LMA JFF Replacement HVAC System

Location: Washington
Posted: Apr 24, 2025
Due: May 8, 2025
Agency: DEPT OF DEFENSE
Type of Government: Federal
Category:
  • N - Installation of Equipment
Solicitation No: W912EF25RSS21
Publication URL: To access bid details, please log in.
Follow
LMA JFF Replacement HVAC System
Active
Contract Opportunity
Notice ID
W912EF25RSS21
Related Notice
Department/Ind. Agency
DEPT OF DEFENSE
Sub-tier
DEPT OF THE ARMY
Major Command
US ARMY CORPS OF ENGINEERS
Sub Command
ENGINEER DIVISION NORTHWESTERN
Office
US ARMY ENGINEER DISTRICT WALLA WAL
Looking for contract opportunity help?

APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.

APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.

The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).

General Information View Changes
  • Contract Opportunity Type: Sources Sought (Updated)
  • Updated Published Date: Apr 24, 2025 09:03 am PDT
  • Original Published Date: Apr 18, 2025 07:19 am PDT
  • Updated Response Date: May 08, 2025 10:00 am PDT
  • Original Response Date: May 02, 2025 10:00 am PDT
  • Inactive Policy: 15 days after response date
  • Updated Inactive Date: May 23, 2025
  • Original Inactive Date: May 17, 2025
  • Initiative:
    • None
Classification
  • Original Set Aside:
  • Product Service Code: N041 - INSTALLATION OF EQUIPMENT- REFRIGERATION, AIR CONDITIONING, AND AIR CIRCULATING EQUIPMENT
  • NAICS Code:
    • 333415 - Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing
  • Place of Performance:
    Kahlotus , WA 99335
    USA
Description View Changes

W912EF - THIS IS A SOURCES SOUGHT NOTICE AND SHOULD NOT BE CONSTRUED AS A SOLICITATION ANNOUNCEMENT. THE SUBMISSION OF THIS INFORMATION IS FOR PLANNING PURPOSES ONLY. IT IS NOT TO BE CONSTRUED AS A COMMITMENT BY THE GOVERNMENT TO PROCURE ANY SUPPLIES OR TO AWARD A CONTRACT ON THE BASIS OF THIS REQUEST FOR INFORMATION.



The US Army Corps of Engineers (USACE), Walla Walla District is seeking sources for a supply project: LMA JFF Replacement HVAC System. This project involves the purchase, installation, and commissioning of two new electric HVAC systems along with removal and disposal of the existing HVAC systems for the first floor and second floor of the Juvenile Fish Facility at Lower Monumental Lock & Dam. The determination of the acquisition strategy for this procurement lies solely with the Government and will be based on market research and information available to the Government from other sources. A market survey is being conducted to determine if there are a reasonable number of firms, large or small businesses, including small-disadvantaged businesses, HUBZONE small businesses, woman-owned small businesses, or service-disabled veteran-owned small businesses interested in and technically capable of performing the scope-of-work in the specified location. If you are capable and interested in this work, please respond accordingly.



Responses to this sources sought announcement will be used by the Government to make appropriate acquisition decisions. The NAICS Code for this acquisition is 333415 Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing. The small Business size standard for this NAICS is 1,250 employees. NO SOLICITATION IS CURRENTLY AVAILABLE.



BACKGROUND AND PURPOSE:



For the purposes of market research, the U.S Army Corps of Engineers, Walla Walla District requests letters of interest from qualified supply/manufacturing contractors capable of supplying the two new HVAC systems for the following project:



Lower Monumental Dam, Kahlotus, WA.



PROJECT DESCRIPTION:



Provide two new HVAC systems which shall be electric split-type systems and shall include outdoor heat pump units, indoor ceiling-mounted air handler units with auxiliary electric heat, new thermostats, and all auxiliary piping, refrigerant, wiring, adapters, and other components needed to make the new systems function properly as a direct replacement of the existing systems. The new systems shall be brand new and shall be the latest version of its kind offered by the manufacturer. All new equipment supplied such as outdoor heat pump units, air handler units, electric heating coils, and thermostats shall be manufactured by the same company as much as possible. The new systems shall conform to the following salient characteristics. Consideration will be given to alternate designs, that meet design intent with variations to specifications, with justification for any variations. Any considerations and allowable specification variations shall be at the discretion of the Government.



3.1 FIRST FLOOR HVAC SYSTEM REQUIREMENTS




  1. Type: Electric split-type heat pump system

  2. Electric:

    1. Condenser: 208V, 3-phase, 60Hz, 30A Breaker

    2. Air Handler: 208V, 3-phase, 60Hz, 50A Breaker



  3. SEER: 14

  4. Size: 4 ton

  5. Refrigerant: R454B Freon

  6. Cooling Performance:

    1. 47,000 BTU/hr total capacity

    2. 33,500 BTU/hr sensible capacity

    3. Entering DB/WB temp: 80F/67F @ 95F ambient air temp



  7. Heat Pump Performance:

    1. High: 46,000 BTU/hr;

    2. Low: 29,000 BTU/hr @ design

    3. Heat Rise: 19.9F @ design



  8. Electric Auxiliary Heat Coil: 11.3 kW

  9. Ventilation:

    1. Main supply fan: 1 HP, ECM Multi-speed Constant Torque

    2. 1300 – 1500 CFM

    3. 0.5 – 0.6 in WC air resistance

    4. Orientation: Horizontal

    5. Heavy gauge galvanized steel cabinet



  10. Dimensions:

    1. Condenser:

      1. Match as closely as possible to existing unit.

      2. Not to exceed 35 in x 35 in x 40 in



    2. Air Handler:

      1. Match as closely as possible to existing unit

      2. Not to exceed 55 in x 22 in x 22 in





  11. Other Accessories/Features:

    1. High capacity drier factory-installed in liquid line

    2. Crankcase heater

    3. Check and expansion valve factory installed







3.2 SECOND FLOOR HVAC SYSTEM REQUIREMENTS






  1. Type: Electric split-type heat pump system

  2. Electric:

    1. Condenser: 208V, 3-phase, 60Hz, 20A Breaker

    2. Air Handler: 230V, 1-phase, 60Hz, 60A Breaker



  3. SEER: 15

  4. Size: 3 ton

  5. Refrigerant: R454B Freon

  6. Cooling Performance:

    1. 34,000 BTU/hr total capacity

    2. 25,800 BTU/hr sensible capacity

    3. Entering DB/WB temp: 80F/67F @ 95F ambient air temp



  7. Heat Pump Performance:

    1. High: 30,800 BTU/hr;

    2. Low: 19,600 BTU/hr @ design

    3. Heat Rise: 17.3F @ design



  8. Electric Auxiliary Heat Coil: 10 kW

  9. Ventilation:

    1. Main supply fan: 0.50 HP, ECM Variable Speed Constant Volume

    2. 1000 – 1200 CFM

    3. 0.5 – 0.6 in WC air resistance

    4. Orientation: Horizontal

    5. Heavy gauge galvanized steel cabinet



  10. Dimensions:

    1. Condenser:

      1. Match as closely as possible to existing unit.

      2. Not to exceed 35 in x 35 in x 40 in



    2. Air Handler:

      1. Match as closely as possible to existing unit

      2. Not to exceed 55 in x 22 in x 22 in





  11. Other Accessories/Features:

    1. High capacity drier factory-installed in liquid line

    2. Crankcase heater

    3. Check and expansion valve factory installed

    4. Variable speed direct driver blower motor





Interested firms should submit a capabilities package, to include the following:



1. Firm's name, address, point of contact, phone number, and email address.



2. CAGE code and UEI.



3. Firm's interest in participating in the solicitation, if issued.



4. Business classification: Small Business (SB), Small Disadvantaged Business (SDB),Woman Owned Small Business (WOSB), Service-Disabled Veteran Owned Small Business (SDVOSB), Historically Underutilized Business Zone Small Business (HUBZone), 8(a), or Other than Small Business (Large Business).



5. Firm's joint venture information (if applicable).



6. Interested parties who believe they can meet the requirements are invited to submit, in writing, complete information describing their interest and capability to meet all requirements stated above. At least one (1) project/capability statement should be provided to demonstrate competency and experience in the required area of supply. Narratives shall be no longer than ten pages.



Submit the above information to Chandra Crow, Contract Specialist, via email to Chandra.d.crow@usace.army.mil. Your response to the notice must be received on or before 10:00 am, Pacific Daylight Time on Friday 08 May 2025.


Attachments/Links
Contact Information
Contracting Office Address
  • CONTRACTING DIVISION 201 NORTH 3RD AVE
  • WALLA WALLA , WA 99362-1876
  • USA
Primary Point of Contact
Secondary Point of Contact
History

Related Document

Apr 18, 2025[Sources Sought (Original)] MNA JFF Replacement HVAC System
Daily notification on new contract opportunities

With GovernmentContracts, you can:

  • Find more opportunities and win more business
  • Receive daily alerts for all new bid opportunities
  • Get contract opportunities matched to your business
ONE WEEK FREE TRIAL

See also

Bid Title: RFP Police Station Security Fencing Project Category: Tribal Employment Rights Ordinance

Quinault Indian Nation

Bid Due: 6/22/2026

Follow Fire Suppression System Inspection and Certification Services Active Contract Opportunity Notice ID

DEPT OF DEFENSE

Bid Due: 6/17/2026

Number IRFP 6569-26 Title Police Extra Duty Coordinator Available Date 6/3/2026 10:00 AM

City of Spokane

Bid Due: 6/24/2026

Title Paine Field Painting, Prep, and Rubber Removal, Unit Price Available Date 6/3/2026

Snohomish County

Bid Due: 6/16/2026

* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.