General Information
-
Contract Opportunity Type: Sources Sought (Original)
-
Original Published Date: Sep 03, 2025 10:56 am PDT
-
Original Response Date: Sep 10, 2025 01:00 pm PDT
-
Inactive Policy: Manual
-
Original Inactive Date:
Nov 09, 2025
-
Initiative:
Classification
-
Original Set Aside:
-
Product Service Code: J046 - MAINT/REPAIR/REBUILD OF EQUIPMENT- WATER PURIFICATION AND SEWAGE TREATMENT EQUIPMENT
-
NAICS Code:
-
561210 - Facilities Support Services
-
Place of Performance:
,
Description
This is a SOURCES SOUGHT ANNOUNCEMENT ONLY
The intent of this Sources Sought Announcement is to assist in our decision-making process for services procurement. This is not a solicitation, nor request for quotes or proposals. Through the receipt of responses, this will enable a more precise type of procurement process. The Government is not obligated to, nor will it pay for or reimburse any costs associated with responding to this sources sought synopsis request. This notice shall not be construed as a commitment by the Government to issue a solicitation or ultimately award of a contract, nor does it restrict the Government to a particular acquisition approach. Any inquiries are to be made in writing by email to the point of contact, Larry Facio, Contracting Officer. Responses to this notice shall be sent by email to larry.facio@va.gov by the due date and time of 09/10/2025 by 1:00 p.m. (Pacific Time). Upon receipt of capabilities statement, Contracting Officer may request additional market research aid such as informal pricing.
Place of Performance:
VA Southern Nevada Healthcare System (VASNHS)
6900 North Pecos Rd, N.
Las Vegas, NV 89086
DESCRIPTION OF SERVICES/GENERAL INFO
1.0. SCOPE OF WORK
VA Southern Nevada Healthcare System (VASNHS) is contracting water treatment services as well as the cleaning of 4 water storage tanks that provide a complete service-oriented water treatment, sampling, disinfect/cleaning and test program that supplies steam, chilled water service, domestic, industrial water and heating water service loops which include a solar heating loop. This contract is specifically for all industrial systems and all 4 water storage tanks. Access to these systems is located VA Medical Center Buildings 1, 2, 5, & 6. The contractor shall supply a complete service oriented water treatment program. A major component of maintaining equipment involves chemical treatment, real time monitoring, and water sampling. The contractor shall provide trained, qualified and certified personnel to perform required tasks. In addition, contractor shall provide all the necessary equipment, tools, materials, supervision, repair, replacement, and other services necessary to perform water treatment services at VASNHS facilities as defined in this Statement of Work (SOW) for Government-owned equipment. Services shall be provided at the VASNHS medical center, located at 6900 North Pecos Road, North Las Vegas, NV 89086. The contractor shall perform in accordance with all federal, state, and local regulations.
Specific Requirements for Industrial Water:
1.1.2 The water treatment program shall service steam boilers, chillers, chilled water system, open condenser water loops, 9 closed hot water heating loops, a refrigeration condenser loop, and a Glycol energy recovery loop, along with all associated piping for the equipment listed below. This list is not all inclusive of the Government owned equipment that may require monitoring, testing, or other services associated with the overall treatment program. Contractor is to supply all equipment and services for real time monitoring of HVAC Cooling Tower open loop.
Chilled Water:
Global GTCHB2234F2615PC Side-stream Filter with MS30ES20 filter cartridges.
Cooling Tower (Condenser Water):
In-Line, Real-Time monitoring system controlling 3 LMI metering pumps and condenser water bleed valve.
Puroflux PF64-060(B) centrifugal separator
Glycol:
Neptune 141-GFS251A.88
Steam/Condensate:
The steam system has three LMI chemical metering pumps for the Boiler treatment, sulfite, phosphate and amine . Feed rates are set manually based on feed water / condensate testing by the operator.
Each boiler is equipped with a pot feeder for start-up/emergency treatment. The other systems are manually dosed with pot feeders.
1.2 FREQUENCY OF SERVICE & TEST REQUIREMENTS
1.2.1. The following charts denote the frequency of service and testing requirements.
1.2.1.1 Specific System: Cooling Tower System, Open Loop, Building 2.
Control
Parameters
Analytical
Method
Target
Range
Service Report Test
Frequency
pH, Makeup Water
PH meter
Record
Weekly
pH, System Water
PH Meter
8.0-9.0
Weekly
Conductivity, Makeup
Conductivity Meter
Record
Weekly
Conductivity,
System Water
Conductivity Meter
2400 ppm TDS
Weekly
Corrosion Inhibitor
Colorimetry
15 30 ppm
Weekly
Calcium, Makeup
Water
DR890-PRG29
Record
Weekly
Calcium, System Water
DR890-PRG29
Weekly
Steel Corrosion
Inhibitor (Active Polymer)
DR890 PRG181
6-8ppm
Weekly
Iron
DR890-PRG33
Weekly
Free Halogen (Chlorine)
Biocide
DR890-PRG 90
0.05-0.5 ppm
Weekly
Bacteria:
Total Heterotrophic
Dip-slides
10^3-10^4 cfu/ml
Weekly
Bacteria:
Sulphate Reducing
Analytical Lab Sample
ND
Semi-Annual
Bacteria:
Iron Related
Analytical Lab Sample
ND
Semi-Annual
Steel Corrosion
Inhibitor (Specify)
Coupons
Semi-Annual
Copper Corrosion
Inhibitor (Specify)
Coupons
Semi-Annual
ND = non detect
Note: Include tests for control parameters, from Program Calculation Sheet, Appendix A
1.2.1.2 Specific System: Chilled Water (Closed), Refrigerant Condenser Loop, Glycol Energy Recovery System, and Hot Closed Systems, Buildings 1, 2, 5, 6 . See Appendix D & E
Control
Parameters
Analytical
Method
Target
Range
Service Report Test
Frequency
Corrosion Inhibitor (Nitrite)
Titration
600-800 ppm
Weekly
pH
PH Meter
Weekly
Monthly for hot
Conductivity
Conductivity Meter
Record
Weekly
Monthly for hot
Steel Corrosion
(Specify)
Coupons
Quarterly
Copper Corrosion
(Specify)
Coupons
Quarterly
Iron
(Total)
DR890-PRG33
Weekly
Monthly for hot
Copper
(Total)
DR890-PRG22
Weekly
Monthly for hot
Bacteria:
Total Heterotrophic
Dip-slide
Monthly
Bacteria:
Sulfate Reducing
Analytical Lab Sample
ND
Semi-annual
Bacteria:
Iron Related
Analytical Lab Sample
ND
Semi-annual
Bacteria: Nitrifying
Analytical Lab Sample
Minimal
Semi-annual
Bacteria: Denitrifying
Analytical Lab Sample
Minimal
Semi-annual
ND = non detect
Note: Include tests for control parameters, from Program Calculation Sheet, Appendix A
1.2.1.3 Specific System: Steam Boiler System, Building 2.
Control
Parameters
Analytical
Method
Target
Range
Service Report Test
Frequency
Makeup Water pH
PH meter
Record
Weekly
Makeup Water Conductivity
Conductivity Meter
Record
Weekly
Makeup Water - Hardness
Drop Test
Record
Weekly
Makeup Water Total Alkalinity
DR890-PRG29
Record
Weekly
Feedwater Hardness
Drop Test
0-2 ppm
Weekly
Feedwater Iron
DR890-PRG33
Weekly
Feedwater pH
PH meter
8.3-10.5
Weekly
Feedwater Conductivity
Conductivity Meter
300 µmhos
Weekly
Feedwater P Alkalinity
Titration
Record
Weekly
Feedwater M Alkalinity
Titration
Record
Weekly
Feedwater Boiler Treatment
DR890-PRG181
20-25ppm
Weekly
Boiler P Alkalinity
Titration
Weekly
Boiler M Alkalinity
Titration
Weekly
Boiler Oxygen scavenger Residual
Sulfite low level test kit
30-60 ppm
Weekly
Boiler Conductivity
On-Line Conductivity Meter
Weekly
Boiler Neutralized Conductivity
DR890-PRG29
Boiler iron
DR890-PRG33
Weekly
Condensate - Conductivity
Conductivity Meter
Weekly
Condensate pH
PH meter
8.0-10.0
Weekly
Condensate Hardness
Drop Test
0-1 ppm
Weekly
Condensate Iron
DR890-PRG33
Weekly
ND = non detect
Note: Include tests for control parameters, from Program Calculation Sheet, Appendix A
1.2.1.4 Industrial Water Systems
System
Location
Analytical
Test Method
Service Report Test
Frequency
Water Tank #1
Water Tank Yard
A, B, C, E, F
Monthly
Water Tank #3
Water Tank Yard
A, B, C, E, F
Monthly
Water Tank #4
Water Tank Yard
A, B, C, E, F
Monthly
Cooling Towers
BLD 2
A, B, C, D,E, F
Weekly
Industrial Water System
Bldg 2, Rm 2-110
A, B, C, D, E
Monthly
1.2.1.5 Industrial Water System Analytical Test Method:
A. Chlorine residual, Free/Total; DPD Colorimeter USEPA (Hach Field Test)
B. Conductivity / TDS; Ultrameter II Conductivity Meter
C. PH; Ultrameter II PH Meter.
D. Hardness; Drop Test, Titration
E. Water Temperature, Ultrameter II, or Contact Thermometer.
F. Dip-slide, Heterotrophic Bacteria, & Mold Indicating
1.2.2. METHOD OF TREATMENT
1.2.2.1. The contractor shall provide water treatment products to prevent scale, corrosion, fouling and microbiological fouling within all heating, chilled, and cooling water systems.
1.2.2.2. Water treatments shall be performed as indicated by testing on each system in all buildings.
1.2.2.3 Sodium Nitrite, or other corrosion inhibitor, applied to closed loops shall always include Leak Detection Dye.
1.2.2.4. Evaluate the flows, pressure and Total Dissolved Solids (TDS), weekly.
1.2.2.5. Cooling towers shall be treated by acid or soft water blend control. See Appendix B for system.
1.2.2.6 Delivery of all water treatment chemicals to points-of use shall be placed on spill containment pallets. It is the contractor s responsibility to ensure all safety precautions for chemicals have been taken.
1.2.2.7 Chemical Tanks - The tanks MUST provide the following features:
Tank level indicators to determine chemical levels.
Flooded suction inlets for chemical pumps to ensure pumps do not loose prime, or provide self-priming pumps.
Containment basins capable of 150% of the tank storage capacity.
Tank sizing shall be appropriate for chemical use; chemical shall be a minimum quantity of 31 days without replenishment.
Chemical labels clearly visible on outside of tank.
SDS sheets attached to tank container.
Tank to tank chemical transfer preferred, when pumping from drums, empty drums shall be removed from VAMC property within 3 working days.
Full spill containment.
1.2.2.7.1 Liquid chemicals shall be stored on site in Mini Porta Feed or equal containers. Containers shall be stainless steel or double walled polyethylene tanks as appropriate. Containers shall be supplied and maintained by the water treatment contractor.
1.2.2.7.2 All chemicals shall be directly injected in to their respective loops via corporation stop injectors whenever provided. Pot feeders are available at the boilers (start-up), and all closed loops.
1.2.3. TESTS
1.2.3.1. Routine Testing. The routine Cooling Tower testing to be performed according to the chart in 1.2.1.1, Closed Loops according to 1.2.1.2 and Boiler testing performed according to chart in 1.2.1.3. which will provide results showing:. Total Hardness, P Alkalinity, M Alkalinity, OH Alkalinity, Total Alkalinity, pH, Conductivity/TDS, Silica, Phosphates/orthophosphates, Nitrite, Calcium Hardness, Free Chlorine, Sulfite, Iron and Copper. Routine testing by the Contractor shall also provide services as listed in Appendix B and C. The contractor shall submit documentation of results and recommendations accurately and within required timeframe in accordance with Paragraph 1.2.10.1.
1.2.3.2. Weekly water tests and treatment for each operating system in building 2 shall provide:
Boilers and Steam:
Orthophosphate (PO4) (Operating Boiler s water)
Sodium Sulfite (SO3) (Operating Boilers)
P-Alkalinity (Operating Boiler s water)
Conductivity (µmhos/cm) (Operating Boiler s water and Feed Water)
Total Hardness, pH, iron, and conductivity (Feed Water, Condensate, High Pressure Drain, Condensate from Bldg 1.
Add neutralizing amine blend to treatment tank, for injection into steam header outlet piping.
Determine gallons/day feed rate for sodium polymethacrylate* and add to proper tank with proper adjustments to feed rate. (*or recommended chemical.)
Add sodium sulfite in chemical feed tank for feedwater treatment.
Add sodium hexametaphosphate*, caustic flake*, and adjustments for feed rates to boiler chemical feed tanks. ( *or recommended chemical).
Sodium Nitrite added to (Hot & Chilled) closed loops to provide protection of metal piping and maintain residual.
Cooling Tower / Open Condenser Loop:
Organophosphonate
Oxidizing and Non-Oxidizing Biocides
1.2.4. STANDARDS. The contractor shall inspect, monitor and document the cooling water characteristics for a stable condition. Conductivity Total Dissolved Solids (TDS) range shall be maintained within 2000 to 2500 µmhos/cm. The contractor shall conduct weekly total bacteria count tests on cooling tower water samples utilizing a dip-slide culture test. ORP measurements will be taken on condenser water to verify relationship between Biocide effective ness and corrosion of tower metal, maintain range of 250 to 450 mV. The contractor shall use test results to change or optimize the biocide feed rates and the timing of the biocide feed applications to maintain bacteria counts at 10,000 CFU/mL or less. The bacteria count, determined by dip-slide culture, shall be reported weekly on the service trip report and provided accordingly to 1.2.10.1.
1.2.4.1. The following standards apply to each operating system in building 2 and shall be on contractor s report. The contractor shall maintain systems within the standards listed in paragraph 1.2.4:
Boilers
Phosphate (PO4) = 15 25 PPM
P-Alkalinity (CaCO3) = 300 600 PPM
Sulfite (SO3) = 30 60 PPM
Neutralized Conductivity (µmhos/cm): 3000-3500
Boiler PH = 10.5 12.0 PPM
Condensate:
PH = 8.3 9.2 SU
Conductivity=
Sodium Softeners: (Hardness Maximum) 1 PPM or 7.1 grains
Low Temperature Hot Water Heat (HWH) the following standards apply:
Nitrite = 1000-1500 ppm in nitrite. Test and record pH, conductivity, iron, copper.
Chilled Water the following standards apply:
Nitrite = 600-800 ppm as nitrite. Test and record pH, conductivity, iron, copper.
Contractor shall clean and replace Side-Stream filters as necessary.
Open Condenser Loop (Cooling Towers) the following standards apply:
Conductivity= 3200 µmhos / TDS= 2400 ppm
Organophosphonate = 15 30 ppm, PTSA trace = 160 170
Biocide = .05 0.5 ppm
1.2.5. MONITORING. The contractor shall inspect, monitor and document each system listed in Appendix B, C, D, & E. to measure effectiveness of the treatment program. The contractor shall inspect, monitor and document the below mentioned conditions. Results shall be documented IAW Section 1.2.10 and provided to COR.
Scale formation onto waterside surfaces
Corrosion of waterside metal surfaces
Slime producing bacteria within the bulk water (dip-slide test)
Make-up water rate
Bleed-off/Blowdown rate
Chemical treatment feed rates
1.2.6. INSPECTIONS
1.2.6.1. The contractor shall perform weekly inspections of the cooling tower, boilers and heat exchange systems to include: chemical feed equipment, chemical feed point locations, and sampling locations. This shall include weekly inspections of the side-stream filter installed in the condenser water system . Adjustments shall be made to backwash timing and frequency. Results and recommendations shall be documented IAW Section 1.2.10.1 and provided to COR.
1.2.6.2. The contractor shall conduct internal and external inspections of steam generation equipment during seasonal shutdowns and perform external inspections when the steam generation equipment is on-line.
1.2.6.3. The contractor shall inspect and document all waterside surfaces of opened heat exchangers and chillers for proper water treatment according to the type of system, its size and location . Inspection results shall include: the tube sheet, end bells, water box, and the end of the tubes.
1.2.7. REVIEWS AND ANALYSIS.
1.2.7.1. The contractor shall conduct a review and analysis of cooling and heating system operating logs and cooling tower including side-stream filters, heat exchangers, and closed system water treatment testing logs. The Contractor shall maintain an electronic data-site of all information. Trend analysis data generated using software shall be included in the Quarterly Report IAW 1.2.10. The contractor shall identify, document correctly, and submit to the COR, quarterly, any potential problem areas and assess trends of chemical consumption, costs, and residuals.
1.2.7.2. The contractor shall document results and recommendations for purposes of long-range planning. Documentation shall be IAW Section 1.2.10.3 and provided to COR.
1.2.7.3. The contractor shall provide actual values of: Bleed-off/Blowdown, Make-up, Drift, Cycles of concentration, and Chemical Feed Rates. The contractor shall document and compare values to theoretical values, and industry standards. The Contractor shall make recommendations to the government to optimize operations. All final decisions are by the government. Documentation shall be IAW Section 1.2.10.3.
1.2.7.4. The contractor shall document the collection of and analyze scale and other deposits found in the system. Results and recommendations shall be IAW Section 1.2.10.3 and provided to COR.
1.2.7.5. Condensate Quality Profile. A Quality Profile shall be created and documented for each condensate stream. Information and targeted performance guidelines shall include:
pH (properly cooled) 8.0 9.0
Iron Conductivity This data shall be reported quarterly IAW Section 1.2.10.2, report shall include all corrective action taken and provided to COR.
1.2.8. STUDIES. The contractor shall perform and document the following studies:
1.2.8.1. Corrosion Studies. Documented Corrosion studies shall include maintain continuous exposure periods for 90 days, conduct coupon analysis, review results and changes in the water treatment program to maintain acceptable Cooling Technology Institute (CTI) standards for Mild Steel Corrosion Rate (1.2.8.2. Annual Flow Rate and Elusion Studies. The contractor shall provide flow rate and elusion studies on ion exchange equipment to evaluate: Operation, Mechanical Status and Efficiency.
1.2.9. BOILER FEEDWATER (BFW)
1.2.9.1. The contractor shall evaluate the overall Boiler Feed water (BFW) program for compliance with American Society of Mechanical Engineers (ASME) and Cooling Technology Institute (CTI) control parameters and operational procedures, Federal and State of Nevada Environmental Protection Agency regulations and environmental compliance issues. The contractor shall inform the government orally and in writing quarterly and annually of all compliance problems associated with the operation of the industrial water treatment program.
1.2.9.2. Evaluate and report, the boiler feed water characteristics to establish siteline data within the first month of contract.
1.2.9.3. Maximum cycles of concentration (no cycles to exceed 20) sited on the following ASME Guidelines: The contractor shall calibrate Government chemical feed and control equipment to maintain water chemistry within industry specifications. Calibration of all monitoring equipment shall be performed accurately and at specified frequency. The calibration results shall be documented and available to COR as requested.
1.2.10. REPORTS AND OTHER DOCUMENTS. The contractor shall send a copy of reports to the Contracting Officer Representative (COR). All urgent problems regarding maintenance of water treatment parameters shall be discussed with the COR on the day of discovery referenced in 1.3.5.2. All reports shall be submitted electronically to the Facility COR.
1.2.10.1. Weekly reports. The contractor shall prepare a written report each week. This report shall describe the results of routine tests (Section 1.2.3.1), the results of system inspections (Section 1.2.6). The reports shall contain recommendations and written proposed corrective actions. The contractor shall review the report with the COR/CO within seven (7) calendar days of data collection.
1.2.10.2. Quarterly reports. The contractor shall prepare a quarterly written report, accurately and on time, due by the 15th of Jan, Apr, Jul, and Oct. This report shall describe conditions of each water system. The reports shall include those items discussed in Section 1.2.5 and the effectiveness of the treatment program and any areas of concern/problems incurred with recommendations for correction. The report shall include all chemical usage (Volume) by the contractor. The contractor shall conduct meeting with the COR and go over the Quarterly report.
1.2.10.3. Annual Reports. An annual report shall be compiled and submitted by the last day of the 11th month of each contract year, for each industrial water system. Each report shall describe sampled trends throughout the year, start and end conditions, and those items identified in Sections 1.2.7 through 1.2.9. The report shall include total yearly chemical usage by the contractor. The contractor shall meet with the COR and affected Contracting Officer and go over the Annual report.
II. SERVICES SUMMARY.
2.1. Â Â Â Â Performance Requirements Summary
2.1.2 Summary Table:
Performance
Indicator
Performance Standard
Performance Threshold
Method Type of
Surveillance
Reference
Cooling Tower Treatment
Maintain Treatment levels
Maintain levels in accordance with parameters in Table 1.2.1.1 to
a 90% accomplishment
Weekly testing
1.2.4
Chilled Water System Treatment
Maintain Treatment levels
Maintain levels in accordance with parameters in Table 1.2.1.2 to a 90% accomplishment
Weekly testing
1.2.4.1
Closed Loop Treatment
Maintain Treatment levels, perform coupon checks
Maintain levels in accordance with parameters in Table 1.2.1.2 to a 90% accomplishment
Monthly testing. Quarterly coupon change-out, submitted for analysis
1.2.4.1
Boiler Water Treatment
Maintain Treatment levels, Recommend changes to chemical pumps and blowdown settings
Maintain levels in accordance with parameters in Table 1.2.1.3 to a 90% accomplishment
Weekly testing
1.2.4.1
Records and Report Management
Reports filled out timely and delivered to Utility Supervisor or COR
Weekly within 7 days of collection.
Monthly Within 7 days of collection.
Quarterly on time.
Annually Before end of contract. To a 100% accomplishment
Meetings with COR, one on one.
1.2.10
Inspections
Inspect Cooling Towers, Boilers, and Heat Exchangers during maintenance periods
Check for indications of corrosion, under-treatment, over-treatment. Make recommendations that show results.
COR to attend inspections
1.2.6
Inventory Management
Sufficient testing and treatment materials on site to ensure plant condition not affected
All treatment levels in all systems maintained to a 90% accomplishment.
Daily checks by COR, contractor notified by email of low levels or missing items
1.0
Appendix B
*The procedures set forth in the Inspection of Services Clause will be used to remedy all deficiencies. The re-performance times will be sited upon sensitivity of the issue.
ORP Oxidation Reduction Potential, measurement of the tendency of a chemical substance to oxidize or reduce another chemical substance. Has a relationship to Biocide reactions.
Welch-Allyn fiber optic inspection. A high-level inspection system that examines tube bundles in great detail to determine if gross deficiencies in water treatment exist.
High Temperature Hot Water (HTHW). Heating system water that is generally circulated at temperatures from 320 to 440 degrees.
Condensate. Condensed water resulting from the removal latent heat from steam.
Deaerator Oxygen Analysis. A study to determine the oxygen removal efficiency of the deaerator. The collected data assists in predicting the potential for oxygen related problems in the feedwater and boiler system(s).
Embrittlement Analysis. A study of the embrittling characteristics of the boiler water.
Controlled Limits. Operating parameters (boundaries)
Elution Studies on Ion Exchange Equipment. A series of tests conducted on the softeners, dealkalizers or demineralizers to determine the efficiency of the regeneration cycle. The collected data is evaluated by drawing an elution curve. The information reveals the regenerate concentrations at all stages of the cycle.
Steam Purity Analysis. A study monitoring the quality of the steam being produced to determine the steam purity.
Corrosion Studies on Feedwater/Condensate Systems. A study to determine the corrosion rates of the pre-boiler systems. The collected data provides information relating to the corrosion protection provided by the chemical treatment program.
Quantitative Deposit Analysis. A study to determine the composition of a deposit.
Resin Analysis. A study generally performed to determine the efficiency of zeolite resin in water.
Appendix B
Cooling tower tonnage, Building 2
Building Number
Capacity in Approx Tons
Sidestream Filters
Tower Treatment
Operation
2
6,500
N/A
Acid or Softwater Blend
Year Round
HVAC main cooling tower open loop
The water treatment program shall include all cooling tower systems and all water pre-treatment equipment. The water treatment program shall include all chemical products, equipment, tools, supervision, professional consulting services, and any additional items necessary to perform the services as specified in the SOW.
The cooling towers consist of five cells.
The water treatment program shall provide control and remote monitoring capability for the following:
Controller capable of the following features:
Monitor system conductivity
Monitor system pH
Monitor system ORP, Oxidation Reduction Potential
Flow switch
Chemical levels in chemical feed tanks/containers
Monitor makeup water use (via contacting head water meter)
Monitor blow down water use (via contacting head water meter)
Receive 4-20mA inputs and provide direct control of system parameters based on input signals.
Provide data logging features, with download capability to a PC via Ethernet or wireless network
Real-Time monitoring of scale/corrosion inhibitor levels in the cooling tower systems whenever they are running.
Real-Time monitor for both planktonic (free flowing) and sessile (attached) microbiological activity in re-circulating cooling water systems.
Multiple controller inputs
Multiple controller outputs
Online corrosion monitors to log corrosion data Real-Time so that immediate chemistry changes can be made.
Appendix C
Building 2 Systems, and Equipment
Boilers:
Three natural gas fired, 25,000 pound per hour, fire tube, 100 PSIG
Domestic Water:
3 sodium zeolite softeners.
3 charcoal bed filters.
Condensate Return:
One condensate receiver
Deaerators:
One 20,000 pound per hour, spray and tray type
Feedwater Pumps:
Three electric driven pumps
Boiler Chemicals Currently Used:
Sodium Bisulfite
Sodium Sulfate
Cyclohexylamine
Diethylethanolamine
Morpholine
Potassuim Bisulfite
Cobalt Sulfate
Methanol
Sodium Hydroxide
Glutaraldehyde
Alkaline Liquid Bromine
HVAC HOT WATER SYSTEM (Closed Loop)
Hot water system for heating and reheat of HVAC systems. Water is continuously circulated in a closed loop through heat exchangers to maintained temperature set-point. Building 1- five loops, building 2, Boiler room- one loop, building 5- one loop, Building 6- one steam heated loop and one solar heated loop. Systems must be closely monitored and sampled at least monthly; corrosion indicator coupons examined every 90 days. Water treatment shall be on an as needed basis to control any corrosion.
Appendix D
Building 1,2, 5 & 6 Systems and Equipment
1. HVAC HOT WATER SYSTEM (Closed Loop)
Hot water system for heating and reheat of HVAC systems. Water is continuously circulated in a closed loop through heat exchangers to maintained temperature set point. Building 1- Four Loops: D&T Basement; Room BD-423 D&T, Ambulatory Basement; BB-208, Admin Basement; BD-160, MH Basement; BE-101, Emergency Department extension (roof-top). Building 2 one loop, Boiler Room, building 5- one loop, basement, building 6- one loop (steam heated) & one loop (solar heated), room to be determined (currently under construction). Systems must be closely monitored and sampled. Water treatment shall be on an as needed basis to control any corrosion and maintain proper residual.
2. REFRIGERANT CONDENSER WATER SYSTEM (Closed Loop)
Chilled water system for cooling the condenser water for freezers, and refrigerators. Water is continuously circulated in a closed loop through plate/frame heat exchangers to maintained temperature set point. Building 1, Fourth floor. System must be closely monitored and sampled. Water treatment shall be on an as needed basis to control any corrosion.
3. HVAC ENERGY RECOVERY SYSTEM (GLYCOL LOOP, 30%)
The glycol and water run-around coil system are an energy recovery system for the HVAC air handling units located in Building 1, on the fourth floor and the roof. All the individual water systems are combined into a single fill and chemical addition location. System shall be monitored, tested, and the water sampled to insure proper operation in accordance with manufacturers recommendations. All consumable products and supplies for this system shall be monitored, supplied, delivered and installed by the vendor.
4.HVAC SOLAR ENERGY HEATING SYSTEM
The Solar Energy Heating System for Building 6 is designed to capture heat from solar panels on the roof and use that heat through the closed loop system to heat up, directly or augment, the building heating/re-heat system. The solar heating system is integrated with the steam heating system utilizing the same circulating pumps and the same heat exchangers. Treatment must be sufficient in chemical nature to provide corrosion inhibitor to all piping, and freeze protection to the exposed panels/piping in colder months. System shall be monitored, tested, and the water sampled to insure proper operation in accordance with manufacturers recommendations. All consumable products and supplies for this system shall be monitored, supplied, delivered and installed by the vendor.
Appendix E
Chilled Water System
BUILDING
SYSTEM
Operation
Frequency
Side Filter
2
Chilled Water, Closed Loop
Five 1300-ton chillers
Year-round
Monthly
Yes
Water Storage Tanks
The Potable water storage tank will have a maintenance service accomplished annually, and the Industrial water storage tank will have a maintenance service accomplished every three years. The Contractor shall provide all labor, tools, supervision, and equipment necessary to complete this project. All the associated equipment is located at the VA facilities Water Storage Tank area and Central Energy Plant Building #2 at the Veteran s Hospital on 6900 North Pecos Rd, North Las Vegas, Nevada.
SPECIFIC REQUIREMENTS:
Water Storage Tanks (1ea. Potable water and 3ea. Industrial water total of 4ea. tanks)
Manufacturer: Storage Product Engineering
Model: 7013 WT
Storage Capacity: 360,000 gallons
This service contract is to clean and disinfect the water tanks according to American Water Works Association (AWWA) standards for disinfection process. Details of maintenance service are listed below. The contractor must minimize interruption of the water system to the medical center prior and during the service contract. If lengthy water systems service interruptions are needed, the interruption has to be scheduled two weeks prior to the start of the job. Furthermore, all interruptions are subject to approval by the Engineer Service Chief. The contractor must be authorized and approved to work, service, and make proper recommendations to resolve discrepancies with the Water Storage Tanks and associated components as recommended by manufacturer s recommendation as well as meet local and federal health standards and requirements. Lastly, the contractor will provide detailed documentation and cleaning certifications for the Water Storage Tank to suffice the annual requirements. This data will be provided to the Energy Plant supervisor or designee.
Tank Cleaning and chlorination process according to AWWA:
The Contractor shall provide all labor, tools, supervision, and equipment necessary to complete this project.
Methods of Chlorination
Three methods of chlorination are explained in this standard. Typically, only
one method will be used for a given storage-facility disinfection, but combinations
of the methods may be used. The three methods are (1) chlorination of the full
storage facility such that, at the end of the appropriate retention period, the water
will have a free chlorine residual of not less than 10 mg/L; (2) spraying or painting of all storage facility water-contact surfaces with a solution of 200 mg/L free chlorine.
and (3) a two-step process of chlorinating the bottom portion of the storage facility
with 50 mg/L free chlorine followed by filling to overflow with potable water. It
shall be held full for a period of not less than 24 h. In chlorinated systems,
achieving a free chlorine residual requires the addition of sufficient additional
chlorine to pass through breakpoint chlorination.
4.3.1 Chlorination method 1. The water-storage facility shall be filled to
the overflow level with potable water to which enough chlorine shall be added
to provide a free chlorine residual in the full facility of not less than 10 mg/L
at the end of the appropriate 6-h or 24-h period, as described in Sec. 4.3.1.4.
This method should be evaluated to assess its appropriateness for chloraminated
systems. For chloraminated systems, additional chlorine may be required to
achieve a free chlorine residual of 10 mg/L. The chlorine, either as liquid chlorine,
sodium hypochlorite, or calcium hypochlorite, shall be introduced into the water
as described in the following subsections.
4.3.1.1 Liquid-chlorine (gas) use. Liquid chlorine (gas) shall be introduced
into the water filling the storage facility in such a way as to give a uniform chlorine
concentration during the entire filling operation. Portable chlorination equipment
shall be carefully operated and shall include a liquid-chlorine cylinder, gas-flow
chlorinator, chlorine ejector, safety equipment, and an appropriate solution tube to
inject the high-concentration chlorine solution into the filling water. The solution
tube shall be inserted through an appropriate valve located on the inlet pipe and
Copyright © 2020 American Water Works Association. All Rights Reserved
Accessed by account: Vir. Dept. of Health-Office of Drinking Water | User: Sarah Hinderliter | Date: Wed Feb 10 12:42:04 2021 | IP address: 166.67.66.244
DISINFECTION OF WATER-STORAGE FACILITIES 7
near the storage facility such that the chlorine solution will mix readily with the
influent water.
4.3.1.2 Sodium hypochlorite use. Sodium hypochlorite shall be added to
the water entering the storage facility by means of a chemical-feed pump or shall be
applied by hand-pouring into the storage facility and allowing the influent water to
provide the desired mixing.
4.3.1.2.1 When a chemical-feed pump is used, the concentrated chlorine
solution shall be pumped through an appropriate solution tube to inject the
high-concentration chlorine solution at a rate that will give a uniform chlorine
concentration in the filling water. The solution tube shall be inserted through an
appropriate valve located on the inlet pipe and near the storage facility, or through
an appropriate valve located on the storage facility such that the chlorine solution
will mix readily with the filling water.
4.3.1.2.2 When sodium hypochlorite is poured into the storage facility,
the filling of the storage facility shall begin immediately thereafter or as soon as
any removed manhole covers can be closed. Sodium hypochlorite may be poured
through the cleanout or inspection manhole in the lower course or level of the
storage facility, in the riser pipe of an elevated tank, or through the roof manhole.
Sodium hypochlorite shall be poured into the water in the storage facility when the
water is not more than 3 ft (0.9 m) in depth, nor less than 1 ft (0.3 m) in depth or
as close thereto as manhole locations permit.
4.3.1.3 Calcium hypochlorite use. Calcium hypochlorite granules
or tablets broken or crushed to sizes not larger than 1/4-in. (6.4-mm) maximum
dimension may be poured or carried into the storage facility through the cleanout
or inspection manhole in the lower course or level of the storage facility, into the
riser pipe of an elevated tank, or through the roof manhole. The granules or tablet
particles shall be placed in the storage facility before flowing water into it. The
granules or tablets shall be located so that the influent water will circulate through
the calcium hypochlorite, dissolving it during the filling operation. The calcium
hypochlorite shall be placed only on dry surfaces unless adequate precautions are
taken to provide ventilation or protective breathing equipment.
4.3.1.4 Retention period. After the storage facility has been filled with
the disinfecting water, it shall stand full as follows: (1) for a period of not less than
6 h when the water entering the storage facility has been chlorinated uniformly by
gas-feed equipment or chemical pump, or (2) for a period of not less than 24 h
when the storage facility has been filled with water that has been mixed with sodium
Copyright © 2020 American Water Works Association. All Rights Reserved
Accessed by account: Vir. Dept. of Health-Office of Drinking Water | User: Sarah Hinderliter | Date: Wed Feb 10 12:42:04 2021 | IP address: 166.67.66.244
8 AWWA C652-19
hypochlorite or calcium hypochlorite within the storage facility as described in
Sec. 4.3.1.2 and 4.3.1.3.
4.3.1.5 Handling of disinfection water. After the retention period stated
in Sec. 4.3.1.4, the free chlorine residual in the storage facility shall be reduced to
a concentration appropriate for distribution by completely draining the storage
facility and refilling with potable water, or by a combination of additional holding
time and blending with potable water having a lower chlorine concentration.
Following this procedure and subject to satisfactory bacteriological testing,
appropriate chlorine residual, and acceptable aesthetic water quality (as described
in Sec. 5.1), the water may be delivered to the distribution system.
Method to Follow:
The Contractor shall provide all labor, tools, supervision, and equipment necessary to complete this project.
4.3.3 Chlorination method 3. Water and chlorine shall be added to the storage facility in amounts such that the solution will initially contain at least 50 mg/L free chlorine and will fill approximately 5 percent of the total storage volume. This solution shall be held in the storage facility for a period of not less than 6 h. The storage facility shall then be filled to the overflow level by flowing potable water into the highly chlorinated water. It shall be held full for a period of not less than 24 h. Highly chlorinated water shall then be purged from the drain piping. Following this procedure and subject to satisfactory bacteriological testing, appropriate chlorine residual, and acceptable aesthetic water quality as described in Sec. 5.1, the remaining water may be delivered to the distribution system. It should be noted that the final chlorine residual may be either as free, total, or combined chlorine depending on the potable water characteristics.
4.3.3.1 Adding chlorine. Chlorine shall be added to the storage facility by the method described in Sec. 4.3.1.1, 4.3.1.2, or 4.3.1.3. In chloraminated systems, the addition of excess chlorine may be required to eliminate the combined chlorine and achieve the specified free chlorine residual (breakpoint chlorination).
4.3.3.2 For any chlorinated water discharges to the environment, refer
to ANSI/AWWA C655 Field Dechlorination, if dechlorination is required.
The environment into which the chlorinated water is to be discharged shall be
inspected. Federal, state or provincial, and local environmental regulations may
require special provisions or permits before disposal of highly chlorinated water.
Proper authorities should be contacted before disposal of highly chlorinated water.
Tank Specifications:
Tank Gallon Capacity for each tank. Â 360,000 gal
Tank Dimensions (Diameter x Height) for each tank 12 x 69 11-1/4
Tank Construction Type: (Steel Welded, Concrete, Poly... On grade, Buried or Elevated Tower or Standpipe) Fiber Glass with Edge Coat Process lining, on concrete foundation above ground
Tank Manway Access (At least a 24" diameter roof access hatch) Yes
Tank Equipment Access (Can a 20' trailer and truck come within 50\ of the tanks No, need hoses and pump to transfer water from tank to tank.
Discharge requirements (Can water and sediment from the cleaning process be discharged within 100' of the tank(s)? Yes. Water must be pump from tank to tank to minimize water loss.
The Contractor shall provide all labor, tools, supervision, and equipment necessary to complete this project.
Anticipated Performance Schedule:
Period of performance: October to November
Base year: clean potable storage tank only: October to November
Option year #1: clean all 4 storage tanks: October to November
Option year #2 & #3: clean potable storage tank only: October to November
Option year #4: clean all 4 storage tanks: October to November
Cost estimate: base on per tank cleaning will be funded
1.3.6. WORK HOURS
1.3.6.1. Normal Hours. The contractor shall perform the services required under this contract during the following hours: 0730-1600 HRS, Monday through Friday. The contractor may work, with prior approval of the Contracting Officer's representative, extended hours to ensure timely completion of work at no additional cost to the government.
1.3.6.2. Emergency Services. The contractor shall provide services to support emergency situations for the water treatment facilities 24/7. Contract service technician must be able to report to the Facility within 2 hours after request for emergency service.
1.3.6.3. Seasons. The heating season (Winter) is from 1 October to 31 May and the cooling season (Summer) is from 1 June to 30 September. The actual dates are sited on temperature. If changes in dates occur, the government will notify the contractor.
1.3.7.1. When a holiday falls on a Saturday, the preceding Friday shall be considered a holiday. When a holiday falls on a Sunday, the following Monday shall be observed. If a task, falls on one of the above listed holidays, the contractor shall perform said task on the next workday immediately following the holiday.
GOVERNMENT FURNISHED PROPERTY AND SERVICES.
3.1. GENERAL.
3.1.1 The government will provide, without cost, the facilities, equipment, materials, and/or services listed below.
3.1.2. PROPERTY.
3.1.2.1. Storage Facilities. The government will provide storage for equipment and materials not to exceed a thirty (30) day supply. The government will not be responsible for the protection or loss of any equipment and materials. The contractor shall obtain approval from before storing equipment or chemicals.
3.2. UTILITIES.
3.2.1. Contractor must provide written request prior to use of government utilities for those outside of the normal use. This written request must be approved by the COR before the contractor uses any Government utilities.
Response Method:
The Government requests capability statements and comments from interested businesses regarding the requirements described above. Responsible sources are encouraged to submit a response to this notice with a statement of interest on company letterhead. When responding, in Subject line insert: Sources Sought VASNHCS Water Services SAM
At a minimum, the following information shall be provided:
1. Company Name;
2. Company Mailing Address;
3. Point(s) of Contact including telephone number(s) & email address(es);
4. Socio-Economic (i.e. Small/Large Business, HUBZone, Service-Disabled Veteran Owned, 8(a), etc.) as it relates to NAICS Code 561210 ($47,000,000.00)
5. Provide a summary of the type of services performed and experience as it relates to Water Treatment/Storage Tank Cleaning as described above.
6. UEI Number
7. If participant in GSA/FSS or Veterans Affairs national contracts; provide contract #.
8. Sub-Contracting Intentions (provide above items 1 thru 6 of intended subcontractor along with description of sub-contractor duties). This area will be heavily scrutinized so as to avoid pass-through acquisitions.
9. Additional information and/or comments.
Veterans First Contracting Program and the VA Rule of Two (Kingdomware v. United States) 38 U.S.C. 8127 - 8128: Service-disabled veteran owned small business (SDVOSB) or Veteran owned small business (VOSB) concern must be registered and verified in VA's Vendor Information Pages (VIP) database at www.vip.vetbiz.gov to be eligible for award as a SDVOSB or VOSB if/when a solicitation is issued for this requirement as a SDVOSB or VOSB set aside. In addition, this requirement has been determined to be set aside as SDVOSB or VOSB acquisition, only SDVOSB or VOSB that respond to this specific notice within the above stated due date will be eligible for award.
Attachments/Links
Contact Information
Contracting Office Address
-
10535 HOSPITAL WAY
-
MATHER , CA 95655
-
USA
Secondary Point of Contact
History
-
Sep 03, 2025 10:56 am PDTSources Sought (Original)