Remodeling of Red Clay Theater

Location: Georgia
Posted: Nov 21, 2025
Due: Jan 15, 2026
Agency: City of Duluth
Type of Government: State & Local
Category:
  • 56 - Construction and Building Materials
Publication URL: To access bid details, please log in.
Description Opening Date/Time Closing Date/Time


Remodeling of Red Clay Theater


PME



November 21, 2025
:


January 15, 2026
2:00
PM

Attachment Preview

ABBREVIATIONS
AAV
A/C
A/F
AFF, AFG
B/F, B/G
BFP
CD
CONT
CW
DN
ET
EWC
ex.
FCO
FD
FHB
FS
FRH
FWH
GCO
GI
HB
HD
HW
HWR
AIR ADMITTANCE VALVE
IMB
ABOVE CEILING
IE
ABOVE FLOOR
IWH
ABOVE FINISHED FLOOR/GRADE L, LAV
BELOW FLOOR/GRADE
MBH
BACKFLOW PREVENTER
MS
CONDENSATE DRAIN
MV
CONTINUATION
O/H
COLD WATER
G
DOWN
PD
EXPANSION TANK
PRV
ELECTRIC WATER COOLER
RP
EXISTING
S, SAN
FLOOR CLEANOUT
SH
FLOOR DRAIN
SK
FREEZEPROOF HOSE BIBB
TP
FLOOR SINK
TYP
FREEZEPROOF ROOF HYDRANT UR
FREEZEPROOF WALL HYDRANT V
GRADE CLEANOUT
VTR
GREASE INTERCEPTOR
WC
HOSE BIBB
W.C.
HUB DRAIN
WCO
HOT WATER
WHA
HOT WATER RETURN
WMB
ICE MACHINE BOX
INVERT ELEVATION
INSTANTANEOUS WATER HEATER
LAVATORY
1000 BTU/HR
MOP SINK
MIXING VALVE
OVERHEAD
NATURAL GAS
PUMPED DISCHARGE
PRESSURE REDUCING VALVE
RECIRCULATION PUMP
SANITARY
SHOWER
SINK
TRAP PRIMER
TYPICAL
URINAL
VENT
VENT THROUGH ROOF
WATER CLOSET
WATER COLUMN
WALL CLEANOUT
WATER HAMMER ARRESTER
WASHING MACHINE BOX
LEGEND
S
GW
F
IW
PD
FW
COLD WATER PIPE
HOT WATER PIPE
HOT WATER RETURN PIPE
SANITARY PIPE
VENT PIPE
GREASE WASTE PIPE
FIRE SPRINKLER PIPE
INDIRECT WASTE PIPE
PUMPED DISCHARGE
FILTERED WATER PIPE
PIPE UP / PIPE DOWN
PIPE TEE FROM TOP / TEE FROM BOTTOM
PIPE CAP / PIPE CONTINUATION
DIRECTIONAL FLOW ARROW
BALL VALVE / CHECK VALVE
MIXING VALVE / PRESSURE REDUCING VALVE
BACKFLOW PREVENTER ASSEMBLY
WALL HYDRANT / HOSE BIBB
FLOOR DRAIN / FLOOR SINK
WATER HAMMER ARRESTOR
GAS COCK / GAS SOLENOID VALVE
P-TRAP
HUB DRAIN
TRAP PRIMER
FLOOR CLEANOUT / GRADE CLEANOUT
VENT THROUGH ROOF
PIPE CLEANOUT / WALL CLEANOUT
SPECIFICATIONS
GENERAL
ALL WORK SHALL COMPLY WITH ALL STATE, CITY AND LOCAL CODES, RULES AND REGULATIONS. CONTRACTOR SHALL
SECURE ALL REQUIRED PERMITS AND INSPECTIONS ASSOCIATED WITH THIS WORK, AND SHALL PAY ALL COSTS AND
FEES INVOLVED.
ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE BEST RECOGNIZED PRACTICE IN THE FIELD CONCERNED.
MANUFACTURED ITEMS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S PRINTED
DIRECTIONS, SPECIFICATIONS AND RECOMMENDATIONS.
CONTRACTOR SHALL REVIEW ALL CONTRACT DOCUMENTS AND SHALL BE FAMILIAR WITH THE SCOPE AND
REQUIREMENTS OF THIS PROJECT. ANY DISCREPANCIES OR LACK OF CLARITY IN THE DOCUMENTS SHALL BE
IDENTIFIED TO THE ARCHITECT OR ENGINEER PRIOR TO THE SUBMISSION OF PRICING BIDS. WITH A SUBMITTED BID,
CONTRACTOR IS ACCEPTING THESE DOCUMENTS AS SUFFICIENT DEFINITION OF THE SCOPE OF WORK, AND ANY
ADDITIONAL COSTS BASED ON UNCLARITY OF CONTRACT DOCUMENTS WILL NOT BE CONSIDERED.
CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND LOCATIONS FOR EQUIPMENT INSTALLATION PRIOR TO THE
SUBMITTAL OF SHOP DRAWINGS. ALL EQUIPMENT AND DEVICES SHALL BE INSTALLED SUCH THAT THEY ARE EASILY
ACCESSIBLE AND SERVICABLE. THIS EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO: PLUMBING FIXTURES, WATER
HEATERS, EXPANSION TANKS, PUMPS, BACKFLOW PREVENTERS, VALVES, MIXING VALVES, THERMOMETERS, GAUGES,
TRAP PRIMERS AND CLEANOUTS.
THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING THE FULL SET OF CONSTRUCTION DOCUMENTS, INCLUDING
ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL & ELECTRICAL DRAWINGS (AS APPLICABLE) TO ENSURE ALL
PLUMBING WORK IS COORDINATED WITH PHYSICAL CONDITIONS AND ALL OTHER TRADES.
THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING THE ARCHITECTURAL DRAWINGS TO ENSURE THERE IS ADEQUATE
WALL THICKNESS SUCH THAT ALL PIPING, FIXTURE CARRIERS, WALL CLEANOUTS, WALL BOXES, WALL HYDRANTS AND
ACCESS PANELS WILL FIT IN THE WALL SPACE. CONTRACTOR SHALL NOTIFY THE ARCHITECT IF WALL SPACE IS
INADEQUATE PRIOR TO COMMENCING WORK.
THE CONTRACTOR SHALL OBTAIN EXACT WALL, FIXTURE, AND LAYOUT DIMENSIONS FROM THE ARCHITECTURAL
DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ROUGH-IN AND INSTALLATION DRAWINGS FOR ALL
PLUMBING FIXTURES, KITCHEN EQUIPMENT AND OWNER FURNISHED EQUIPMENT (AS APPLICABLE), AND SHALL
COORDINATE THE PLUMBING INSTALLATION PRIOR TO COMMENCING THE WORK. THE CONTRACTOR IS RESPONSIBLE
FOR PROVIDING AND INSTALLING ALL NECESSARY VALVES, CONNECTIONS, TRAPS, ACCESS PANELS, UNIONS,
ESCUTCHEONS, WATER HAMMER ARRESTORS, VACUUM BREAKERS, RELIEF VALVES, PIPE INSULATION, AND
EQUIPMENT SPECIALTY DEVICES AS REQUIRED TO FACILITATE COMPLETE AND OPERATIONAL CONDITIONS WHICH ARE
IN STRICT COMPLIANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
THESE DRAWINGS ARE DIAGRAMMATIC AND DO NOT REFLECT ALL POSSIBLE PHYSICAL CONDITIONS. REFER TO
ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS AND EXACT LOCATIONS OF EQUIPMENT AND FIXTURES. PROVIDE
NECESSARY PIPING OFFSETS TO COORDINATE WITH THE BUILDING STRUCTURE, WORK OF OTHER TRADES, AND
CONNECTION TO SITE UTILITIES (AS APPLICABLE).
COORDINATE THE ELECTRICAL REQUIREMENTS AND CHARACTERISTICS OF ALL PLUMBING EQUIPMENT WITH THE
ELECTRICAL CONTRACTOR PRIOR TO ISSUING SUBMITTALS OR PURCHASING EQUIPMENT.
UNLESS NOTED OTHERWISE, ALL DRAINAGE PIPING SHALL BE SLOPED AT A MINIMUM OF 18" PER FOOT. 2" SANITARY
PIPING AND ALL GREASE WASTE PIPING SHALL BE SLOPED AT 14" PER FOOT.
DOMESTIC WATER PIPING SHALL BE PURGED OF DELETERIOUS MATTER AND DISINFECTED PRIOR TO UTILIZATION.
PIPING TO BE FLUSHED AND STERILIZED IN ACCORDANCE WITH IPC 610.1 AND ALL APPLICABLE LOCAL AND STATE
HEALTH DEPARTMENT STANDARDS.
ALL DOMESTIC WATER PIPING, SANITARY P-TRAPS AND GREASE WASTE PIPING SUBJECT TO FREEZING SHALL BE
INSULATED AND PROVIDED WITH HEAT TRACE. CONDENSATE PIPING SUBJECT TO FREEZING WITHIN WALK-IN FREEZERS
SHALL BE INSULATED AND PROVIDED WITH HEAT TRACE. PIPING INSTALLED IN EXTERIOR WALLS SHALL BE WRAPPED IN
1" THICK PIPE INSULATION AND BE LOCATED ON THE INTERIOR SIDE OF THE BUILDING INSULATION. IF INSTALLED IN
EXTERIOR BLOCK WALLS, INTERSTITIAL SPACES SHALL BE FILLED WITH FOAM INSULATION.
IN CONCEALED LOCATIONS WHERE PIPING, OTHER THAN CAST-IRON OR GALVANIZED STEEL, IS INSTALLED THROUGH
HOLES OR NOTCHES IN STUDS, JOISTS, OR SIMILAR MEMBERS LESS THAN 112" FROM THE NEAREST EDGE OF
MEMBER, PIPE SHALL BE PROTECTED BY STEEL SHIELD PLATES IN ACCORDANCE WITH IPC 305.6.
PIPE PENETRATIONS THROUGH FIRE RATED WALLS OR FLOORS SHALL HAVE EQUIVALENTLY RATED SLEEVES AND SHALL
BE SEALED AND FIRE CAULKED WITH A U.L. LISTED FIRE STOPPING SYSTEM INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S LISTED DETAILS AND SPECIFICATIONS.
THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING WITH THE REQUIREMENTS OF THE COUNTY HEALTH
DEPARTMENT AND OTHER LOCAL AUTHORITIES HAVING JURISDICTION REGARDING CROSS CONNECTION CONTROL OR
OBTAINING A FOOD SERVICE PERMIT (AS APPLICABLE). REPORT ANY OBSERVED DISCREPANCIES TO THE ARCHITECT
OR ENGINEER PRIOR TO COMMENCING WITH THE WORK.
CONTRACTOR SHALL CONFIRM PLUMBING FIXTURE FINISHES WITH THE ARCHITECTURAL SCHEDULES & DETAILS (AS
APPLICABLE).
PROFICIENT ENGINEERING WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM
FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND THE DESIGN INTENT THEY CONVEY, OR PROBLEMS WHICH
ARISE FROM OTHER'S FAILURE TO OBTAIN AND/OR FOLLOW PROFICIENT'S GUIDANCE WITH RESPECT TO ANY ERRORS,
OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED. THE DRAWINGS ARE GENERALLY
DIAGRAMMATIC IN NATURE.
SUBMITTALS
FURNISH SHOP DRAWINGS FOR MANUFACTURED PRODUCTS. ALL ITEMS SHALL BE CLEARLY MARKED TO MATCH
EQUIPMENT MARKS ON THE PLUMBING DRAWINGS. ALL OPTIONS MUST BE CLEARLY MARKED ON THE SUBMITTAL
SHEET. A MODEL NUMBER LISTING ON A COVER SHEET IS NOT AN ACCEPTABLE SUBSTITUTE FOR MARKING THE
ACTUAL SUBMITTAL SHEET. ELECTRICAL DATA FOR POWERED EQUIPMENT MUST BE INDICATED ON THE SUBMITTAL
SHEET FOR THAT ITEM.
SUBMITTAL REVIEW IS CONSIDERED A GENERAL ACCEPTANCE OF THE BASIC APPLICABILITY OF THE EQUIPMENT.
CONTRACTOR IS RESPONSIBLE FOR THE INSTALLATION AND/OR ALTERNATE ARRANGEMENT OF THE EQUIPMENT WITHIN
A GIVEN SPACE. WHEN SUBSTITUTED EQUIPMENT IS INSTALLED, CONTRACTOR SHALL BE RESPONSIBLE FOR ANY
COORDINATION OR ADDITIONAL COST BROUGHT ON BY THE USE OF THIS EQUIPMENT.
HANGERS AND SUPPORTS
HANGERS SHALL BE COMPLETE WITH RODS AND SUPPORTS PROPORTIONED TO THE SIZE OF PIPE TO BE SUPPORTED,
IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
SIZE HANGERS FOR INSULATED PIPING TO BEAR ON OUTSIDE OF INSULATION. PROVIDE INSULATION PROTECTORS AT
HANGERS BEARING ON THE OUTSIDE OF INSULATION. PROVIDE A RIGID INSERT OR RIGID INSULATION AT EACH
INSULATION PROTECTOR.
WHERE SEVERAL PIPES 212" AND SMALLER RUN PARALLEL AND IN THE SAME PLANE, THEY MAY BE SUPPORTED ON
GANG OR MULTIPLE HANGERS. LARGER PIPING SHALL BE INDEPENDENTLY HUNG, RUN PARALLEL AND BE EQUALLY
SPACED.
PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH IPC SECTION 308, AND SPACING OF HANGERS SHALL NOT
EXCEED THE LIMITS SET FORTH IN TABLE 308.5. PIPES SHALL BE SUPPORTED WITHIN 1'-0" OF EACH ELBOW.
VERTICAL PIPE SUBJECT TO MOVEMENT SHALL BE SUPPORTED FROM THE WALL BY MEANS OF A PIPE CLAMP.
SUPPORT DOMESTIC WATER PIPING IN SPACES BEHIND PLUMBING FIXTURES BY BRACKETS AND U-BOLTS SECURED TO
WASTE AND VENT STACKS. SIZE U-BOLTS TO BEAR ON THE PIPING.
AFTER HANGER RODS ARE INSTALLED IN FINISHED CONCRETE CEILING, FILL THE REMAINING OPENING WITH CEMENT SO
THAT NO HOLE SHOWS AT THE CEILING.
WHERE COPPER PIPING IS USED, NONFERROUS METAL SUPPORT(S) OR PROPER ISOLATION BETWEEN DISSIMILAR
MATERIALS SHALL BE PROVIDED.
PIPE HANGERS AND SUPPORTS SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH RECOMMENDATIONS SET
FORTH IN MANUFACTURER'S STANDARDIZATION SOCIETY STANDARD PRACTICES NO. SP-69 AND SP-58.
SPECIFICATIONS
DOMESTIC WATER SYSTEMS AND ACCESSORIES
THE PRIMARY SPECIFICATION FOR DOMESTIC WATER PIPING SHALL BE AS FOLLOWS: WATER PIPING ABOVE FLOOR: TYPE 'L' HARD
DRAWN COPPER TUBING, ASTM B88, WROUGHT SOLDER JOINTS, ANSI B16.22. WATER PIPING BELOW FLOOR: TYPE 'K SOFT DRAWN
COPPER TUBING, WITH NO JOINTS BELOW SLAB, ASTM B88.
AS AN ALTERNATE TO THE PRIMARY SPECIFICATION FOR WATER PIPING, THE FOLLOWING MAY BE USED IN WHOLE OR IN PART. THE
PLUMBING CONTRACTOR SHALL LIST EACH SYSTEM AS A SEPARATE LINE ITEM AS AN ALTERNATE FOR THE OWNER'S SELECTION. USE
OF ANY ALTERNATE SHALL BE AT THE SOLE DISCRETION OF THE OWNER. SERVICE PIPING BELOW GRADE: CPVC (CHLORINATED
POLYVINYL CHLORIDE) SCHEDULE 40 WHEN APPROVED BY THE AUTHORITY HAVING JURISDICTION. SHALL MEET ASTM D2846 AND
ASTM F 441. HOT AND COLD WATER PIPING ABOVE FLOOR: CPVC (CHLORINATED POLYVINYL CHLORIDE) SCHEDULE 40 WITH SOLVENT
WELD JOINTS WHEN APPROVED BY THE AUTHORITY HAVING JURISDICTION. PIPING SHALL MEET ASTM D 2848 AND SHALL BE
CERTIFIED BY THE NSF INTERNATIONAL FOR USE WITH POTABLE WATER SYSTEMS. SOLVENT CEMENTS FOR CPVC PLASTIC PIPING
SHALL MEET ASTM F437, ASTM F438 AND ASTM F439. WATER PIPING ABOVE FLOOR: CROSS-LINKED POLYETHYLENE (PEX) TUBING,
SHALL COMPLY WITH ASTM F 876, ASTM F 877; CSA B137.5. HOT AND COLD WATER PIPING ABOVE FLOOR: CROSS-LINKED
POLYETHYLENE (PEX) TUBING, SHALL COMPLY WITH ASTM F 876, ASTM F 877; CSA B137.5.
ALL DOMESTIC HOT WATER PIPING SHALL HAVE A MINIMUM PRESSURE RATING OF 100PSI AT 180°F.
DOMESTIC WATER PIPING SHALL BE TESTED IN ACCORDANCE WITH ALL GOVERNING CODES. PIPING SHALL BE PURGED OF
DELETERIOUS MATTER AND DISINFECTED PRIOR TO UTILIZATION. PIPING TO BE FLUSHED AND STERILIZED IN ACCORDANCE WITH IPC
610.1 AND ALL APPLICABLE LOCAL AND STATE HEALTH DEPARTMENT STANDARDS.
BALL VALVES SHALL BE TWO-PIECE BRONZE BODY, LARGE PORT WITH SOLID, SMOOTH BORE CHROME PLATED BRASS BALL. SEATS
SHALL BE REINFORCED TFE WITH TEFLON PACKING RING AND THREADED ADJUSTABLE PACKING NUT. PROVIDE STEM EXTENSION AS
NEEDED TO PROVIDE HANDLE ON OUTSIDE OF PIPE INSULATION. VALVES SHALL BE APOLLO 70 OR EQUAL.
BACKFLOW PREVENTERS SHALL BE INSTALLED IN ACCESSIBLE LOCATIONS FOR EASE OF TESTING AND SERVICING. FOR BACKFLOW
PREVENTERS WITH VENT CONNECTIONS, ROUTE VENT LINE TO NEAREST DRAIN AND DISCHARGE WITH AIR GAP. BACKFLOW
PREVENTERS SHALL BE TESTED IN ACCORDANCE WITH IPC 312.10.2. CONTRACTOR SHALL PROVIDE CERTIFICATIONS THAT STATE
DEVICES HAVE BEEN TESTED AND APPROVED.
THERMOMETERS SHALL BE 9" ADJUSTABLE ANGLE, 30°-180°F RANGE (TRERICE BX9 OR EQUAL). PRESSURE GAUGES SHALL BE 412"
DIAL SIZE, 0-160PSI (TRERICE 600CB OR EQUAL).
CONTRACTOR SHALL FIELD VERIFY INCOMING DOMESTIC WATER PRESSURE TO CONFIRM ADEQUATE PRESSURE TO SERVE THE
DOMESTIC WATER SYSTEM. CONTRACTOR SHALL ALERT ENGINEER TO A POTENTIAL LOW PRESSURE CONDITION. WHERE PRESSURE
EXCEEDS 80PSI, PROVIDE PRESSURE REGULATING VALVE (WATTS LF223) AND UPSTREAM STRAINER (WATTS LSF777).
CONTRACTOR SHALL FIELD COORDINATE LOCATION OF ACCESSIBLE ISOLATION VALVES ON DOMESTIC HOT & COLD WATER SUPPLIES
TO FIXTURES OR GROUPS OF FIXTURES SUCH THAT THEY MAY BE SHUT OFF FOR SERVICING. SERVICE AND HOSE BIBB VALVES SHALL
BE IDENTIFIED. ALL OTHER VALVES INSTALLED IN LOCATIONS THAT ARE NOT ADJACENT TO THE FIXTURE(S) SHALL BE IDENTIFIED,
INDICATING THE FIXTURE(S) SERVED.
RETURN AIR PLENUMS
ALL EXPOSED MATERIALS WITHIN RETURN AIR PLENUMS SHALL BE NONCOMBUSTIBLE OR HAVE A FLAME SPREAD INDEX OF NOT MORE
THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50, AS DETERMINED IN ACCORDANCE WITH ASTM E84/UL723.
COPPER AND CAST IRON PIPING IS APPROVED. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL RETURN AIR PLENUM
LOCATIONS WITH THE MECHANICAL CONTRACTOR.
INSULATION
INSULATE ALL DOMESTIC HOT WATER AND HOT WATER RECIRCULATION PIPING IN ACCORDANCE WITH IECC TABLE C403.2.10. PIPE UP
TO 114": 1" THICK INSULATION. PIPE 112" OR LARGER: 112" THICK INSULATION
INSULATE ALL HORIZONTAL COLD WATER PIPING LOCATED ABOVE CEILING, VERTICAL PIPING LOCATED IN AN EXTERIOR WALL, EXPOSED
PIPING (I.E. MECH ROOMS). PIPE UP TO 1": 12" THICK. PIPING 114" AND OVER: 1" THICK INSULATION. ALL WATER AND DRAINAGE PIPING
INSTALLED IN EXTERIOR WALLS SHALL BE WRAPPED IN 1" THICK PIPE INSULATION AND BE LOCATED ON THE INTERIOR SIDE OF THE
BUILDING INSULATION. IF INSTALLED IN EXTERIOR BLOCK WALLS, INTERSTITIAL SPACES SHALL BE FILLED WITH FOAM INSULATION.
ALL JOINTS SHALL BE SEALED WITH MATCHING VAPOR BARRIER TAPE.
INSULATION SHALL HAVE A K-FACTOR (AVERAGE THERMAL CONDUCTIVITY) NOT TO EXCEED 0.27 BTU-IN/HR x SQFT x °F.
PROTECTION OF PIPING
PIPING PASSING UNDER FOOTINGS OR THROUGH FOUNDATION WALLS SHALL BE PROVIDED WITH A SLEEVE TWO PIPE SIZES LARGER
THAN THE PIPE. OPEN ENDS OF SLEEVES SHALL BE SEALED. PIPING PASSING THROUGH CONCRETE OR CINDER WALLS AND FLOORS
OR OTHER CORROSIVE MATERIAL SHALL BE PROTECTED IN ACCORDANCE WITH IPC 305.1. ALL PIPING INSTALLED THROUGH HOLES OR
NOTCHES IN STUDS, JOISTS, RAFTERS OR SIMILAR MEMBERS SHALL BE PROTECTED BY STEEL SHIELD PLATES IN ACCORDANCE WITH
IPC 305.6. VERTICAL STACKS IN WOOD CONSTRUCTION SHALL BE PROTECTED FROM BUILDING SETTLING WITH
COMPRESSION/EXPANSION FITTINGS AND PIPE CLAMPS INSTALLED PER MANUFACTURER'S RECOMMENDATIONS (FERNCO XJ SERIES OR
EQUAL).
SLEEVES AND PENETRATIONS
SLEEVES SHALL BE PROVIDED WHERE PIPES PASS THROUGH WALLS, FLOORS AND ROOFS.
PROVIDE STANDARD WEIGHT STEEL SLEEVES IN CONCRETE AND MASONRY CONSTRUCTION, PROVIDE 26GA GALVANIZED SHEET METAL
SLEEVES IN INTERIOR DRYWALL CONSTRUCTION. SLEEVES SHALL BE THE FULL THICKNESS OF WALLS AND SHALL ALLOW FOR THE FULL
THICKNESS OF PIPE INSULATION, WHERE APPLICABLE.
SLEEVES MAY BE OMITTED WHEN OPENINGS ARE CORE DRILLED FOR CONCEALED VERTICAL AND HORIZONTAL PIPING. SLEEVES ARE
NOT REQUIRED AT INDIVIDUAL PLUMBING FIXTURES OR IN CONCRETE FLOOR SLABS ON GRADE, UNLESS OTHERWISE NOTED.
SLEEVES FOR ALL PIPING PENETRATING FIRE RATED WALLS AND FLOORS SHALL BE PROVIDED WITH 3M PIPE BARRIER NO. CP-25 FIRE
PROOFING CAULKING, OR EQUAL, IN ANNULAR SPACE BETWEEN SLEEVE AND PIPING. CONTRACTOR SHALL VERIFY THE RATING OF THE
WALL AND CONFIRM THE PENETRATION PROTECTION PROVIDED MEETS THAT RATING.
PENETRATIONS THROUGH OUTSIDE WALLS SHALL BE WATERTIGHT. CAULK BETWEEN PLUMBING PIPE AND SLEEVE. PACK WITH
FIBERGLASS AND CAULK, 1" DEEP AT EACH FACE WITH NON-HARDENING SEALANT BETWEEN PIPE AND SLEEVE.
IN EXTERIOR WALLS AND BEARING PARTITIONS, WOOD STUDS ARE PERMITTED TO BE CUT OR NOTCHED TO A DEPTH NOT EXCEEDING
25 PERCENT OF THE WIDTH OF THE STUD. CUTTING OR NOTCHING OF STUDS TO A DEPTH NOT GREATER THAN 40 PERCENT OF THE
WIDTH OF THE STUD IS PERMITTED IN NONBEARING PARTITIONS NOT SUPPORTING LOADS OTHER THAN THE WEIGHT OF THE PARTITION.
BORED HOLES NOT GREATER THAN 40 PERCENT OF THE STUD WIDTH ARE PERMITTED TO BE BORED IN ANY WOOD STUD. BORED
HOLES NOT GREATER THAN 60 PERCENT OF THE STUD WIDTH ARE PERMITTED IN NONBEARING PARTITIONS IN ANY WALL WHERE EACH
BORED STUD IS DOUBLED, PROVIDED THAT NOT MORE THAN TWO SUCH SUCCESIVE DOUBLED STUDS ARE SO BORED. THE EDGE OF
A BORED HOLE SHALL NOT BE NEARER THAN 58 INCH (15.9 mm) TO THE EDGE OF THE STUD. BORED HOLES SHALL NOT BE LOCATED AT
THE SAME SECTION OF STUD AS A CUT OR NOTCH.
WASTE AND VENT PIPING SYSTEMS AND ACCESSORIES
SANITARY PIPING SHALL BE PVC SCHEDULE 40 SOLID WALL PIPE AND DWV FITTING SYSTEM.
PIPE AND FITTINGS SHALL BE MANUFACTURED FROM PVC COMPOUND WITH A CELL CLASS OF 12454 PER ASTM D-1784 AND
CONFORM WITH NATIONAL SANITATION FOUNDATION (NSF) STANDARD 14. PIPE SHALL BE IRON PIPE SIZE (IPS) CONFORMING TO
ASTM D-1785 AND ASTM D-2665. INJECTION MOLDED FITTINGS SHALL CONFORM TO ASTM D-2665. FABRICATED FITTINGS SHALL
CONFORM TO ASTM F-1866. SOLVENT CEMENTS SHALL CONFORM TO ASTM D-2564. PRIMER SHALL CONFORM TO ASTM F-656.
BURIED PIPE SHALL CONFORM TO ASTM D-2321.
WASTE AND VENT PIPING SHALL BE TESTED IN ACCORDANCE WITH THE GOVERNING CODES. AT A MINIMUM, WASTE PIPING SHALL BE
TESTED WITH AT LEAST 10 FOOT OF WATER HEAD PRESSURE APPLIED.
ALL VENTS THROUGH ROOF SHALL BE LOCATED AT LEAST 10'-0" AWAY FROM ANY AIR INTAKE, EVAPORATIVE COOLER, OR ANY OTHER
DEVICE THAT WOULD DRAW AIR FROM THE VENT. FLASH AROUND ALL PIPES PENETRATING THROUGH ROOF WITH STANDARD
MANUFACTURED FLASHINGS. FLASHING SHALL BE SHEET METAL WITH RUBBER GASKETS AND SHALL EXTEND INTO ROOFING AND UP
PIPE DISTANCES IN ACCORDANCE WITH THE LOCAL CODE.
NO DOUBLE COMBINATION FITTINGS MAY BE UTILIZED IN THE HORIZONTAL.
WHERE TWO HORIZONTAL PIPES (BACK-TO-BACK WATER CLOSETS OR TWO SANITARY BRANCHES) COMBINE IN THE VERTICAL, A
DOUBLE COMBINATION WYE EIGHTH BEND FITTING SHALL BE INSTALLED. DOUBLE SANITARY TEE OR SANITARY CROSS IS NOT
ACCEPTABLE.
WHERE DRAWINGS REQUIRE CONNECTION TO EXISTING SANITARY SEWER PIPING IN BUILDING, IT IS THE CONTRACTOR'S RESPONSIBILITY
TO FIELD DETERMINE EXACT LOCATION, DEPTH AND DIRECTION OF FLOW PRIOR TO COMMENCING WORK. CONTRACTOR SHALL ALERT
ARCHITECT/ENGINEER IF THERE IS A POTENTIAL ISSUE MAINTAINING PROPER SLOPE IN CONNECTING TO EXISTING, OR IF THERE IS A
MORE DIRECT CONNECTION POSSIBLE. CONTRACTOR SHALL CONFIRM THAT ANY EXISTING PIPING TO BE REUSED IS CLEAN, FREE OF
DEFECTS, ADEQUATELY SLOPED (18"/FT MINIMUM) AND THAT THERE ARE NO DIPS THAT COULD HOLD WATER. PROVIDE CAMERA
SCOPING TO DOCUMENT THIS INFORMATION. CONTRACTOR SHALL ALERT ARCHITECT/ENGINEER OF ANY DEFICIENCIES.
3150 Holcomb Bridge Road
Norcross, Georgia 30071
404.330.9798
PROJECT # 125297
SO
GO
ARCHITECTURE & INTERIORS
ATLANTA, GA TEL 678.271.8054 STUDIOSOGO.COM
ISSUANCE SCHEDULE
06.27.25 PERMIT
REVISION SCHEDULE
MARK DATE
DESCRIPTION
Project ID
Drawn By
Checked By
Sheet Title
2428
PG
MR
GENERAL
Drawing
No.
P-0.1
Paper Size:
24" x 36"
INDIRECT WASTE DETAIL
NO SCALE
SLOPE INDIRECT
WASTE PIPING @ 14"/FT
MINIMUM
DISCHARGE INTO
FLOOR SINK W/AIR GAP
(GAP TO BE TWICE THE
DIAMETER OF PIPE AND
NOT LESS THAN 2").
PROVIDE CHAMFER AT
PIPE END.
PROVIDE 12
OR
3
4
GRATE ON FLOOR
SINK, BASED ON
NUMBER OF INDIRECT
WASTE LINES.
INDIRECT WASTE FROM
PLUMBING FIXTURE
(RUN FULL SIZE OF
UNIT CONNECTION
SUPPORT
HORIZONTAL PIPING
FROM FLOOR WITH
PIPE STAND
FLOOR SINK OR HUB
DRAIN (REFER TO
PLANS FOR REQUIRED
DRAIN TYPE)
INDIRECT WASTE PIPING THAT DRAINS ICE MAKERS OR CONDENSATE FROM ANY
AIR CONDITIONING OR REFRIGERATION EQUIPMENT SHALL BE INSULATED
POINT OF USE MIXING VALVE
NO SCALE
110°HW OUTLET
38" COMPRESSION
FITTING (TYP)
MIXING VALVE (SEE
PLUMBING FIXTURE
SCHEDULE)
38" FAUCET
CONNECTIONS
KEYNOTES
1 3" P-TRAP AT BASE OF TRENCH DRAIN.
2 112" CW & 34" HW A/C & CONNECT NEW DISTRIBUTION TO EXISTING HOT &
COLD WATER SUPPLIES IN THIS AREA, FIELD VERIFY SIZES AND EXACT
LOCATIONS.
3 2" V DN.
4 4" S B/F & CONNECT TO EXISTING SANITARY PIPING IN BUILDING. FIELD
VERIFY EXACT LOCATION, DEPTH AND DIRECTION OF FLOW PRIOR TO
COMMENCING WORK.
5 2" V A/C & CONNECT TO EXISTING VENT PIPING. FIELD VERIFY EXACT
LOCATION PRIOR TO COMMENCING WORK.
6 3" FLOOR SINK FS-1. DISCHARGE ALL NEARBY INDIRECT WASTE
CONNECTIONS FULL SIZE W/AIR GAP AT LEAST TWICE THE DIAMETER OF
INDIRECT WASTE PIPE (SEE DETAIL). FIELD COORDINATE WITH
INSTALLED EQUIPMENT.
7 2" VENT TO AIR ADMITTANCE VALVE AAV-1 UNDER COUNTER.
8 12" CW & 12" 140°HW TO FIXTURE.
9 12" CW & 12" 140°HW TO FIXTURE, PROVIDE MIXING VALVE MV-1 TO
TEMPER HW TO 110°.
10 12" CW & 12" HW UP FROM B/F. 12" CW & 12" 140°HW TO FIXTURE,
PROVIDE MIXING VALVE MV-1 TO TEMPER HW TO 110°.
11 12" CW TO WSB-1, PROVIDE IN-LINE BACKFLOW PREVENTER (WATTS
'SD3,' ASSE 1022).
12 12" CW & 12" HW DN & B/F.
13 12" CW & 12" HW DN.
14 114" CW DN TO WATER CLOSET, PROVIDE WHA-A AT BASE OF DROP.
GENERAL NOTES
CONTRACTOR TO ENSURE 140° SETPOINT FOR EXISTING WATER HEATER.
CONTRACTOR TO ENSURE THERMOSTATIC MIXING VALVES ARE PROVIDED TO
LAVATORIES AND HAND WASHING SINKS TO TEMPER HOT WATER DOWN TO
110°.
HW INLET
CW INLET
WALL SUPPLIES
WITH ANGLE STOPS
12x24 (304.8 x 609.6)
10
12" CW & 12" HW B/F
11
ICE
9
FRIDGE
12"
12"
12
12" 12"
12"
12"
8
14
WC-1
14
WC-1
114"
3 4"
L-1
112"
114"
L-1
3 4"
2
13 13
112"
2 1/4" = 1'-0" FIRST FLOOR PLAN - SUPPLY
3150 Holcomb Bridge Road
Norcross, Georgia 30071
404.330.9798
PROJECT # 125297
SO
GO
ARCHITECTURE & INTERIORS
ATLANTA, GA TEL 678.271.8054 STUDIOSOGO.COM
WASTE/VENT ISOMETRIC
NO SCALE
SK FS
AAV
3" FCO
3"
FD
4"
2"
2"
FS
3"
3"
4"
SK
FS
2"
S
4"
3"
4" 3"
2" 2"
FD
4"
3"
FS
3"
4"
LAV
2"
2"
FD
4"
2" 3" S
3" 3"
WC
4"
2"
4"
2"
4"
2"
2"
WC
LAV
FD 4" 4"
2" 3" 4"
3"
3" 4"
6
FCO
12x24 (304.8 x 609.6)
7
6
FD-2
3
1
S
ICE
TD-1
FRIDGE
FD-2
6
3
WC-1
S
FD-1
L-1
WC-1
FD-1
L-1
3
5
4
3
1 1/4" = 1'-0" FIRST FLOOR PLAN - DRAINAGE
0' 2' 4'
N
8'
12'
ISSUANCE SCHEDULE
06.27.25 PERMIT
REVISION SCHEDULE
MARK DATE
DESCRIPTION
Project ID
Drawn By
Checked By
Sheet Title
2428
PG
MR
FLOOR PLANS
Drawing
No.
P-1.0
Paper Size:
24" x 36"
SPECIFICATIONS
GENERAL NOTES:
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL CEILING
MOUNTED EQUIPMENT.
ALL DUCT DIMENSIONS INDICATED IN THESE DOCUMENTS ARE INSIDE-CLEAR DIMENSIONS.
PORTIONS OF DUCTWORK OR PIPING VISIBLE THROUGH GRILLES AND REGISTERS IN FINISHED
AREAS SHALL BE PAINTED FLAT BLACK. PAINT BLACK BEHIND ALL GRILLES.
ALL WIRING IN THE CEILING PLENUM SHALL BE PLENUM RATED CABLE.
MOUNTING FRAME OF CEILING MOUNTED AIR DISTRIBUTION DEVICES SHALL BE COMPATIBLE
WITH CEILING TYPE. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPE.
ALL FIRE SEPARATIONS MUST BE PROTECTED WHEN APPLICABLE.
PROVIDE NEW FILTERS (MERV 7 OR BETTER PER OWNER) FOR ALL APPLICABLE HVAC
EQUIPMENT AT THE END OF CONSTRUCTION.
ALL MATERIAL IN PLENUM MUST MEET FIRE AND SMOKE SPREAD AS REQUIRED BY NFPA 90A.
ALL ROOF PENETRATIONS TO BE 12" APART AND AT LEAST 12" AWAY FROM CURBS, WALLS,
AND DRAIN SUMPS TO PROVIDE ROOFING CONTRACTOR WITH SUFFICIENT ACCESS FOR
FLASHING EACH ROOF PENETRATION.
SUBSTITUTIONS MUST BE APPROVED IN WRITING BY ARCHITECT PRIOR TO BID SUBMISSION.
CONTRACTOR SHALL REVIEW ALL CONTRACT DOCUMENTS AND SHALL BE FAMILIAR WITH THE
SCOPE AND REQUIREMENTS OF THIS PROJECT. ANY DISCREPANCIES OR LACK OF CLARITY IN
THE DOCUMENTS SHALL BE IDENTIFIED TO THE ARCHITECT OR ENGINEER PRIOR TO THE
SUBMISSION OF PRICING BIDS. WITH A SUBMITTED BID, CONTRACTOR IS ACCEPTING THESE
DOCUMENTS AS SUFFICIENT DEFINITION OF THE SCOPE OF WORK, AND ANY ADDITIONAL
COSTS BASED ON UNCLARITY OF CONTRACT DOCUMENTS WILL NOT BE CONSIDERED.
THE CONTRACTOR SHALL REFERENCE THE FULL SET OF CONSTRUCTION DOCUMENTS DURING
PRICING AND CONSTRUCTION FOR COORDINATION BETWEEN DISCIPLINES RELATIVE TO THE
MECHANICAL SCOPE.
GUARANTEE:
GUARANTEE THAT EACH PIECE OF APPARATUS SHALL BE OF THE CUSTOMARY STANDARD AND
QUALITY FURNISHED BY THE DESIGNED MANUFACTURER FOR THAT CATALOG NUMBER.
GUARANTEE THAT THE AIR SYSTEMS SHALL OPERATE WITHOUT AERODYNAMIC NOISE
GENERATED FROM THE FAULTY INSTALLATION OF DUCT WORK OR ANY COMPONENT OF THE
AIR DISTRIBUTION SYSTEM.
GUARANTEE THAT ALL SYSTEMS AND COMPONENTS SHALL BE PROVIDED WITH A ONE YEAR
WARRANTY FROM THE TIME OF DATE OF SUBSTANTIAL COMPLETION. THE WARRANTY SHALL
COVER ALL MATERIALS AND WORKMANSHIP. DURING THIS WARRANTY PERIOD, ALL DEFECTS IN
MATERIALS AND WORKMANSHIP SHALL BE CORRECTED BY REPAIR OR REPLACEMENT WITHOUT
INCURRING ADDITIONS TO THE CONTRACT.
EXISTING CONDITIONS:
CONTRACTOR SHALL VISIT THE SITE AND UNDERSTAND JOB CONDITIONS BEFORE SUBMITTING
A PROPOSAL. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY LOCATIONS AND
SIZES OF ALL EXISTING UTILITY SERVICES PRIOR TO SUBMITTING HIS PROPOSAL. NO
CONSIDERATION WILL BE GIVEN TO CLAIMS FOR EXTRA COST ARISING FROM CONTRACTOR'S
FAILURE TO BE FULLY COGNIZANT OF JOB OR SITE CONDITIONS EXISTING AT TIME OF
ACCEPTANCE OF BID.
ACTIVE SERVICES: WHEN ENCOUNTERED IN WORK, PROTECT, BRACE, SUPPORT EXISTING
ACTIVE SEWERS, GAS AND OTHER SERVICES REQUIRED FOR PROPER EXECUTION OF WORK. IF
EXISTING ACTIVE SERVICES ARE ENCOUNTERED THAT REQUIRE RELOCATION, RELOCATE AS
APPROVED. DO NOT PREVENT OR DISTURB OPERATION OF ACTIVE SERVICES THAT ARE TO
REMAIN.
INACTIVE SERVICES: WHEN ENCOUNTERED IN WORK, REMOVE, CAP OR PLUG INACTIVE
SERVICES, AS INDICATED.
INTERRUPTION OF SERVICES: WHERE WORK MAKES TEMPORARY SHUT-DOWNS OF SERVICES
UNAVOIDABLE, SHUT DOWN AT NIGHT, OR AT SUCH TIMES AS APPROVED BY OWNER, WHICH
WILL CAUSE LEAST INTERFERENCE WITH ESTABLISHED OPERATING ROUTINE. ARRANGE WORK
TO ASSURE THAT SERVICES WILL BE SHUT DOWN ONLY DURING TIME ACTUALLY REQUIRED TO
MAKE NECESSARY CONNECTION TO EXISTING WORK.
WHERE EXISTING WALLS, CEILINGS, FLOORS, ETC., ARE CUT OR OTHERWISE DAMAGED DURING
CONSTRUCTION, REPAIR ALL SURFACES TO THEIR ORIGINAL CONDITION.
TEST AND BALANCE:
TEST AND BALANCE (TAB) CONTRACTOR SHALL HOLD A CURRENT NATIONAL BALANCING
COUNCIL (NBC) CERTIFICATION AND POSSESS ACCURATE AND CALIBRATED INSTRUMENTS.
TAB WORK AND REPORTS SHALL BE PER NBC PRACTICAL STANDARDS, PROCEDURES AND
FORMS. ACCEPTIBLE ALTERNATIVE TAB FIRM CERTIFICATIONS/PROCEDURES: NEBB, AABC, OR
TABB.
PRIOR TO COMMENCEMENT OF THE TAB WORK, THE MECHANICAL SYSTEMS ARE TO BE
STARTED AND FULLY FUNCTIONING. A CHECKLIST PRIOR TAB WORK IS TO BE SENT TO THE
INSTALLING CONTRACTOR AND RETURNED ATTESTING TO THE READINESS OF THE SYSTEMS
FOR BALANCING.
PREFERRED TAB FIRM: P-TAB.COM
CEILING FAN:
CEILING MOUNTED EXHAUST FANS SHALL BE OF THE CENTRIFUGAL DIRECT DRIVE TYPE. THE
FAN HOUSING SHALL BE CONSTRUCTED OF STEEL. THE PLASTIC DUCT COLLAR SHALL BE A
TAPERED SLEEVE FOR EASE OF CONNECTION TO 3 IN AND 4 IN ROUND DUCTWORK AND SHALL
INCLUDE A BACKDRAFT DAMPER. THE GRILLE SHALL BE CONSTRUCTED OF NON-YELLOWING
HIGH STRENGTH POLYMER AND ATTACHED TO THE HOUSING WITH TORSION SPRINGS. THE
WHEELS SHALL BE CONSTRUCTED OF HIGH STRENGTH POLYMER. THE ACCESS FOR WIRING
SHALL BE EXTERNAL. THE MOTOR DISCONNECT SHALL BE INTERNAL AND OF THE PLUG IN TYPE.
ALL FANS SHALL BEAR THE AMCA CERTIFIED RATINGS SEALS FOR SOUND AND AIR
PERFORMANCE AND SHALL BE U.L. LISTED.
SPECIFICATIONS
DUCTWORK AND ACCESSORIES:
INDUSTRY STANDARDS: COMPLY WITH SMACNA (SHEET METAL AND AIR CONDITIONING
CONTRACTORS' NATIONAL ASSOCIATION) HVAC DUCT CONSTRUCTION STANDARDS,
RECOMMENDATIONS FOR FABRICATION, GAUGES, CONSTRUCTION AND DETAILS, AND
INSTALLATION PROCEDURES, EXCEPT AS OTHERWISE INDICATED.
COMPLY WITH ASHRAE (AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR
CONDITIONING ENGINEERS) FUNDAMENTALS HANDBOOK RECOMMENDATIONS, EXCEPT AS
OTHERWISE INDICATED.
DUCTWORK METAL AND GAUGES: EXCEPT AS OTHERWISE INDICATED, FABRICATE DUCTWORK
FROM GALVANIZED SHEET STEEL COMPLYING WITH ASTM A527, LOCKFORMING QUALITY, WITH
ASTM A525 G90 ZINC COATING, MILL PHOSPHATIZED. GAUGES TO COMPLY WITH SMACNA
STANDARDS.
DUCT SEALANT: NON-HARDENING, NON-MIGRATING MASTIC OR LIQUID ELASTIC SEALANT (TYPE
APPLICABLE FOR THE FABRICATION/INSTALLATION DETAIL) AS COMPOUNDED AND
RECOMMENDED BY THE MANUFACTURER SPECIFICALLY FOR SEALING JOINTS AND SEAMS IN
DUCTWORK.
DUCTWORK SUPPORT MATERIALS: EXCEPT AS OTHERWISE INDICATED, PROVIDE UPPER
ATTACHMENT, HANGERS OF GALVANIZED STEEL STRAPS, OR STEEL RODS AND LOWER
ATTACHMENT FOR SUPPORT OF DUCTWORK. HANGING/SUPPORT SYSTEMS SHALL BE IN
ACCORDANCE WITH SMACNA REQUIREMENTS.
EXPOSED DUCTWORK SHALL BE DOUBLE-WALL SPIRAL PIPE WITH PAINT GRIP UNLESS
OTHERWISE NOTED OR SUBSTITUTION APPROVED BY OWNER.
VOLUNTARY ALTERNATE EXPOSED DUCTWORK SHALL BE SINGLE-WALL SPIRAL PIPE UNLESS
OTHERWISE NOTED OR SUBSTITUTION APPROVED BY OWNER. ALL EXPOSED DUCTWORK
SHALL BE LINED IN LIEU OF WRAPPED. DUCT LINER THERMAL RESISTANCE SHALL MEET THE
MINIMUM VALUES SPECIFIED IN PARAGRAPH 'DUCT INSULATION' BELOW.
DUCTWORK LOCATED OUTSIDE OF THE BUILDING ENVELOPE SHALL BE THERMADUCT
PRODUCTS OR COVERED WITH 3M VENTURECLAD JACKETING, OR EQUAL PRODUCT, AND
SEALED WEATHER-TIGHT.
DUCT INSULATION:
R-6 SUPPLY, OUTSIDE AND RETURN AIR DUCT INSULATION IN CONDITIONED AND
UNCONDITIONED SPACES
R-8 SUPPLY AND RETURN AIR DUCT INSULATION OUTSIDE THE BUILDING
R-8 INSULATION BETWEEN DUCTS AND THE BUILDING EXTERIOR WHEN DUCTS ARE PART OF A
BUILDING ASSEMBLY
DIFFUSERS, GRILLES, & REGISTERS:
EGGCRATE GRILLE:
RETURN GRILLES SHALL BE TITUS MODEL 50F FOR THE SIZES AND MOUNTING TYPES AS
SHOWN ON THE PLANS AND OUTLET SCHEDULE. RETURN GRILLES MUST PROVIDE A FREE AREA
OF AT LEAST 90%. OUTER BORDERS SHALL BE CONSTRUCTED OF HEAVY EXTRUDED
ALUMINUM WITH A THICKNESS OF 0.040-0.050 INCH AND SHALL HAVE COUNTERSUNK
SCREW HOLES FOR A NEAT APPEARANCE. BORDER WIDTH SHALL BE 1¼ INCHES ON ALL SIDES
AND SHALL BE INTERLOCKED AT THE FOUR CORNERS AND MECHANICALLY STAKED TO FORM A
RIGID FRAME. CHOICE OF THREE SIZES OF ALUMINUM GRID: ½ X ½ X ½ INCH, ½ X ½ X 1
INCH, OR 1 X 1 X 1 INCH SHALL BE AVAILABLE.
OPTIONAL OPPOSED-BLADE VOLUME DAMPER SHALL BE CONSTRUCTED OF HEAVY GAUGE
STEEL OR ALUMINUM. DAMPER MUST BE OPERABLE FROM THE FACE OF THE GRILLE.
SLOT AND LINEAR DIFFUSERS:
DIFFUSERS SHALL BE OF THE SIZES AND MOUNTING TYPES SHOWN ON THE PLANS AND
OUTLET SCHEDULE. DIFFUSERS SHALL HAVE 3/4-,1-, OR 1 1/2-INCH SLOT WIDTH WITH 1 TO 4
PARALLEL SLOTS, AS SHOWN ON THE PLANS AND OUTLET SCHEDULE. LENGTH SHALL BE AS
SHOWN ON THE PLANS AND OUTLET SCHEDULE. DIFFUSERS SHALL BE CONSTRUCTED OF
24-GAUGE STEEL OR 0.040 ALUMINUM.
EACH DIFFUSER SHALL HAVE A PATTERN CONTROLLER WITH TIGHT SEALING GASKET EDGE AND
PROVIDES FULL HORIZONTAL FLOW. THE PATTERN CONTROLLER MUST BE FIELD ADJUSTABLE
FROM THE FACE OF THE DIFFUSER TO CHANGE THE DISCHARGE PATTERN FROM HORIZONTAL
TO VERTICAL.
THE FINISH SHALL BE #26 WHITE. THE FINISH SHALL BE AN ANODIC ACRYLIC PAINT, BAKED AT
315°F FOR 30 MINUTES. THE PENCIL HARDNESS MUST BE HB TO H. THE PAINT MUST PASS A
100-HOUR ASTM B117 CORROSIVE ENVIRONMENTS SALT SPRAY TEST WITHOUT CREEPAGE,
BLISTERING OR DETERIORATION OF FILM. THE PAINT MUST PASS A 250-HOUR ASTM D870
WATER IMMERSION TEST. THE PAINT MUST ALSO PASS THE ASTM D2794 REVERSE IMPACT
CRACKING TEST WITH A 50-INCH POUND FORCE APPLIED.
OPTIONAL DAMPER SHALL BE CONSTRUCTED OF HEAVY GAUGE STEEL. DAMPER MUST BE
OPERABLE FROM THE FACE OF THE DIFFUSER.
OPTIONAL MOLDED INSULATION BLANKET SHALL BE AVAILABLE. THE INSULATION SHALL BE R-6,
FOIL-BACKED AND PROVIDED AN ADDITIONAL 1-INCH GAP AROUND THE NECK TO INSTALL
INSULATED FLEX DUCT.
THE MANUFACTURER SHALL PROVIDE PUBLISHED PERFORMANCE DATA FOR THE SLOT/LINEAR
DIFFUSER. THE DIFFUSER SHALL BE TESTED IN ACCORDANCE WITH ANSI/ASHRAE STANDARD
70-2006.
LOUVERED FACE DIFFUSERS:
CEILING DIFFUSERS SHALL BE OF THE SIZES AND MOUNTING TYPES SHOWN ON THE PLANS
AND OUTLET SCHEDULE. A UNIFORM FACE SIZE AND APPEARANCE WHEN DIFFERENT NECK
SIZES ARE USED IN THE SAME AREA. ALL CONES SHALL BE ONE PIECE PRECISION
DIE-STAMPED; THE BACK CONE SHALL ALSO INCLUDE AN INTEGRALLY DRAWN INLET (WELDED-IN
INLETS AND CORNER JOINTS ARE NOT ACCEPTABLE). THE TWO INNER CONES SHALL BE
CONSTRUCTED AS A SINGLE, REMOVABLE INNER CONE ASSEMBLY FOR EASY INSTALLATION
AND CLEANING. THE INNER CONE ASSEMBLY MUST HAVE A HOLE WITH REMOVABLE PLUG IN
THE CENTER TO ALLOW QUICK ADJUSTMENT OF AN OPTIONAL INLET DAMPER WITHOUT
REMOVING THE INNER CONE ASSEMBLY. DIFFUSERS SHALL BE CONSTRUCTED OF 24-GAUGE
STEEL OR 0.040 ALUMINUM.
THE FINISH SHALL BE #26 WHITE. THE FINISH SHALL BE AN ANODIC ACRYLIC PAINT, BAKED AT
315°F FOR 30 MINUTES. THE PENCIL HARDNESS MUST BE HB TO H. THE PAINT MUST PASS A
100-HOUR ASTM B117 CORROSIVE ENVIRONMENTS SALT SPRAY TEST WITHOUT CREEPAGE,
BLISTERING OR DETERIORATION OF FILM. THE PAINT MUST PASS A 250-HOUR ASTM D870
WATER IMMERSION TEST. THE PAINT MUST ALSO PASS THE ASTM D2794 REVERSE IMPACT
CRACKING TEST WITH A 50-INCH POUND FORCE APPLIED.
OPTIONAL ROUND DAMPER SHALL BE CONSTRUCTED OF HEAVY GAUGE STEEL. DAMPER MUST
BE OPERABLE FROM THE FACE OF THE DIFFUSER. OPTIONAL SECTORIZING BAFFLES SHALL BE
AVAILABLE TO RESTRICT THE DISCHARGE AIR IN CERTAIN DIRECTIONS.
OPTIONAL MOLDED INSULATION BLANKET SHALL BE AVAILABLE. THE INSULATION WILL BE R-6,
FOIL-BACKED AND PROVIDED AN ADDITIONAL 1-INCH GAP AROUND THE NECK TO INSTALL
INSULATED FLEX DUCT.
THE MANUFACTURER SHALL PROVIDE PUBLISHED PERFORMANCE DATA FOR THE SQUARE
DIFFUSER. THE DIFFUSER SHALL BE TESTED IN ACCORDANCE WITH ANSI/ASHRAE STANDARD
70-2006.
LEGEND
SYMBOLS
X1
X2
FD
FSD
FD
FSD
T
H
S
UNIT
#
3150 Holcomb Bridge Road
Norcross, Georgia 30071
404.330.9798
PROJECT # 125297
SO
GO
ARCHITECTURE & INTERIORS
ATLANTA, GA TEL 678.271.8054 STUDIOSOGO.COM
DESCRIPTION
DIFFUSER, GRILLE, REGISTER OR LOUVER TAG
X1 = TYPE, X2 = CFM
POSITIVE PRESSURE (AIR GOES OUT) DIFFUSER OR REGISTER, 4-WAY
AIR PATTERN (UNLESS OTHERWISE NOTED)
NEGATIVE PRESSURE (AIR GOES IN) GRILLE
POSITIVE PRESSURE AIRFLOW (TYP. SUPPLY)
NEGATIVE PRESSURE AIRFLOW (TYP. RETURN/EXHAUST)
FLEXIBLE DUCT
MANUAL VOLUME DAMPER (MVD)
BACKDRAFT DAMPER (BDD)
VERTICAL (TYP. WALL) FIRE DAMPER
VERTICAL (TYP. WALL) COMBINATION FIRE/SMOKE DAMPER
HORIZONTAL (TYP. FLOOR/CEILING) FIRE DAMPER
HORIZONTAL (TYP. FLOOR/CEILING) COMBINATION FIRE/SMOKE
DAMPER
THERMOSTAT
HUMIDISTAT
REMOTE TEMPERATURE SENSOR
INTERNALLY LINED DUCT
DUCT UP
DUCT UP
DUCT DOWN
SUPPLY DUCT
EQUIPMENT TYPE
EQUIPMENT NUMBER. WHERE A LETTER IS USED, THERE ARE MULTIPLE
INSTANCES.
ABBREVIATIONS
AFF
BDD
AHU
CO2
CU
D
DB
DH
EA
EAT
EDH
EF
ESP
EWH
F
FCU
FD
FSD
FURN
H
IH
LAT
LWT
ABOVE FINISHED FLOOR
M
BACKDRAFT DAMPER
MA
AIR HANDLING UNIT
CARBON DIOXIDE
CONDENSING UNIT
CONDENSATE DRAIN
MAU
MAV
MBH
MFCU
DRY BULB
MHP
DEHUMIDIFIER
MVD
EXHAUST AIR
NC
ENTERING AIR TEMPERATURE
NO
ELECTRIC DUCT HEATER
OA
EXHAUST FAN
OBD
EXTERNAL STATIC PRESSURE
PIU
ELECTRIC WALL HEATER
RA
DEGREES FAHRENHEIT
RH
FAN COIL UNIT
RTU
FIRE DAMPER
SA
COMBINATION FIRE/SMOKE DAMPER SP
FURNACE
HUMIDISTAT
U.N.O
UC
INTAKE HOOD
VAV
LEAVING AIR TEMPERATURE
WB
LEAVING WATER TEMPERATURE
WL
MOTOR
MAKE-UP AIR
MAKE-UP AIR UNIT
MANUAL AIR VENT
1,000 BTU PER HR
MINI FAN COIL UNIT
MINI HEAT PUMP
MANUAL VOLUME DAMPER
NORMALLY CLOSED
NORMALLY OPEN
OUTSIDE AIR
OPPOSED BLADE DAMPER
POWER INDUCTION UNIT
RETURN AIR
RELIEF HOOD
ROOFTOP UNIT
SUPPLY AIR
STATIC PRESSURE
UNLESS NOTED OTHERWISE
UNDER CUT DOOR
VARIABLE AIR VOLUME
WET BULB
WALL LOUVER
ISSUANCE SCHEDULE
06.27.25 PERMIT
REVISION SCHEDULE
MARK DATE
DESCRIPTION
Project ID
Drawn By
Checked By
Sheet Title
2428
SC
JD
GENERAL
Drawing
No.
M-0.1
Paper Size:
24" x 36"
3150 Holcomb Bridge Road
Norcross, Georgia 30071
404.330.9798
PROJECT # 125297
SO
GO
ARCHITECTURE & INTERIORS
ATLANTA, GA TEL 678.271.8054 STUDIOSOGO.COM
DIFFUSER, GRILLE, AND REGISTER SCHEDULE
CALLOUT
DESCRIPTION
RC1818
EGGCRATE GRILLE
FACE SIZE
(IN)
18x18
INLET SIZE
(IN)
18x18
NOISE
CRITERIA @
MAX CFM
25
MODEL
TITUS 50F
S2S406
PLENUM SLOT 4' (2) 1" SLOTS 6" NECK
48x4
25
TITUS TBD 80
S2S408
PLENUM SLOT 4' (2) 1" SLOTS 8" NECK
48x4
25
TITUS TBD 80
SCEC2424 EGGCRATE GRILLE
24x24
24x24
25
TITUS 50F
SCL06
LOUVERED FACE SUPPLY
12x12
25
TITUS TMS
A. REFER TO ARCHITECTURAL DRAWINGS FOR COLOR SELECTIONS. CONTRACTOR SHALL SUBMIT COLOR/FINISH CHARTS FOR
ARCHITECTURAL REVIEW AND SELECTION.
B. THE CONTRACTOR SHALL COORDINATE AIR DEVICE FRAME AND/OR SUSPENSION TYPE WITH THE ARCHITECTURAL REFLECTED CEILING
PLAN.
DIFFUSER TAKE-OFF DETAIL
NO SCALE
ROUND SHEET
METAL DUCT
DIAMETER AS
INDICATED ON
PLANS.
TRUNK DUCT
SPIN-IN FITTING
WITH SCOOP
DAMPER HERE FOR
ACCESSIBLE CEILINGS
NYLON TIE ON EXTERIOR INSULATION
NYLON TIE ON INTERNAL LINER
INTERIOR LINER
PREINSULATED FLEXIBLE
DUCTWORK. SEE
SPECIFICATIONS. LENGTH
SHALL NOT EXCEED 8'-0".
PROVIDE SUPPORT PER
SMACNA STANDARDS.
INSTALL FREE OF KINKS &
SAGS.
DAMPER HERE FOR
INACCESSIBLE CEILINGS
(I.E. HARD CEILINGS)
PROVIDE FACTORY,
PRE-MOLDED INSULATION
BLANKET ON DIFFUSER
BACKPLATE
NOTE:
CONNECT FLEX DUCT ENDS TO
SHEET METAL DUCT AND DIFFUSER
NECK WITH NYLON TIES. INTERIOR
LINER AND EXTERIOR INSULATION OF
FLEX DUCT TO BE TIED INDIVIDUALLY.
INSTALL USING TENSIONING TOOL AS
PER MANUFACTURER'S
RECOMMENDATIONS.
SUPPLY DIFFUSER CEILING
SEE ARCH.
WHERE BRANCH DUCT SIZE DIFFERS FROM
SCHEDULED DIFFUSER NECK SIZE, CONTRACTOR
SHALL PROVIDE NECESSARY TRANSITION.
PLENUM SLOT DIFFUSER DETAIL
NO SCALE
NYLON TIE ON EXTERIOR INSULATION
NYLON TIE ON INTERNAL LINER
INTERIOR LINER
ROUND SHEET
METAL DUCT
DIAMETER AS
INDICATED ON
PLANS.
BRANCH DUCT
NOTE:
CONNECT FLEX DUCT ENDS TO
CEILING
SEE ARCH.
SHEET METAL DUCT AND DIFFUSER
NECK WITH NYLON TIES. INTERIOR
LINER AND EXTERIOR INSULATION OF
FLEX DUCT TO BE TIED INDIVIDUALLY.
INSTALL USING TENSIONING TOOL AS
PER MANUFACTURER'S RECOMMENDATIONS.
PREINSULATED FLEXIBLE
DUCTWORK. SEE
SPECIFICATIONS. LENGTH
SHALL NOT EXCEED 8'-0".
PROVIDE SUPPORT PER
SMACNA STANDARDS.
INSTALL FREE OF KINKS &
SAGS.
DAMPER HERE FOR
INACCESSIBLE CEILINGS
(I.E. HARD CEILINGS)
SUPPLY DIFFUSER
WITH ADJUSTABLE
AIR PATTERN CONTROL
AND ACCESSIBLE INLET
DAMPER CONTROL
DUCTWORK DETAILS
COPYRIGHT - PROFICIENT ENGINEERING, INC. - 2009 - WWW.PROFICIENTENGINEERING.COM
NO SCALE
S-CLIP JOINT OR
ADHESIVE GASKET
FITTING
45°
LATERAL
TEE
ROUND - ROUND
CONICAL TEE
AIRFLOW
M.V.D.
RECTANGULAR - ROUND
M.V.D.
AIRFLOW
X1
X2
WHERE:
X2 = (1/4)*(X1), 4" MIN.
RECTANGULAR - RECTANGULAR
ISSUANCE SCHEDULE
06.27.25 PERMIT
REVISION SCHEDULE
MARK DATE
DESCRIPTION
Project ID
Drawn By
Checked By
Sheet Title
2428
SC
JD
DETAILS &
SCHEDULES
Drawing
No.
M-0.2
Paper Size:
24" x 36"
24" x 36"
Paper Size:
12'
8'
0' 2' 4'
1 1/4" = 1'-0" FIRST FLOOR PLAN - MECHANICAL
Drawing
No.
M-1.0
N
FLOOR PLAN
MECHANICAL
2428
SC
JD
Project ID
Drawn By
Checked By
Sheet Title
DESCRIPTION
MARK DATE
REVISION SCHEDULE
ISSUANCE SCHEDULE
06.27.25 PERMIT
SO
GO
ARCHITECTURE & INTERIORS
ATLANTA, GA TEL 678.271.8054 STUDIOSOGO.COM
3150 Holcomb Bridge Road
Norcross, Georgia 30071
404.330.9798
PROJECT # 125297
This is the opportunity summary page. It provides an overview of this opportunity and a preview of the attached documentation.
Daily notification on new contract opportunities

With GovernmentContracts, you can:

  • Find more opportunities and win more business
  • Receive daily alerts for all new bid opportunities
  • Get contract opportunities matched to your business
ONE WEEK FREE TRIAL

See also

..., (Not Otherwise Classified) 91065 Remodeling and Alteration Services 90922 Building Construction, Non...

State Government of Georgia

Bid Due: 6/04/2026

...Construction, Non-Residential, Office Bldg., etc. 91065 Remodeling and Alteration Services BuyerContact: Victor Colon ...

State Government of Georgia

Bid Due: 7/17/2026

..., regulations, specifications, and requirements. NIGP Codes Code Description 91065 Remodeling and Alteration...

State Government of Georgia

Bid Due: 6/30/2026

...Services: Granite, Marble, and Terr 91065 Remodeling and Alteration Services 90945 Finishes, Flooring, ...

State Government of Georgia

Bid Due: 6/16/2026

* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.