Holly Hill School - Replace Boiler

Location: Florida
Posted: Jul 30, 2026
Due: Aug 17, 2026
Agency: Volusia County Schools
Type of Government: State & Local
Category:
  • Y - Construction of Structures and Facilities
  • Z - Maintenance, Repair or Alteration of Real Property
Solicitation No: Project No. 2648219
Publication URL: To access bid details, please log in.
Holly Hill School - Replace Boiler - Project No. 2648219
Mandatory Prebid Meeting: July 30, 2026 at  10:00 AM
Bid: August 17, 2026 at  1:00 PM
Project Bid Documents: Plans
Project Manual
Prebid Sign-in
Estimate: $204,560.46
Consultant: DDC Engineering, Inc.
David DaSilva

(321) 633-4522
Owner: VCS Project Manager
Paul Martino

(386) 947-8786
Bid Status: Active

Attachment Preview

VOLUSIA
COUNTY SCHOOLS
"LEADING WITH GRACE AND RESPECT"
THE SCHOOL BOARD OF VOLUSIA
COUNTY FLORIDA
200 North Clara Avenue
DeLand, Florida 32720
DESCRIPTION OF WORK
REMOVAL AND REPLACEMENT OF BOILERS AND GAS WATER HEATER
TO THE BEST OF OUR KNOWLEDGE, THESE DRAWINGS AND SPECIFICATIONS ARE COMPLETE
AND COMPLY WITH THE FOLLOWING CODES AND THEIR REVISIONS:
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - BUILDING (FBCB)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - EXISTING BUILDING (FBCEB)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - ACCESSIBILITY (FBCA)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - ENERGY CONSERVATION (FBCEC)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - MECHANICAL (FBCM)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - PLUMBING (FBCP)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - FUEL GAS (FBCFG)
8TH EDITION OF THE 2023 FLORIDA FIRE PREVENTION CODE (FFPC)
NFPA 70 - 2020 NATIONAL ELECTRICAL CODE (NEC)
2014 STATE REQUIREMENTS FOR EDUCATIONAL FACILITIES (SREF)
VOLUSIA COUNTY SCHOOL DISTRICT DESIGN STANDARDS
BUILDING DATA
A. SURVEY PARCEL ID
B. LEGAL DESCRIPTION
C. OCCUPANCY TYPE
D. CONSTRUCTION TYPE
E. RISK CATEGORY
F. AUTOMATIC SPRINKLER
G. BUILDING AREA
H. BUILDING HEIGHT
I. OCCUPANT LOAD
XXX
XXX
XXX
TYPE XXX
XXX
XXX
XXX
XXX
XXX
LOCATION MAP
HOLLY HILL SCHOOL
REPLACE BOILER
VCS Project NO. 2648219
1500 CENTER AVENUE,
HOLLY HILL, FL. 32117
ENGINEERS & CONSULTANTS
ENGINEERING
DAVID A. DAVILSA
4083 SOUTH U.S. HIGHWAY 1, SUITE. 101
ROCKLEDGE, FLORIDA 32955
PHONE 321.633.4522
DASILVA.DAVID@DDC-ENGINEERS.COM
WWW.DDC-ENGINEERS.COM
SCHOOL BOARD
MEMBERS
RUBEN COLÓN
KRISTA GOODRICH
DONNA BROSEMER
JAMIE HAYNES
JESSIE THOMPSON
BOARD CHAIR
VICE BOARD CHAIR
MEMBER
MEMBER
MEMBER
DR. CARMEN J. BALGOBIN
SUPERINTENDENT
4083 South U.S. Highway 1, Ste. 101
Rockledge, Florida 32955
Phone 321.633.4522 Fax 321.633.4528
www.ddc-engineers.com
dasilva.david@ddc-engineers.com
C.O.A.: 25988
DDC PROJECT NO.: 25007.01
David A. DaSilva
54739
THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY DAVID A.
DASILVA ON THE DATE ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
NOT TO SCALE
CONSTRUCTION DOCUMENTS - 03/27/2026
ENGINEER
DAVID A. DASILVA
ENGINEER OF RECORD
DESIGNED BY
DAD
DRAWN BY
IO/HR
ISSUE DATE
03/27/2026
AE PROJECT NUMBER
25007.01
SHEET TITLE
COVER SHEET
DRAWING NO.
G001
HVAC LEGEND
20x12
20x12
EDH-#
OAL
RI-#
RI-#
RV-#
RV-#
EF-#
EF-#
EF-#
SWD
SWR
T
H
R
S
M
TS
P
BD
20"Ø
20"Ø
20"Ø
ZD-#
VAV-#
VAV-#
EF-#
CU-#
AC-#
AC-#
HP-#
RTU-#
MECHANICAL SYMBOLS LEGEND, NOTES, AND REQUIREMENTS
DOUBLE LINE DUCTWORK, FIRST DIMENSION IS SIDE SHOWN.
SINGLE LINE DUCTWORK, FIRST DIMENSION IS SIDE SHOWN.
ITEM(S) TO BE REMOVED
ELECTRIC DUCT HEATER
FLEX DUCTWORK
OUTSIDE AIR LOUVER
OUTSIDE AIR ROOF INTAKE
DUCT UP TO OUTSIDE AIR ROOF INTAKE ABOVE
EXHAUST AIR ROOF VENT
DUCT UP TO EXHAUST AIR ROOF VENT ABOVE
ROOF TOP EXHAUST FAN
DUCT UP TO ROOF TOP EXHAUST FAN ABOVE
CEILING DIFFUSER, ROUND NECK (CEILING DIFFUSERS ARE 4-WAY THROW UON)
ROUND DIFFUSER
CEILING RETURN GRILLE WITH SQUARE CONNECTION
CEILING RETURN GRILLE WITH ROUND CONNECTION
CEILING EXHAUST GRILLE
EXHAUST FAN
SIDE WALL DIFFUSER
SIDE WALL RETURN
THERMOSTAT/TEMPERATURE SENSOR
HUMIDISTAT/HUMIDITY SENSOR
PHOTOELECTRIC DUCT SMOKE DETECTOR
R=RETURN S=SUPPLY
MOTORIZED CONTROL DAMPER
TEMPERATURE SENSOR
PRESSURE SENSOR
BACKDRAFT DAMPER
CEILING MOUNTED ACCESS DOOR
90° ELBOW W/TURNING VANES
RADIUS ELBOW W/O TURNING VANES
FIRE DAMPER (WITH ACCESS PANEL)
FIRE & SMOKE DAMPER (WITH ACCESS PANEL)
SMOKE DAMPER (WITH ACCESS PANEL)
MANUAL BALANCING DAMPER
ROUND SPIRAL
DOUBLE LINE ROUND DUCTSOCK
SINGLE LINE ROUND DUCTSOCK
ZONE DAMPER
VARIABLE AIR VOLUME (VAV) BOX W/ NO HEAT
VARIABLE AIR VOLUME (VAV) BOX W/ HEAT
IN-LINE EXHAUST FAN
CONDENSER UNIT
VERTICAL AC UNIT
HORIZONTAL AC UNIT
HORIZONTAL HEAT PUMP UNIT
PACKAGED ROOFTOP OR GROUND MOUNTED AC UNIT
HVAC PIPING LEGEND
CHS
CHR
CWS
CWR
REF
CD
HWS
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
REFRIGERANT PIPING
CONDENSATE
HOT WATER SUPPLY
FLOW DIRECTION
GATE VALVE OR BALL VALVE
CALIBRATING BALANCING VALVE
BUTTERFLY VALVE
STRAINER
CONTROL VALVE
UNION
CHECK VALVE
THERMOMETER
CONNECTION, BOTTOM
CONNECTION, TOP
MISCELLANEOUS
#
SHEET NOTE CALLOUT
#
(150)
100
NEW CFM
EXISTING
CFM
AC-#
REVISION REFERENCE
LIGHT DASHED INDICATES EXISTING FIXTURE OR DEVICE
DARK DASHED INDICATES EXISTING FIXTURE OR DEVICE RELOCATED
DARK SOLID INDICATES NEW FIXTURE OR DEVICE
HATCHED ITEMS INDICATES FIXTURE OR DEVICE TO BE REMOVED OR RELOCATED
NOT IN CONTRACT (N.I.C.)
POINT OF CONNECTION
POINT OF DISCONNECT
EXISTING DIFFUSER WITH CFM'S
EQUIPMENT TAG
ABBREVIATIONS
ABV
AC
AFF
AFG
AHU
AP
AS
BD
BOP
BHP
BTUH
CAP
CD
CFM
CH
CHP
CHR
CHS
COMB
CONN
CONT
CT
CW
CWP
CWS
CWR
CU
DB
DIA
DG
DL
DN
DP
DWG
EA
EAT
EDH
EER
EF
EFF
EG
ENT
ESP
ET
EWT
EXP
FA
FCU
FD
FLA
FLEX
FPM
FS
FT
FV
GA
GPM
HP
HB
HR
HW
HWR
HWS
- ABBREVIATION
- AIR CONDITIONER
- ABOVE FINISHED FLOOR
- ABOVE FINISHED GRADE
- AIR HANDLING UNIT
- ACCESS PANEL
- AIR SEPARATOR
- BYPASS DAMPER
- BOTTOM OF PIPE
- BRAKE HORSE POWER
- BRITISH THERMAL UNIT
- CAPACITY
- CONDENSATE DRAIN
- CUBIC FEET PER MINUTE
- CHILLER
- CHILLED WATER PUMP
- CHILLED WATER RETURN
- CHILLED WATER SUPPLY
- COMBINATION
- CONNECTION
- CONTINUE
- COOLING TOWER
- COLD WATER
- CONDENSER WATER PUMP
- CONDENSER WATER SUPPLY
- CONDENSER WATER RETURN
- CONDENSING UNIT
- DRY BULB
- DIAMETER
- DOOR GRILLE
- DOOR LOUVER
- DOWN
- DIFFERENTIAL PRESSURE
- DRAWING
- EXHAUST AIR
- ENTERING AIR TEMPERATURE
- ELECTRIC DUCT HEATER
- ENERGY EFFICIENCY RATIO
- EXHAUST FAN
- EFFICIENCY
- EXHAUST GRILLE
- ENTERING
- EXTERNAL STATIC PRESSURE
- EXPANSION TANK
- ENTERING WATER TEMPERATURE
- EXPANSION
- FACE AREA
- FAN COIL UNIT
- FIRE DAMPER
- FULL LOAD AMPS
- FLEXIBLE
- FEET PER MINUTE
- FLOOR SINK
- FEET
- FACE VELOCITY
- GAUGE
- GALLONS PER MINUTE
- HORSE POWER
- HOSE BIBB
- HOUR
- HOT WATER
- HOT WATER RETURN
- HOT WATER SUPPLY
HZ
IN
IW
KEF
KSF
KW
LAT
LF
LWT
LD
LIQ
LP
MAU
MAX
MBH
MCA
MECH
MIN
MD
NC
NFPA
NO
NOM
NTS
OA
OAU
OC
PD
PH
PRV
PSI
PSIG
PTAC
PVC
QTY
RA
REF
RG
RPM
RLA
RTU
SA
SEER
SEN
SD
SP
SWD
SWR
T
TEMP
TG
TSH
TSP
TYP
UC
UG
UON
VAV
VLV
VSD
WB
ZD
∆T
∆P
- HERTZ
- INCHES
- INDIRECT WASTE
- KITCHEN EXHAUST FAN
- KITCHEN SUPPLY FAN
- KILOWATT
- LEAVING AIR TEMPERATURE
- LINEAR FOOT
- LEAVING WATER TEMPERATURE
- LINEAR DIFFUSER
- LIQUID
- LOOP PUMPS
- MAKE-UP AIR UNIT
- MAXIMUM
- THOUSAND BTU PER HOUR
- MINIMUM CIRCUIT AMPACITY
- MECHANICAL
- MINIMUM
- MOTORIZED DAMPER
- NORMALLY CLOSED
- NATIONAL FIRE PROTECTION ASSOCIATION
- NORMALLY OPEN
- NOMINAL
- NOT TO SCALE
- OUTSIDE AIR
- OUTSIDE AIR UNIT
- ON CENTER
- PRESSURE DROP
- PHASE
- PRESSURE REDUCING VALVE
- POUNDS PER SQUARE INCH
- PSI GAUGE
- PACKAGED TERMINAL AIR CONDENSER
- POLYVINYL CHLORIDE PIPE
- QUANTITY
- RETURN AIR
- REFRIGERANT
- RETURN GRILLE
- REVOLUTIONS PER MINUTE
- RATED LOAD AMPS
- ROOF TOP UNIT
- SUPPLY AIR
- SEASONAL ENERGY EFFICIENCY RATING
- SENSIBLE
- SMOKE DAMPER
- STATIC PRESSURE
- SIDEWALL DIFFUSER
- SIDEWALL RETURN
- THERMOSTAT
- TEMPERATURE
- TRANSFER GRILLE
- TOTAL SENSIBLE HEAT
- TOTAL STATIC PRESSURE
- TYPICAL
- UNDER CUT
- UNDER GROUND
- UNLESS OTHERWISE NOTED
- VARIABLE AIR VOLUME
- VALVE
- VARIABLE SPEED DRIVE
- WET BULB
- ZONE DAMPER
- CHANGE IN TEMPERATURE
- CHANGE IN PRESSURE
GENERAL NOTES
1. VERIFY THAT ALL EQUIPMENT, AS SHOWN ON THESE DRAWINGS, WILL NOT CONFLICT WITH ANY DRAINS, SCUTTLES,
JOINTS, VENTS, PIPING OR OTHER EQUIPMENT PRIOR TO INSTALLATION.
2. EQUIPMENT SUPPLIER SHALL PROVIDE COMPLETE INFORMATION AND COOPERATE WITH THE OWNER'S
REPRESENTATIVE AS REQUIRED FOR PROJECT COMPLETION AND COORDINATION.
3. CONTRACTOR SHALL ADMINISTER AND SUBMIT ALL DRAWINGS FOR PERMITTING.
4. ALL OUTSIDE AIR INTAKES SHALL BE A MINIMUM OF 10'-0" FROM ANY EXHAUST FAN, GAS OR PLUMBING VENT.
5. PROVIDE VIBRATION ISOLATION DEVICES AND FLEXIBLE CONNECTIONS TO ALL MOVING MACHINERY.
6. ALL PIPE AND DUCTWORK DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS.
7. COORDINATE WITH ALL OTHER TRADES, ALL REQUIRED OPENINGS AND ROOF PENETRATIONS. ALL REQUIRED
OPENINGS IN FOUNDATIONS, FLOORS, WALLS AND ROOF SHALL BE MADE AND INSTALLED INTO THE STRUCTURE WITH
THE USE OF SLEEVES, CURBS, ETC.
8. PROVIDE SHOP DRAWINGS FOR ALL HVAC EQUIPMENT AND MATERIALS.
9. CONTROL PANELS AND REMOTE SENSORS SHALL BE LOCATED GENERALLY AS SHOWN. EXACT LOCATIONS SHALL BE
FIELD COORDINATED TO AVOID INTERFERENCE WITH WALL MOUNTED WORK.
10. FURNISH AND INSTALL 4" HIGH BLACK NAMEPLATES FOR ALL EQUIPMENT.
11. FIELD VERIFY ALL EXISTING SERVICES PRIOR TO START OF CONSTRUCTION.
12. REMOVE EXISTING CEILINGS, GRID, CEILING DEVICES, ETC., TO INSTALL NEW HVAC SYSTEMS. REINSTALL OR
PROVIDE NEW CEILING GRID AND TILE, TO MATCH EXISTING CONDITIONS. REINSTALL EXISTING CEILING DEVICES.
13. CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF EXISTING CEILING, WALLS, SLABS, ETC. TO INSTALL
NEW SYSTEM. MINIMIZE SAW CUTTING OF WALLS, SLABS, ETC. PATCH AND REPAIR ALL SURFACES IMPACTED BY
CONSTRUCTION. PAINT ALL SURFACE TO MATCH EXISTING FINISH.
GENERAL DEMOLITION NOTES
A. THE CONTRACTOR SHALL VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY
THIS WORK BEFORE SUBMITTING PROPOSAL SO AS TO BECOME FAMILIAR WITH EXISTING WORK. SUBMISSION OF A
PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR
LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OR BY DIFFICULTIES ENCOUNTERED WILL NOT BE
RECOGNIZED. IT IS TO BE UNDERSTOOD THAT UNFORESEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT
BE FIELD LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COOPERATION WITH OTHER TRADES IN EQUIPMENT
ROUTING AS DETERMINED DURING CONSTRUCTION AND AS DIRECTED BY THE ARCHITECT/ENGINEER MAY BE
NECESSARY AND IT IS INTENDED THAT SUCH DEVIATIONS SHALL BE CONSIDERED AS PART OF THIS CONTRACT. IT IS
ALSO UNDERSTOOD THAT THE PLANS ARE NOT COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY
DIMENSIONS OF ALL EXISTING CONDITIONS, PRIOR TO BID AND INCLUDE ANY DEVIATIONS IN THE CONTRACT.
B. ALL DEVICES AND EQUIPMENT NOT SHOWN AND IN AREAS OUTSIDE OF REMODELING SHALL REMAIN ACTIVE UNLESS
OTHERWISE NOTED. INSTALL AS REQUIRED TO MAINTAIN CONTINUITY TO EXISTING DEVICES AND EQUIPMENT THAT
ARE TO REMAIN.
C. ALL EQUIPMENT AND MATERIAL REMOVED AND NOT REUSED SHALL BE TURNED OVER TO THE OWNER OR AT THE
OWNERS REQUEST LEGALLY DISPOSED OF BY THE CONTRACTOR.
D. ALL HVAC DEVICES, EQUIPMENT, DUCTWORK, ETC., THAT ARE REMOVED SHALL BE REMOVED AS DIRECTED BY THE
OWNER/ENGINEER, AND CEILING OR WALL SHALL BE PATCHED TO MATCH EXISTING OR NEW FINISH. ALL PATCHES
SHALL BE PATCHED OR PAINTED AS DIRECTED BY ARCHITECTURAL DRAWINGS.
E. ALL EXISTING HVAC EQUIPMENT, DUCTWORK, DEVICES, ETC., IS NOT SHOWN. IT IS THE CONTRACTORS
RESPONSIBILITY TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO BID, AND INCLUDE IN HIS BID THE
REMOVAL OF ALL EQUIPMENT, DUCTWORK, DEVICES, ETC., THAT IS NOT BEING REUSED BACK TO ITS SOURCE.
F. ALL CONCRETE, WALL PATCHING, CEILING REPAIR, AND OTHER GENERAL WORK REQUIRED FOR INSTALLING THE HVAC
SYSTEMS AND TO REPAIR TO "LIKE NEW CONDITION" TO BE PROVIDED AND INSTALLED BY THE CONTRACTOR.
G. PROVIDE AND INSTALL ANY ADDITIONAL HANGERS/SUPPORTS REQUIRED TO ACCOMMODATE ANY EQUIPMENT
RELOCATIONS.
H. COORDINATE ALL CEILING MOUNTED DEVICES WITH ARCHITECTURAL REFLECTED CEILING AND WORK OF ALL OTHER
TRACES.
I. ITEMS NOTED AS EXISTING TO BE REMOVED SHALL BE REMOVED COMPLETELY. REMOVAL SHALL INCLUDE ALL
DEVICES, PIPING, HANGERS, SUPPORTS, ETC.
SHOP DRAWING SUBMITTALS
ITEM
BOILER EQUIPMENT
INSULATION
PIPING
CONTROLS
ELECTRIC DISCONNECTS
DUCTWORK/SUPPORTS
NOTES:
1- FOR REVIEW
2- FOR RECORD
3- COLOR SELECTION
4- SAMPLE
COPY FOR
OWNER
PRODUCT DATA
SHOP TEST
DRAWINGS REPORTS
COORDINATION
DRAWINGS
WIRING
DIAGRAMS
O&M
MANUAL
REVIEW 1 2 3 4 1 2 1 2 1
2
1 2 12
NOTE:
FOR ALL MATERIALS FOR CONSTRUCTION, INSTALLATION REQUIREMENTS AND
TESTING REQUIREMENTS, REFER TO CONTRACT SPECIFICATIONS.
CONTRACTOR SHALL SUBMIT ALL ITEMS UNDER ONE SUBMITTAL THAT REFERENCES
DDC PROJECT NUMBER. NO PARTIAL SUBMITTALS WILL BE ACCEPTED. ALL
SUBMITTALS SHALL BE EMAILED TO INFO@DDC-ENGINEERS.COM .
DESIGN CRITERIA
DESIGN TEMPERATURES:
OUTDOOR AIR:
SUMMER: 95°F DB/80°F WB
WINTER: 30°F DB
INSIDE AIR:
SUMMER: 75°F DB/60% RH
WINTER: 72°F DB
NOTES:
THE DESIGN CRITERIA ABOVE IS BASED ON ASHRAE STANDARD 62.1. ANY CHANGES TO THIS OCCUPANCY OR FLOOR PLAN
WILL REQUIRE FURTHER REVIEW AND MODIFICATIONS TO THIS VENTILATION SYSTEM.
CODE COMPLIANCE REQUIREMENTS
ALL WORK SHALL BE IN COMPLIANCE WITH THE FOLLOWING CODES, BUT NOT LIMITED TO:
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - BUILDING (FBCB)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - EXISTING BUILDING (FBCEB)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - ACCESSIBILITY (FBCA)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - ENERGY CONSERVATION (FBCEC)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - MECHANICAL (FBCM)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - PLUMBING (FBCP)
8TH EDITION OF THE 2023 FLORIDA BUILDING CODE - FUEL GAS (FBCFG)
8TH EDITION OF THE 2023 FLORIDA FIRE PREVENTION CODE (FFPC)
NFPA 70 - 2020 NATIONAL ELECTRICAL CODE (NEC)
SCOPE OF WORK
· REMOVE AND REPLACE EXISTING BOILERS.
· REMOVE AND REPLACE EXISTING WATER HEATER.
· MODIFY ELECTRICAL SERVICE TO EQUIPMENT.
· MODIFY DDC CONTROLS FOR NEW EQUIPMENT.
NOTE: CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF
DOORS AND FRAMING AS NEEDED TO INSTALL NEW EQUIPMENTS.
REFER TO MECHANICAL SPECIFICATIONS FOR FURTHER
REQUIREMENTS.
4083 South U.S. Highway 1, Ste. 101
Rockledge, Florida 32955
Phone 321.633.4522 Fax 321.633.4528
www.ddc-engineers.com
dasilva.david@ddc-engineers.com
C.O.A.: 25988
DDC PROJECT NO.: 25007.01
David A. DaSilva
54739
THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY DAVID A.
DASILVA ON THE DATE ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
ENGINEER
DAVID A. DASILVA
ENGINEER OF RECORD
DESIGNED BY
DAD
DRAWN BY
IO/HR
ISSUE DATE
03/27/2026
AE PROJECT NUMBER
25007.01
SHEET TITLE MECHANICAL
LEGEND, NOTES
DRAWING NO.
M001
D2
D5
D3
D2
D1 D4
D6 D7
D1 D4
MECHANICAL DEMOLITION PLAN
ENLARGED BOILER ROOM
1/2" = 1'-0"
EX. EF
SEE ENLARGED PLAN ABOVE
EX. AHU
EX. AHU-6-2
EX. AHU-6-1
MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"
DEMOLITION PLAN NOTES
MD#
D1. REMOVE EXISTING BOILER.
D2. DISCONNECT HOT WATER PIPING AND REMOVE BOILER PUMP.
D3. REMOVE EXISTING GAS WATER HEATER.
D4. REMOVE EXISTING VENT CONNECTION SERVING BOILER OR HEATER.
D5. DISCONNECT BENT PIPING.
D6. REMOVE ALL CONTROL TEMPERATURE SENSORS WITHIN PIPES BEING
REPLACE.
D7. EXISTING CONTROL SYSTEM (ALERTON) TO BE REUSED.
4083 South U.S. Highway 1, Ste. 101
Rockledge, Florida 32955
Phone 321.633.4522 Fax 321.633.4528
www.ddc-engineers.com
dasilva.david@ddc-engineers.com
C.O.A.: 25988
DDC PROJECT NO.: 25007.01
David A. DaSilva
54739
THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY DAVID A.
DASILVA ON THE DATE ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
EXISTING BOILERS
AREA OF
WORK
KEY PLAN
N.T.S.
ENGINEER
DAVID A. DASILVA
ENGINEER OF RECORD
DESIGNED BY
DAD
DRAWN BY
IO
ISSUE DATE
03/27/2026
AE PROJECT NUMBER
25007.01
SHEET TITLE
MECHANICAL
DEMOLITION PLANS
DRAWING NO.
MD100
GWH-1
943
B-1
1
2
9
HWP-3
6
349
HWP-4
B-2 1 2 9
7
7
MECHANICAL PLAN
ENLARGED BOILER ROOM
1/2" = 1'-0"
EX. EF
SEE ENLARGED PLAN ABOVE
EX. AHU
EX. AHU-6-2
EX. AHU-6-1
MECHANICAL PLAN
1/4" = 1'-0"
PLAN NOTES
#
1. INSTALL NEW BOILERS ON EXISTING CONCRETE PAD.
2. MODIFY PAD AS NECESSARY FOR NEW BOILERS.
3. CONNECT NEW BOILER TO EXISTING PIPING.
4. PROPERLY INSULATE ALL PIPING WITH SIMILAR TYPE INSULATION.
5. LABEL ALL PIPING.
6. CONNECT BOILERS TO EXISTING VENT SYSTEM.
7. INSTALL NEW BUTTERFLY VALVES.
8. INSTALL NEW ENTERING AND LEAVING HOT WATER TEMPERATURE
SENSORS IN PIPES FOR EACH BOILER.
9. EXISTING DDC CONTROL PANEL TO CONNECT TO NEW BOILER
CONTROL PANEL.
4083 South U.S. Highway 1, Ste. 101
Rockledge, Florida 32955
Phone 321.633.4522 Fax 321.633.4528
www.ddc-engineers.com
dasilva.david@ddc-engineers.com
C.O.A.: 25988
DDC PROJECT NO.: 25007.01
David A. DaSilva
54739
THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY DAVID A.
DASILVA ON THE DATE ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
AREA OF
WORK
KEY PLAN
N.T.S.
ENGINEER
DAVID A. DASILVA
ENGINEER OF RECORD
DESIGNED BY
DAD
DRAWN BY
IO/HR
ISSUE DATE
03/27/2026
AE PROJECT NUMBER
25007.01
SHEET TITLE
MECHANICAL
PLANS
DRAWING NO.
M100
BOILER
PIPE
PIPE SADDLE
(TYP.)
ALL INSULATION PASSES
THRU HANGER UNBROKEN
SIZES UP TO 3"
SINGLE
ATTACH TO
STRUCTURE
CONTINUOUS
THREADED ROD
U-BOLT
PIPE INSULATION
PIPE
PIPE SADDLE
(18 GA., 18" LONG)
WASHER (TYP.)
UNISTRUT OR
ANGLE IRON
LOCKNUT (TYP.)
MULTIPLE
M1
INSULATED
PIPE HANGER DETAIL
N.T.S.
M-D009
3" HWS
HEADER
PRESSURE
RELIEF VALVE
HWP-4
3" HWR
HEADER
THERMOSTAT
PRESSURE
RELIEF VALVE
HWP-3
B-2
THERMOSTAT
ROUTE DRAIN
TO EXISTING
FLOOR DRAIN
B-1
ROUTE DRAIN TO
EXISTING 4"
EXISTING FLOOR DRAIN
CONCRETE PAD
EXISTING 4"
CONCRETE PAD
M2 HOT WATER
BOILER DETAIL
N.T.S.
NOTES:
1. BOILER CIRCUIT PIPING MUST BE SIZED
LARGE ENOUGH TO HANDLE MAXIMUM
FLOW THROUGH UNIT.
2. BOILER PUMP SIZED TO BOILER DESIGN
FLOW REQUIREMENTS.
3. ALL BOILERS FURNISHED WITH FACTORY
MOUNTED OUTLET WATER TEMPERATURE
GAUGE.
4. BOILER PUMP PURGING REQUIRED. USE
TERMINALS SUPPLIED.
5. A SENSOR IS REQUIRED AND INSTALLED
AT A MINIMUM OF 12" FROM PRIMARY
LOOP TEE.
1
EX. HOT
WATER
PIPING
PUMP
THERMOSTAT
PRESSURE RELIEF
M3 MULTIPLE
BOILERS DETAIL
4083 South U.S. Highway 1, Ste. 101
Rockledge, Florida 32955
Phone 321.633.4522 Fax 321.633.4528
www.ddc-engineers.com
dasilva.david@ddc-engineers.com
C.O.A.: 25988
DDC PROJECT NO.: 25007.01
David A. DaSilva
54739
THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY DAVID A.
DASILVA ON THE DATE ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
ENGINEER
DAVID A. DASILVA
ENGINEER OF RECORD
DESIGNED BY
DAD
DRAWN BY
IO/HR
ISSUE DATE
03/27/2026
AE PROJECT NUMBER
25007.01
SHEET TITLE
MECHANICAL
DETAILS
DRAWING NO.
M500
This is the opportunity summary page. It provides an overview of this opportunity and a preview of the attached documentation.
Daily notification on new contract opportunities

With GovernmentContracts, you can:

  • Find more opportunities and win more business
  • Receive daily alerts for all new bid opportunities
  • Get contract opportunities matched to your business
ONE WEEK FREE TRIAL

See also

Project ID: Title: Vault Room and Oil Room Project Addenda: 0 Release Date:

Sarasota County

Bid Due: 8/26/2026

Project ID: Title: Red-Light Camera Traffic Infraction Detector System Addenda: 0 Release Date:

City of Orlando

Bid Due: 9/17/2026

Main Agency Hillsborough County Public Schools Status Active Fiscal Year 2026 Primary Contact

Hillsborough County Public Schools

Bid Due: 8/17/2026

Follow Environmental Analytical and Regulatory Compliance Services Active Contract Opportunity Notice ID FA6648-19

DEPT OF DEFENSE

Bid Due: 8/07/2026

* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.