TRANSPORTATION/MAINTENANCE
VOLUSIA
COUNTY SCHOOLS
DELTONA
REPLACE
EMERGENCY
SCHOOL BOARD
MEMBERS
RUBEN COLON
BOARD CHAIR
"LEADING WITH GRACE AND RESPECT"
THE SCHOOL BOARD OF VOLUSIA
GENERATOR AND MDP
KRISTA GOODRICH
DONNA BROSEMER
JAMIE HAYNES
VICE BOARD CHAIR
MEMBER
MEMBER
COUNTY FLORIDA
200 North Clara Avenue
DeLand, Florida 32720
VCS Project NO. 2648209
JESSIE THOMPSON
DR. CARMEN J. BALGOBIN
MEMBER
SUPERINTENDENT
201 N FRANKLIN ST
SUITE 1400
TAMPA, FL 33602
PHONE: 813.620.1460
REGISTRY NO. 35106
This document is an instrument of service prepared
solely for Kimley-Horn's client and for a particular
purpose. Any other use or reliance is without liability to
Kimley-Horn.
2101 Eustace Ave, Deltona, FL 32725
DESCRIPTION OF WORK
REPLACE THE EXISTING 60 KW 208Y/120V GENERATOR AND THE EXISTING STANDBY ELECTRICAL
DISTRIBUTION SYSTEM TO PROVIDE ADDITIONAL ELECTRICAL STANDBY POWER CAPACITY FOR THE SITE. AN
ALTERNATE SERVICE, OF A NEW LARGER DIESEL GENERATOR FOR THE ENTIRE SITE LOCATED BY THE MAIN
DISTRIBUTION PANEL IN LIEU OF REPLACING THE EXISTING GENERATOR FOR THE TRANSPORTATION
BUILDING.
Architect's Statement of Compliance
To the best of my knowledge, these drawings and the project manual are complete and comply with
the Florida Building Code.
ENGINEERS & CONSULTANTS
ELECTRICAL
KIMLEY-HORN
201 N FRANKLIN ST, SUITE 1400
TAMPA, FL 33602
(813) 635 - 5555
JIMMY NGUYEN
JIMMY.NGUYEN@KIMLEY-HORN.COM
WWW.KIMLEY-HORN.COM
STRUCTURAL
KIMLEY-HORN
11601 KEW GARDENS AVE, SUITE 200
PALM BEACCH GARDENS, FL 33410
(561) 840 - 0281
SHEILA PREBLE
SHEILA.PREBLE@KIMLEY-HORN.COM
WWW.KIMLEY-HORN.COM
CIVIL
KIMLEY-HORN
6876 MARWICK LANE , SUITE 350
ORLANDO , FL 32827
(407) 409 - 7003
BLAKE WAGNER
BLAKE.WAGNER@KIMLEY-HORN.COM
WWW.KIMLEY-HORN.COM
PROJECT SHEET INDEX
SHEET NUMBER
GENERAL
G000
CIVIL
C300
C310
C400
ELECTRICAL
E000
ED100
E100
E500
E600
STRUCTURAL
S100
SHEET NAME
COVER SHEET
OVERALL EXISITNG CONDITIONS AND DEMOLITION PLAN
EXISITNG CONDITIONS AND DEMOLITION PLAN
SITE PLAN
ELECTRICAL SYMBOLS, ABBREVIATIONS, AND NOTES
ELECTRCIAL DEMO SITE PLAN
ELECTRICAL SITE PLAN
ELECTRICAL RISER DIAGRAM
ELECTRICAL DETAILS
GENERAL SLAB DETAIL
LOCATION MAP
NOT TO SCALE
CONSTRUCTION DOCUMENTS 03/19/2025
ARCH/ENGR OF RECORD
JIMMY NGUYEN PE 91973
DESIGNED BY
JN
ISSUE DATE
03/19/2026
DRAWN BY
JNJ
AE PROJECT NUMBER
145642004
SHEET TITLE
COVER SHEET
DRAWING NO.
G000
SYSTEM SYMBOLS
EQUIPMENT
SM
SHOA
MOTOR RATED SWITCH
MOTOR RATED HAND-OFF-AUTO SWITCH
EMERGENCY POWER OFF SWITCH, MUSHROOM TYPE
DISCONNECT, HEAVY DUTY, NON-FUSIBLE
DISCONNECT, HEAVY DUTY, FUSIBLE
MAGNETIC MOTOR STARTER
COMBINATION MOTOR STARTER & DISCONNECT
VFD
VARIABLE FREQUENCY DRIVE
W ALL
W ALL
T
ELECTRICAL PANEL, SURFACE MOUNTED
ELECTRICAL PANEL, FLUSH MOUNTED
TRANSFORMER
DP
W ALL
AC
WH-1 AC1
1
W ALL
AUDIO/VIDEO
DISTRIBUTION PANELBOARD
INVERTER
EQUIPMENT CALLOUT
AUXILIARY SYSTEM CABINET
S
AUDIO SPEAKER
TELECOMMUNICATION DEVICES
#
#
DATA OUTLET, DASH INDICATES 42" AFF
#
TELEPHONE OUTLET
#
#
WAP
CR
DATA OUTLET, CEILING MOUNTED
DATA OUTLET, IN FLOOR BOX, REUSE DEMOLISHED AMF50 FLOOR BOX HOUSING WHEN
AVAILABLE. IF NOT, PURCHASE SAME OR EQUIVALENT.
WIRELESS ACCESS POINT (WAP)
MOUNTING
(UON)
CARD READER
FVM
TELECOMMUNICATION DEVICE TYPE DESIGNATION LEGEND
X = TYPE, # = NUMBER OF DATA DROPS
E000
ED100
E100
E500
E600
ELECTRICAL SHEET LIST
#
SHEET NAME
ELECTRICAL SYMBOLS, ABBREVIATIONS, AND NOTES
ELECTRCIAL DEMO SITE PLAN
ELECTRICAL SITE PLAN
ELECTRICAL RISER DIAGRAM
ELECTRICAL DETAILS
ELECTRICAL SYMBOLS
CONDUIT AND RACEWAY
CONDUIT RUN IN OR ON CEILING OR WALL.
CONDUIT RUN IN FLOOR, UNDER FLOOR, OR UNDERGROUND.
MARKS INDICATE QTY OF CONDUCTORS IN CONDUIT EXCLUDING GROUND. NO MARKS
INDICATE (2) CONDUCTORS. ADD GROUND PER NEC FOR EMT & NON-METALLIC CONDUIT.
LONG MARK INDICATES GROUND FOR ISOLATED GROUNDING SYSTEM. SIZE PER NEC.
BRANCH CIRCUIT (DIAGRAMMATIC)
LA-1
LA-[1,3,5]
ON HA-1
HOMERUN INDICATING PANEL AND CIRCUIT NUMBER.
HOMERUN WITH CIRCUIT NUMBER IN BRACKETS INDICATING MULTI-PHASE LOAD.
"ON" INDICATES CIRCUITING SPLIT AT DIFFERENT LOCATIONS
CONDUIT DOWN.
CONDUIT UP.
CONDUIT STUB AND CAP.
POWER DEVICES
DUPLEX CONVENIENCE OUTLET, +18" AFF (TYPICAL).
MOUNTING
(UON)
W, +18" AFF
DUPLEX CONVENIENCE OUTLET, COUNTER HEIGHT +42" AFF (TYPICAL).
W, FVMH
CONVENIENCE OUTLET W/ GFCI PROTECTION.
W, +18" AFF
WP
IG
MON
CONVENIENCE OUTLET W/ GFCI PROTECTION & WEATHER PROOF-IN-USE COVER.
DUPLEX CONVENIENCE OUTLET W/ DEDICATED CIRCUIT & ISOLATED GROUND.
DUPLEX CONVENIENCE OUTLET FOR MONITOR. COORDINATE WITH ARCH/OWNER.
DUPLEX CONVENIENCE OUTLET WITH INTEGRAL USB CHARGING PORTS.
W, +18" AFF
W, +18" AFF
W, +60" AFF
W, +18" AFF
EWC
REF
DISP
DUPLEX CONVENIENCE OUTLET FOR ELECTRIC WATER COOLER
DUPLEX CONVENIENCE OUTLET W/ DEDICATED CIRCUIT FOR REFRIGERATOR.
DUPLEX CONVENIENCE OUTLET W/ DEDICATED CIRCUIT FOR WASTE DISPOSAL.
DOUBLE DUPLEX CONVENIENCE OUTLET.
W, +30" AFF
W, +42" AFF
W, +18" AFF
W, +18" AFF
DUPLEX CONVENIENCE OUTLET, CEILING MOUNTED, FVMH.
C, FVMH
QUAD RECEPTACLE IN FLOOR BOX.
FL
DUPLEX RECEPTACLE IN FLOOR BOX.
FL
J USE
SPECIAL PURPOSE OUTLET, NEMA CONFIGURATION AND VOLTAGE AS NOTED.
JUNCTION BOX, SPECIFIC USE AS NOTED.
W, FVMH
W, FVMH
ABBREVIATIONS
AC
AFF
ANSI
AWG
BLDG
CU
DIA
EX
EMT
ENT
ETC
IEEE
GEC
GFCI
kW
KVA
MC
MH
NEC
NEMA
NFPA
NORM
NTS
OCP
PH
PWR
PVC
SES
SPD
SWBD
TYP
UBC
UL
UON
UPS
W
XFMR
WP
ARMORED CABLE
ABOVE FINISHED FLOOR
AMERICAN NATIONAL STANDARDS INSTITUTE
AMERICAN WIRE GAUGE
BUILDING
COPPER
DIAMETER
EXISTING TO REMAIN. PROVIDE WHITE TRIM FOR NON-WHITE TRIM DEVICES
ELECTRIC METAL TUBING
ELECTRIC NON-METALLIC TUBING
ETCETERA
INSTITUTE FOR ELECTRONIC AND ELECTRICAL ENGINEERS
GROUNDING ELECTRODE CONDUCTOR
GROUND FAULT CIRCUIT INTERRUPT
KILOWATT
KILOVOLT-AMPS
METAL CLAD
MOUNTING HEIGHT
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRIC MANUFACTURERS ASSOCIATION
NATIONAL FIRE PROTECTION AGENCY
NORMAL
NOT TO SCALE
OVER CURRENT PROTECTION
PHASE
POWER
POLYVINYL CHLORIDE
SERVICE ENTRANCE SECTION
SURGE PROTECTION DEVICE
SWITCHBOARD
TYPICAL
UNIFORM BUILDING CODE
UNDERWRITERS LABORATORY
UNLESS NOTED OTHERWISE
UNINTERRUPTED POWER SUPPLY
WIRE
TRANSFORMER
WEATHER PROOF
GENERAL NEW NOTES:
1.
FURNISH ALL LABOR, MATERIALS, TOOLS, ACCESSORIES, ETC. REQUIRED FOR A COMPLETE WORKING ELECTRICAL SYSTEM.
2.
ALL ELECTRICAL WORK SHALL COMPLY WITH ALL APPLICABLE STATE, COUNTY, AND LOCAL CODES AND ORDINANCES, AS WELL AS
ALL CURRENT STANDARDS, CODES AND PRACTICES AS REQUIRED BY NEC 2020, NEMA, ANSI, NFPA, UBC, UL, IEEE, AND UTILITY
COMPANY STANDARDS.
3.
ALL EQUIPMENT, MATERIALS, AND WORK SHOWN ARE NEW UNLESS SPECIFICALLY NOTED AS EXISTING OR NOTED OTHERWISE ON
OTHER SHEETS.
4.
VERIFY EXACT LOCATION OF ALL RECEPTACLES ABOVE OR ADJACENT TO COUNTERS, FIXTURES, MIRRORS OUTDOOR FIXTURES
AND MOUNTING HEIGHTS AND LOCATIONS OF ALL FIXTURES AND BOXES PRIOR TO ROUGH-IN. NO EXTRA COSTS WILL BE ALLOWED
FOR FAILURE TO COMPLY.
5.
ANY POWER OUTAGE OF ANY CIRCUIT SHALL BE APPROVED BY THE OWNER IN WRITING A MINIMUM OF TWO WEEKS PRIOR TO
OUTAGE. ALL OUTAGES SHALL BE DONE EXACTLY WHEN DETERMINED BY THE OWNER AND DONE BEFORE OR AFTER WORKING
HOURS AND ON WEEKENDS. NO SINGLE OUTAGE SHALL REQUIRE MORE THAN 4 HOURS. PROVIDE TEMPORARY POWER, HEAT AND
COOLING AS REQUIRED DURING OUTAGE.
6.
DUE TO THE REQUIREMENTS TO INTERFACE WITH EXISTING FACILITIES AND UTILITIES, IT IS REQUIRED THAT THE CONTRACTOR
VISIT THE SITE TO DETERMINE EXISTING CONDITIONS PRIOR TO BID.
7.
PRIOR TO PURCHASE OF ANY PANEL, PROTECTIVE DEVICES, SWITCH, STARTER, CONDUIT, WIRE, ETC., TO FEED ANY PIECE OF
MECHANICAL EQUIPMENT, VERIFY THE VOLTAGE, PHASE, AND LOAD OF THAT ITEM IN THE FIELD AND/OR WITH THE PARTICULAR
ENTITY INVOLVED IN FURNISHING THE ITEM SUCH THAT THE PROPER SIZE & RATING OF THE MATERIALS ARE PURCHASED. NO
EXTRAS WILL BE ALLOWED FOR FAILURE TO COMPLY. THIS APPLIES TO ALL EQUIPMENT UNDER OTHER SECTIONS & BY THE
OWNER.
8.
ALL RECEPTACLES SHALL MATCH THE MALE PLUG CONNECTOR OF ALL EQUIPMENT PROVIDED. VERIFY PRIOR TO PURCHASE. SEE
GENERAL NOTE 7.
9.
PULL ROPES: PROVIDE 300 POUND PULL WIRE OR NYLON EQUIVALENT IN ALL INTERIOR EMPTY CONDUIT RUNS. PROVIDE 1/4" DIA
NYLON PULL ROPE IN EACH EMPTY EXTERIOR CONDUIT OR DUCT.
10. COORDINATE WITH MECHANICAL CONTRACTOR TO AVOID CONFLICTS BETWEEN DUCT WORK, SUPPLY & EXHAUST DIFFUSERS,
LIGHTING, SOUND SYSTEMS, AND FIRE ALARM SYSTEM FIXTURES.
11. ELECTRICAL CONTRACTOR SHALL GUARANTEE THE ELECTRICAL WORK TO BE FREE FROM DEFECTS IN MATERIALS AND
WORKMANSHIP FOR A PERIOD OF TWO YEARS FROM DATE OF FINAL ACCEPTANCE.
12. VERIFY THE EXACT LOCATION AND ELEVATION OF ALL ELECTRICAL EQUIPMENT PRIOR TO ROUGH-IN. FINAL CONNECTIONS OF
EQUIPMENT SHALL BE PER MANUFACTURERS APPROVED WIRING DIAGRAMS, DETAILS, AND INSTRUCTIONS. THE ELECTRICAL
CONTRACTOR SHALL PROVIDE MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENT ACTUALLY SUPPLIED.
13. ORDER AND/OR RELEASE ORDERED MATERIALS PROMPTLY AFTER SUBMITTAL APPROVAL. NO SUBSTITUTIONS OR ALTERNATE
METHODS OF INSTALLATION WILL BE ACCEPTED FOR FAILURE TO ORDER MATERIALS IN A TIMELY FASHION.
14. OBTAIN WRITTEN APPROVAL FROM THE ENGINEER OF ALL SHOP DRAWINGS AND MANUFACTURERS DATA FOR PANEL BOARDS,
TRANSFORMERS, WIRING DEVICES, ETC. BEFORE RELEASING ORDERED MATERIALS. SUBMITTAL DATA SHALL INDICATE THAT THE
CONTRACTOR HAS REVIEWED THE INFORMATION THEREIN AND THAT THE PROPOSED EQUIPMENT WILL MEET THE PHYSICAL
CONSTRAINTS AT THE JOB SITE. ANY SUBSTITUTIONS SHALL BE OF THE EQUIVALENT OR BETTER QUALITY THAN THE SPECIFIED
COMPONENTS.
15. TYPE MC OR TYPE AC CABLE SHALL ONLY BE USED WITH THE SPECIFIC WRITTEN PERMISSION OF THE PROGRAM/PROJECT
MANAGER. ENT TYPE CONDUIT IS NOT ALLOWED.
16. CONDUIT/CONDUCTOR RUNS SHOWN ARE DIAGRAMMATICAL ONLY. THE BEST FINAL CONDUIT ROUTING SHALL BE AS DETERMINED
BY THE ELECTRICAL CONTRACTOR AT THE TIME OF CONSTRUCTION.
17. ALL WIRE SHALL BE COPPER. MINIMUM SIZE FOR POWER WIRING SHALL BE #10 AWG. STRANDED UNLESS OTHERWISE NOTED.
MINIMUM SIZE FOR CONTROL WIRING SHALL BE #14 AWG.
18. PROVIDE ALL PANEL BOARDS WITH TYPED DIRECTORIES INSTALLED UNDER A CLEAR PLASTIC COVER. SUBMIT DIRECTORY
INFORMATION TO THE OWNER FOR APPROVAL PRIOR TO FINALIZATION.
19. SERIES RATING OF UPSTREAM OR DOWNSTREAM CIRCUIT BREAKERS OR FUSES IS PROHIBITED. ONLY FULLY RATED SYSTEM
COMPONENTS WILL BE ACCEPTED.
20. PROVIDE ALL TRENCHING, EXCAVATION, BACK FILLING, SHORING, PUMPING, COMP ACTION TEST ETC. THAT ARE REQUIRED FOR
THE SCOPE OF ELECTRICAL WORK.
21. ALL PANEL BOARDS, SWITCHES, MOTOR STARTERS, AND SWITCHBOARD CIRCUIT BREAKERS SHALL HAVE ENGRAVED MICARTA
NAMEPLATES.
22. ALL CIRCUITS THAT SHARE A NEUTRAL SHALL BE PROVIDED WITH MULTIPOLE BREAKER.
23. PROVIDE CIRCUIT BREAKER LOCK LOCKED IN THE 'ON' POSITION FOR ALL CIRCUITS SERVING EMERGENCY LIGHTING.
24. ALL EMERGENCY FIXTURES SHALL BE ALWAYS ON AS NIGHT LIGHTS AND WIRED TO THE UNSWITCHED HOT LEG OF THE CIRCUIT.
25. ALL ANALOG INSTRUMENTATION WIRING SHALL BE SHIELDED.
26. IN ADDITION TO SURFACE RACEWAY AND/OR FLOOR MOUNTED OUTLET BOXES AND POWER POLES INDICATED ON ELECTRICAL
DRAWINGS, THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CABLE TRAY AND FLUSH MOUNTED OUTLET BOXES/BACK BOXES
AND ASSOCIATED CONDUIT FOR ALL TELECOMMUNICATIONS OUTLETS (INCLUDING PA/MASTER CLOCK/SOUND SYSTEMS,
CATV/VIDEO SYSTEMS, AND SECURITY SYSTEMS) ON THIS PROJECT.
Compliance Data
The following are the primary codes under which this project is
designed and permitted
CODE
APPLICABLE CODE BOOK AND YEAR
BUILDING CODE
ELECTRICAL
ENERGY
ACCESSIBILITY
2023 FBC (IBC 2018 with Amendments)
2020 National Electrical Code
IECC 2021 with Amendments
2021 IBC - Chapter 11
FIRE ALARM
2023 Florida Fire Prevention Code
201 N FRANKLIN ST
SUITE 1400
TAMPA, FL 33602
PHONE: 813.620.1460
REGISTRY NO. 35106
This document is an instrument of service prepared
solely for Kimley-Horn's client and for a particular
purpose. Any other use or reliance is without liability to
Kimley-Horn.
JIMMY NGUYEN
PE 91973
ARCH/ENGR OF RECORD
DESIGNED BY
JN
DRAWN BY
JNJ
ISSUE DATE
03/19/2026
AE PROJECT NUMBER
145642004
SHEET TITLE
ELECTRICAL SYMBOLS,
ABBREVIATIONS, AND
NOTES
DRAWING NO.
E000