FY24 Emergency Replace Condensers FS Warehouse MOD 00001
Recover refrigerant, disconnect piping, move equipment with
customer forklift, set new equipment, connect to existing piping,
install new suction line accumulator outside new unit, pressure
test, evacuate lines, charge with new refrigerant, start and test.
Isolated compressor and pressure tested with customer supplied
nitrogen. Traced to leak at base of compressor bolt. Attempted
to tighten to repair. Found unsuccessful. Determined compressor
would need to be removed for repair or possibly sent out for
rebuild. Unit is 15 years old, added customer supplied POE to
prevent oil failure, reset from tripping. Released nitrogen charge
and completed evacuation test. Restored power, unit is operational
but continuously loosing oil. Customer requests replacement unit.