C1DA--Project 575-23-107 | Expand Electrical Capability | Design

Location: Federal
Posted: Jul 17, 2026
Agency: VETERANS AFFAIRS, DEPARTMENT OF
Type of Contract: Awards
Type of Government: Federal
Category:
  • C - Architect and Engineering Services - Construction
Solicitation No: 36C25925R0113
Publication URL: To access bid details, please log in.
Follow
C1DA--Project 575-23-107 | Expand Electrical Capability | Design
Active
Contract Opportunity
Notice ID
36C25925R0113
Related Notice
Contract Line Item Number
0001-1001
Department/Ind. Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-tier
VETERANS AFFAIRS, DEPARTMENT OF
Office
NETWORK CONTRACT OFFICE 19 (36C259)
Award Details
  • Contract Award Date: Jul 16, 2026
  • Contract Award Number: 36C25926C0059
  • Task/Delivery Order Number:
  • Contractor Awarded Unique Entity ID: JKPGTKHSKRP4
  • Contractor Awarded Name: CITRINE LLC
  • Contractor Awarded Address: LAKEWOOD , CO 80215
  • Base and All Options Value (Total Contract Value): $769,409.00
General Information
  • Contract Opportunity Type: Award Notice (Original)
  • Original Published Date: Jul 17, 2026 03:26 pm EDT
  • Inactive Policy: Manual
  • Original Inactive Date: Aug 16, 2026
  • Initiative:
    • None
Classification
  • Original Set Aside: Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14)
  • Product Service Code: C1DA - ARCHITECT AND ENGINEERING- CONSTRUCTION: HOSPITALS AND INFIRMARIES
  • NAICS Code:
    • 541330 - Engineering Services
  • Place of Performance:
    ,
Description
SCOPE OF WORK: This contract will provide designs for expanding the electrical capacity of the Grand Junction VA Medical Center.

The A-E is to provide design services to expand the electrical capacity of the Grand Junction VA Medical Center (2121 North Ave, Grand Junction, COÂ 81501).

The contractor shall design the following:

Statement of Work: The Grand Junction VA Medical Center campus has 22 buildings, with 321,557 gross square feet of space. To expand services, the VA requires additional electrical power on the north and east sides of the campus. The northern electrical room remodel will support future expansions while the newly created eastern electrical room will support temporary facilities that provide workspaces for displaced employees. In the past, temporary spaces have been modular in nature and could be tents, trailers or other types of temporary facilities.

Most work will be conducted indoors, however, Grand Junction, CO has a semi-arid climate, with hot summers and generally mild winters. During the summer months temperatures typically reach into the 90s Fahrenheit during the day, while evenings tend to remain comfortable and cool. Winters are usually mild, but snow does occur, and temperatures can cool down to freezing averages. Spring and fall tend to be transitional seasons with moderate temperatures. The area receives around ten (10) inches of precipitation per year with most of it falling from April through August.

Specific project tasks:

Remodel and add on to 1634-1 (433 SF) / 1635-1 (433 SF) to ensure adequate electrical utilities exist to support the north portion of the WCHCS on the Grand Junction, CO campus. This will include expanding the rooms by 800 SF to the west. This additional space will allow the hospital to add switchboards and panels when needed and enclose an Automatic Transfer Switch (ATS).

Add a new electrical room to ensure adequate electrical utilities are in place on the eastern side of the WCHCS on the Grand Junction, CO campus. This will provide electrical capacity from location 1 on the western side of the WCHCS to location 2 (see attachment A) on the eastern side.

The minimum power requirements are three-phase, 208V, 800A and include normal, critical, life safety and emergency power circuits. This electrical run will terminate in a new conditioned electrical space at location 2 after passing through necessary electrical step-down equipment at site 3. Any future projects that have temporary facilities will be designed to be compatible with 208V and use no more than 80% of the amperage available per branch circuit. These facilities will be expected to run power from their location to the new electrical room distribution point designed at location 2.

All aspects of the design must adhere to the NEC Design manuals posted on the VA technical information library at the following sites: http://www.cfm.va.gov/til/ and https://vatilms.va.gov/vatilms/catalog.

All electrical, architectural, and mechanical work for these systems will be designed by the A-E.

The installation must, at a minimum, be in accordance with all applicable codes indicated in the Department of Veterans Affairs (VA) Design Manuals and VA Publications (Master Construction Specifications, Construction Standards, National Fire Protection Association (NFPA), Underwriters Laboratory, International Building Code IBC 2003, NFPA and National Electric Code (NEC), building codes and standards, and VA Information Security Handbook 6500.6, etc.).

DESIGN CRITERIA: As part of the design the following list needs to be considered:

All electrical work will be terminated by the contractor. The design must be clear who and what is supplied for the termination equipment.

Any penetration through any fire barriers whether a floor or wall will be done in this contract to meet VA standards and National Fire Protection Association (NFPA). The contractor shall obtain permits issued by the facility before any penetration shall occur.

The installed system and its components shall be tested and commissioned. This will be included in the design and construction documents.

Implement new technologies in electrical systems to improve and facilitate energy usage reductions. The system will be compatible with the existing control systems on station.

All finishes will be coordinated with the VA interior designer and called out in a finish schedule.

All testing and balancing parameters will be provided by the A-E.

Design documents that show the red lines will be submitted by the contractor to the A-E, put into the AutoCAD drawings and submitted within 30 days of the completion of the construction project. According to VA standards as outlined in the VA Specifications Technical Library.

All existing utilities which are designed to be relocated or modified shall have directions to the contractor on the new location and modifications.
Attachments/Links
Contact Information
Contracting Office Address
  • 6162 S WILLOW DR SUITE 300
  • Greenwood Village , CO 80111
  • USA
Primary Point of Contact
Secondary Point of Contact


History
  • Jul 17, 2026 03:26 pm EDTAward Notice (Original)

Related Document

Sep 26, 2025[Presolicitation (Updated)] C1DA--Project 575-23-107 | Expand Electrical Capability | Design
Oct 8, 2025[Presolicitation (Updated)] C1DA--Project 575-23-107 | Expand Electrical Capability | Design
Jul 17, 2026[Award Notice (Original)] C1DA--Project 575-23-107 | Expand Electrical Capability | Design
Daily notification on new contract opportunities

With GovernmentContracts, you can:

  • Find more opportunities and win more business
  • Receive daily alerts for all new bid opportunities
  • Get contract opportunities matched to your business
ONE WEEK FREE TRIAL

See also

...WEAPON SYSTEMS SUPPORT Sub Command 2 NAVSUP WSS PHILADELPHIA Office NAVSUP WEAPON SYSTEMS ...

DEPT OF DEFENSE

Bid Due: 10/30/2026

...Follow 58--CONTROL PANEL ASSY Active Contract Opportunity Notice ID SPE4A527T0627 Related Notice... Code: ...

DEPT OF DEFENSE

Bid Due: 10/20/2026

...Follow 58--PANEL,CONTROL,ELECTRIC Active Contract Opportunity Notice ID SPE4A527T0868 Related... NAICS Code: 334511 - ...

DEPT OF DEFENSE

Bid Due: 10/20/2026

...Follow 16--PANEL,ELECTRONICS,V, IN REPAIR/MODIFICATION OF Active Contract Opportunity Notice ID... Command NAVSUP Sub ...

DEPT OF DEFENSE

Bid Due: 11/01/2026

* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.