relay outputs shall be confirmed and maximum slip rate shall be noted on the test reports.

VOLTAGE & FREQUENCY SENSORS
All voltage and frequency sensors for both normal and emergency shall be calibrated with a three-phase test set, using calibrated meters for all pickup & dropout values. All results, including as found and as left settings shall be noted on the test reports.

AUXILIARY CONTACTS & SPECIAL TIMED CONTACTS

All auxiliary position contacts shall be tested in both positions and so noted in the test reports.
All auxiliary contact functions such as Normal Power Available , Emergency Power Available , ETC. Shall be verified and noted in the test reports.

TIMER CALIBRATION AND OPERATION CHECKS

The following timers shall be checked for accuracy and so noted in the test reports:
Time delay, engine start.
Time Delay, transfer to Emergency. UMD Timer for Pre, Post, or Both. .
T3/W3 elevator presignal time delay w/ bypass.
Time delay, retransfer to normal. (set at 30 minutes) Time delay, engine cool down. (set at 300 seconds)
Time delay neutral position on Delayed transition switches.

LOAD SHED, BLOCK TRANSFER & RE-ADD CRKTS.

Special custom Load shed, Block Transfer & Re-add circuits shall be verified to be operational and be noted on the test reports (if applicable).

VERIFY TOTAL POWER FAILURE TO RESTORATION OF LOAD FROM EMERGENCY GENERATOR
Time delay, engine start = 1 or 3 seconds (Engineering Dept to specify actual time)
Time delay, transfer to emergency = .1-15 seconds (Engineering Dept to specify actual time)
Time delay, presignal = 10-20 seconds (Elevator contractor to specify actual required time)
Time delay, load shed = 1-30 seconds (Engineering Dept to specify actual required time delay)
Engine up to speed time = typical 4.5-6 seconds Retransfer to normal position = 5 minutes
Insure total transfer time on Critical or Life Safety switches do not exceed 10 seconds.
Insure that Elevator transfer switches transfer within 10 seconds, or as allowed by Mass Elevator Regulations (524 CMR) which is typically 25 seconds.

BYPASS/ISOLATION SWITCH TESTS
Provide bypass to normal and bypass to emergency operations with Isolation option for each. Ensure no load-break condition exists. (Switch must be a make-before-break arrangement) If switches are of the Load-break design, Engineering will establish the time & date for these tests.
Verify Manual Transfer switch function of Bypass switch. (Manual Transfer Switch Operation)
Ensure engine start contacts stay closed with ATS module out in Isolate position
After switch is isolated, rack ATS module back into the TEST position and cycle the switch through a complete sequence.
Follow manufacturer s instructions for returning switch to normal operating position
Verify B/I module relays are properly energized and that all blocking interlocks are operating correctly.
Verify all auxiliary and B/I engine start contacts.

QUALIFICATIONS FOR BIDDERS:

Qualified Bidders Shall be NETA certified Company and either Factory Trained & Authorized or Factory Trained on the Equipment to be tested. (General Electric, Zenith Controls, Russelectric, Pace, Asco, Westinghouse, Kohler, and Generac) and have a minimum of 20 years of experience, as many of the VA sites have older gear operating on site in excess of 15 years. Submit qualifications for technical review. All required certifications and proof of required experience must be provided to be considered for award.
The Field Engineer/Technician shall also be a Certified Level 2 or greater Thermographer.

SUBCONTRACTORS

If Prime vendor determines to utilize subcontractors, Prime vendor must be physically present at all times there are sub-contractors present, work activities are ongoing, materials are being delivered, etc. In addition, Prime vendor to submit in technical proposal the delineation of work from prime and subcontractors to include percentage (%) of work breakdown and description of work activities.

TEST REPORT REQUIREMENTS:

Test Reports are required to document results of each switch.
PREMIUM TIME WORK:
Bidders are reminded that all work must be done on premium time as designated by the contract.

PLEASE NOTE: TESTING OF BYPASS/ISOLATION SWITCHES REQUIRES ADDITIONAL TESTING CRITERIA DIFFERENT AND IN ADDITION TO A STANDARD ATS.
Bid prices shall be per unit and Campus may add or delete units from their BOM.
All services & inspections shall be scheduled thru COR.
No additional work can be performed under this contract, and no changes to this Scope of Work can be made without the authority and prior approval of the Contracting Officer.

3.0 Equipment to be serviced:
ATS Inventory
Â
Designation
Make
Model
Serial
Controller
Location
EE#
1
B1-1
Russelectric
RTBD-4004CEF
30535-1 A/8
2000
B1
82503
2
B1-2
Russelectric
RTBD-4004CEF
30535-2 C/D
2000
B1
82502
3
B1-3
Russelectric
RTBD-6004CEF
30535-2 A/8
2000
B1
82495
4
B1-4
Russelectric
RTBD-6004CEF
30535-2 C/D
2000
B1
82498
5
B1-5
Russelectric
RTBD-4004CEF
30535-1 E/F
2000
MCC431-01-WR
82501
6
B1-6 (Fire pump)
Zenith
Â
Â
Â
GD130-01-WR
56611
7
B1-7
Russelectric
RTBD-6004CEF
30535-2 E/F
2000
A3E-06 (B1)
82497
8
B1-8
Russelectric
RTBD-6004CEF
30535-2G/H
2000
A3 061 (B1)
82504
9
B1-10
Russelectric
RTBDLBCT-8004CEF
35621-2A/B
2000
B1
136551
10
B1-11
Russelectric
RTS03-ABLB6004AMF1
36512-1A/B
RPTCS
B1
147444
11
Emg Light Relays
Â
Â
Â
Â
Auditorium
Â
12
A3C-1 (ATS-2)
Russelectric
RTB-4004CEF
24509-3A/B
2000
B2
62947
13
A3C-2 (ATS-1)
Russelectric
RTB-2604CEF
24509-1A/B
2000
B2
62948
14
A3C-3 (ATS-8)
Russelectric
RTB-4004CEF
35621-1A/B
2000
B2
136550
15
A3C-4 (ATS-11)
Russelectric
RTS03-ABLB4004AMF1
39016 -1A/B
RPTCS
Â
Â
16
A3S-1 (ATS 5)
Russelectric
RTB-2604CEF
24509-1C/D
2000
B2
62945
17
A4E-1 (ATS 4)
Russelectric
RTB-4004CEF
24509-2A/B
Â
B2
62946
18
A4E-2 (ATS 6)
Russelectric
RTB-4004CEF
29772-1A/B
2000
B2
73136
19
A4E-3 (ATS 10) (Fire pump)
Zenith
Â
Â
Â
B2
72469
20
A4E-4 (ATS-3)
Russelectric
RTB-4004CEF
31010-1 A/B
Â
B2
83279
21
A4E-5 (ATS-9)
Russelectric
RTBDLB-6004CEF
35145-1 A/B
2000
B2
136549
22
A4E-7 (ATS-7)
Russelectric
RTS03-ABLB8004AMF1
36466-1A/B
RPTCS
B2
168928
23
ATS- (Mobile OR)
GE
Â
Â
Â
B2
73137
25
B8-Boiler
Russelectric
RTS03-ABLA4004AMF1
36608-1A/B
RPTCS
B8
140803
26
B20-Research
Russelectric
RTS03-ABLB8004AMF1
38472-1A/B
RPTCS
B20
Â
27
B21-Research
Russelectric
RTBDNB-6004CEF
35273-1A/B
2000
B21
136548
28
B3-1
Russelectric
RTBD-1004CEF
29772-2A/B
2000
B3
71293
29
B3-2
Russelectric
RTBDLB-4004CEF
33859-2C/D
2000
B3
104155
30
B3-3
Russelectric
RTBDLB-4004CEF
33859-2A/B
2000
B3
104153
31
B3-4
Russelectric
RTBDLB-6004CEF
33859-1A/B
2000
B3
104154
32
B3-5
Russelectric
RTBDLB-4004CEF
37890-1A/B
RPTCS
B3
167460
33
Garage
Russelectric
Â
Â
RPTCS
Garage
Â
34
Garage
Russelectric
Â
Â
RPTCS
Garage
Â

All quoters shall submit the following:
1. Questions: Any questions must be submitted in writing no later than Monday, September 15, 2025 at 10:00 AM EST.
2. Quote: Offeror shall provide a quote using the table above. Offerors must also provide all applicable labor rates for the solicited services so they can be compared to the applicable wage determination for compliance with the Service Contract Labor Standards.
All quotes shall be sent to the Contract Specialist, Rosangela Pereira at Rosangela.Pereira@va.gov.
Award will be based upon a comparative evaluation of quotes in accordance with the Simplified Acquisition Procedures of FAR 13. Comparative evaluation is the side by side pairwise comparison of quotes based on factors resulting in a Contracting Officer decision for the quote most favorable to the Government.
The following are the decision factors:
Price: Quotes will be compared by price.
Technical: The offeror s quote shall be evaluated to determine if the organization has the experience and capabilities to provide the requested services IAW the Statement of Work in a timely efficient manner.Â
Contractor shall provide specification sheets for proposed equipment and include within the solicitation response.
The award will be made to the response most advantageous to the Government. Responses should contain your best terms, conditions.
Submission of your response shall be received not later than Wednesday, September 17, 2025 at 3:00 PM EST. All quotes shall be emailed to Rosangela Pereira at Rosangela.Pereira@va.gov.
Late submissions shall be treated in accordance with the solicitation provision at FAR 52.212-1.
Any questions or concerns regarding this solicitation should be forwarded in writing via e-mail to the Point of Contact listed below.
Point of Contact: Rosangela Pereira, Rosangela.Pereira@va.gov
Attachments/Links
Contact Information
Contracting Office Address
  • ONE VA CENTER
  • TOGUS , ME 04330
  • USA
Primary Point of Contact
Secondary Point of Contact


History
  • Sep 10, 2025 09:30 am EDTCombined Synopsis/Solicitation (Original)
Daily notification on new contract opportunities

With GovernmentContracts, you can:

  • Find more opportunities and win more business
  • Receive daily alerts for all new bid opportunities
  • Get contract opportunities matched to your business
ONE WEEK FREE TRIAL

See also

...Follow Advanced Imaging Technology (AIT) Qualified Product List (QPL) Active Contract Opportunity... Regulation ...

HOMELAND SECURITY, DEPARTMENT OF

Bid Due: 1/30/2027

...Follow Advanced Imaging Technology (AIT) Qualified Product List (QPL) Active Contract Opportunity... Far ...

HOMELAND SECURITY, DEPARTMENT OF

Bid Due: 1/30/2027

...Follow Advanced Imaging Technology (AIT) Qualified Product List (QPL) Active Contract Opportunity... Announcement ...

HOMELAND SECURITY, DEPARTMENT OF

Bid Due: 1/30/2027

.... RFPs are in portable document format (PDF). To download and view these ...

DEPT OF DEFENSE

Bid Due: 6/15/2026

* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.