J061--Maintenance Services for Emergency Generators Aleda E. Lutz VA Medical Center

Location: Virginia
Posted: Dec 20, 2024
Due: Jan 3, 2025
Agency: VETERANS AFFAIRS, DEPARTMENT OF
Type of Government: Federal
Category:
  • J - Maintenance, Repair, and Rebuilding of Equipment
Solicitation No: 36C25025Q0188
Publication URL: To access bid details, please log in.
Follow
J061--Maintenance Services for Emergency Generators Aleda E. Lutz VA Medical Center
Active
Contract Opportunity
Notice ID
36C25025Q0188
Related Notice
Department/Ind. Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-tier
VETERANS AFFAIRS, DEPARTMENT OF
Office
250-NETWORK CONTRACT OFFICE 10 (36C250)
Looking for contract opportunity help?

APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.

APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.

The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).

General Information
  • Contract Opportunity Type: Sources Sought (Original)
  • Original Published Date: Dec 19, 2024 10:39 am EST
  • Original Response Date: Jan 03, 2025 03:00 pm EST
  • Inactive Policy: Manual
  • Original Inactive Date: Mar 04, 2025
  • Initiative:
    • None
Classification
  • Original Set Aside:
  • Product Service Code: J061 - MAINT/REPAIR/REBUILD OF EQUIPMENT- ELECTRIC WIRE AND POWER DISTRIBUTION EQUIPMENT
  • NAICS Code:
    • 811310 - Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance
  • Place of Performance:
    Aleda E. Lutz VA Medical Center Saginaw , 48602
    USA
Description
This Sources Sought/Market Survey Notice is being conducted by Aleda E. Lutz VA Medical Center, 1500 Weiss Street, Saginaw MI, 48602 to identify all sources that are capable of providing Maintenance Service for Emergency Generator for the period of April 5, 2025 April 4, 2026 at the discretion of the Government in strict accordance with all schedules, specifications, terms, conditions and provisions of this contract.
General Information
VISIT #1 Furnish all tools, labor, materials, parts, and laboratory services to perform the following specified maintenance on the five generators listed at the end of this document:
All maintenance, service, operational checks, and parts shall be performed and supplied per the manufacturer s recommendations by manufacturer certified technicians.
Contractor shall provide all fluid analysis reports and within 7 10 days after completion of maintenance.
Contractor performance shall be monitored through service reports that shall be submitted after each repair has been conducted. Field service reports must be submitted within 7-10 days and will be reviewed for accuracy and timely submission.
Contractor shall perform services within 60 days of award.
Maintenance Checks:

Radiator core for air flow
Antifreeze protection
Coolant level
Coolant inhibitor strength (add conditioner if required to update strength)
Radiator cap and seal
Coolant leaks
Lube oil level
Fan belt tension
Condition of all hoses
Hose clamps
Condition of flex fuel lines
Day tank float controls, solenoid, and main fuel pump operation
Fuel system for leaks
Cranking voltage drop
Battery electrolyte level
Battery voltage
Battery charger rate
Battery cables and connections
Flex exhaust couplings rain flashing
Turbo wheel for bearing wear
Terminal strip connections
Loose relays in control panel
Jacket water heater operation
Governor oil level
Governor linkage
Remote governor control operation
Air gap on generator
Collector rings and brushes
Oil and dirt buildup in generator
System for loose bolts, etc.
Crank termination time
Engine instruments
Abnormal noise or vibration
Exhaust characteristics
Louver operation
Crankcase blow by
Voltage and frequency
All switches in correct position
Drain water and sediment from day tank
Lubricate generator bearing
Clean engine crankcase breather
Lubricate fan pulley
Clean primary filter
Drain exhaust moisture traps
Inspect the turbocharger for end play and leaks
Maintenance Services:
Note: All filters shall be OEM
Change air cleaner elements, check seals, air cleaner indicators and air induction system
Take oil sample and perform infrared analysis (performed by a Fluid Analysis Lab)
Take fuel and coolant samples and perform analysis (performed by a Fluid Analysis Lab)
Change lube oil and filters, lube oil is to be replaced with fully-synthetic oil in accordance with manufacturers recommendations
Change fuel filters
Oil, fuel, and coolant samples taken will be delivered to the testing laboratory in a reasonable time as to not compromise the samples. Care will be taken as to storing the samples as recommended by the testing laboratory until they are delivered.
Operational Checks:
Recheck oil level while running
Recheck all fluid systems for leaks
Used Oil Transportation and Recycling:

Transportation and recycling of used oil shall be performed in accordance with Federal, state and local regulations including:

Michigan Natural Resources and Environmental Protection Act 451, of 1994 as amended, Part 121 Liquid Industrial By-Product.
Prior to transporting used oil from the property, the transporter must provide a shipping document describing the materials in accordance with above regulation for certification by the Detroit VAMC GEMS Program Manager or designee. The contractor shall arrange for the designated recycling facility to notify the COR, in writing, that the shipment(s) arrived at its destination within 7 days of the date the shipment left the facility.

Michigan Hazardous Material Transportation Act 138.
Prior to transporting used oil from the property, the contractor shall provide a copy of the Act 138 transporter s permit and registration to the COR for the approval of the GEMS Program Manager. During transport, the transporter must also be able to produce a copy of the Act 138 permit and registration, either via electronic record or hard copy, to DEQ staff or a peace officer when requested.

Generator #1
Cummins/Onan Model: DFEB-4955010 Sn: B010204440
KW: 400 PF: .8 Volt: 120/208 Amp: 1387
Generator #2
MTU Onsite Energy Model: 400PXC6DT3 Sn: 331914-1-1-0411
KW: 400 PF: .8 Volt: 120/208 Amp: 1387
Generator #3
Cummins/Onan Model: 350 DFCC Sn: G920477586
KW: 350 PF: .8 Volt: 277/480 Amp: 526
Generator #6
MTU Onsite Energy Mod: 750RXC6DT2(G05) Sn: WA-572596-0410
KW: 750 PF: .8 Volt: 277/480 Amp: 1127
Generator #7
MTU Onsite Energy Mod: DS00500D6SRAH1583 Sn: 331787-1-1-0411
KW: 500 PF: .8 Volt: 277/480 Amp: 751
If this is a service your business can provide, respond to this Sources Sought by Friday, January 3, 2025; 3:00 P.M. Eastern time. Responses should include: (1) Business Name and Address (2) Point of Contact Name, Phone Number, and E-mail Address (3) SAM UEI and NAICS code (4) Business Size SMALL or LARGE (5) Type of Business SERVICE DISABLED VETERAN OWNED, VETERAN OWNED, 8A, HUBZone, WOMEN-OWNED etc. (6) Applicable GSA/FSS Contract Number (if applies). All businesses eligible to provide this service are encouraged to reply as this information may be used to determine potential set-asides for the above noted service. E-mail responses to: Ariel Bautista-Lagares, at Ariel.Bautista-Lagares@va.gov (Note: This is NOT A REQUEST FOR QUOTE or an announcement of a solicitation.)
Attachments/Links
Contact Information
Contracting Office Address
  • VISN 10 CONSOLIDATED CONTRACTING 4100 WEST 3RD STREET
  • DAYTON , OH 45428
  • USA
Primary Point of Contact
Secondary Point of Contact


History
  • Dec 19, 2024 10:39 am ESTSources Sought (Original)
Daily notification on new contract opportunities

With GovernmentContracts, you can:

  • Find more opportunities and win more business
  • Receive daily alerts for all new bid opportunities
  • Get contract opportunities matched to your business
ONE WEEK FREE TRIAL
* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.