4520--Lyons VAMC Water Heater Replacement Brand Specific to ensure hookups are compatible no additional piping being considered

Location: New Jersey
Posted: May 4, 2026
Due: May 11, 2026
Agency: VETERANS AFFAIRS, DEPARTMENT OF
Type of Government: Federal
Category:
  • 45 - Plumbing, Heating, and Sanitation Equipment
Solicitation No: 36C24226Q0588
Publication URL: To access bid details, please log in.
Follow
4520--Lyons VAMC Water Heater Replacement Brand Specific to ensure hookups are compatible no additional piping being considered
Active
Contract Opportunity
Notice ID
36C24226Q0588
Related Notice
Department/Ind. Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-tier
VETERANS AFFAIRS, DEPARTMENT OF
Office
242-NETWORK CONTRACT OFFICE 02 (36C242)
Looking for contract opportunity help?

APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.

APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.

The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).

General Information
  • Contract Opportunity Type: Sources Sought (Original)
  • Original Published Date: May 04, 2026 12:54 pm EDT
  • Original Response Date: May 11, 2026 04:00 pm EDT
  • Inactive Policy: Manual
  • Original Inactive Date: Aug 18, 2026
  • Initiative:
    • None
Classification
  • Original Set Aside:
  • Product Service Code: 4520 - SPACE AND WATER HEATING EQUIPMENT
  • NAICS Code:
    • 333414 - Heating Equipment (except Warm Air Furnaces) Manufacturing
  • Place of Performance:
    Lyons VAMC 151 Knollcroft Road Lyons , NJ 07939-5001
    USA
Description
Qty 1 Patterson-Kelley Model PK-08D Semi-Instantaneous Water Heater rated to
provide 27 GPM of Domestic Hot Water from 40-120F when supplied with 25 psig Inlet
Steam and 5 psig in the Coil @ 1122#/hr. Heater to be furnished with the following
features and controls to meet the specified demand:
- Solid Copper Nickel Pressure Vessel rated for 150 psi ASME working
pressure.
- Factory Insulation.
- 90/10 Double Wall Copper Nickel Tube Bundle rated for 150 psi ASME
working pressure and 210F test pressure.
- All bronze circulator pump, 1/6HP, NYC Trim Package, 115v/1ph/60Hz,
with isolation valves, ball and check valves, and venturi tees.
- 1 ½ Spence Pilot Operated, Self-Contained Steam Control Valve.
- 1 ½ Wye Strainer.
- ¾ ASME Temperature & Pressure Relief Valve at 150 psi.
- ¾ ASME Pressure Only Relief Valve (Shipped Loose).
- 1 ½ Float & Thermostatic Condensate Steam Trap & Strainer (Shipped
Loose).
- ½ Auxiliary Drip Tap (Shipped Loose).
- ¾ Drain Valve Factory Installed.
- Double Solenoid High Temperature Limit System with pre-wired control
box.
- Vertical Stand suitable for removal of heating section without
disconnection of domestic water lines.
- ¾ Vacuum Breaker Factory Installed.
- 3 ½ Dial Thermometer & Bundle Steam Pressure Gauge.
- Operation & Maintenance Manuals in electronic form.
- Factory Authorized Start-Up & Training
Tags: 276458 (WH-2)

Qty 1 Patterson-Kelley Model PK-10D Semi-Instantaneous Water Heater rated to
provide 65 GPM of Domestic Hot Water from 40-140F when supplied with 40 psig Inlet
Steam and 25 psig in the Coil @ 3469#/hr. Heater to be furnished with the following
features and controls to meet the specified demand:
- Solid Copper Nickel Pressure Vessel rated for 150 psi ASME working
pressure.
- Factory Insulation.
- 90/10 Double Wall Copper Nickel Tube Bundle rated for 150 psi ASME
working pressure and 210F test pressure.
- All bronze circulator pump, 1/6HP, NYC Trim Package, 115v/1ph/60Hz,
with isolation valves, ball and check valves, and venturi tees.
- 2 ½ Spence Pilot Operated, Self-Contained Steam Control Valve.
- 2 ½ Wye Strainer.
- 1 ASME Temperature & Pressure Relief Valve at 150 psi.
- 1 ½ ASME Pressure Only Relief Valve (Shipped Loose).
- 1 ½ Float & Thermostatic Condensate Steam Trap & Strainer (Shipped
Loose).
- ½ Auxiliary Drip Tap (Shipped Loose).
- ¾ Drain Valve Factory Installed.
- Double Solenoid High Temperature Limit System with pre-wired control
box.
- Vertical Stand suitable for removal of heating section without
disconnection of domestic water lines.
- ¾ Vacuum Breaker Factory Installed.
- 3 ½ Dial Thermometer & Bundle Steam Pressure Gauge
.

Attachments/Links
Contact Information
Contracting Office Address
  • 113 HOLLAND AVE
  • ALBANY , NY 12208
  • USA
Primary Point of Contact
Secondary Point of Contact


History
  • May 04, 2026 12:54 pm EDTSources Sought (Original)

Related Document

May 19, 2026[Solicitation (Original)] 4520--Lyons VAMC Water Heater Replacement Brand Specific to ensure hookups are compatible no additional piping being considered
May 26, 2026[Solicitation (Updated)] 4520--Lyons VAMC Water Heater Replacement Brand Specific to ensure hookups are compatible no additional piping being considered
Daily notification on new contract opportunities

With GovernmentContracts, you can:

  • Find more opportunities and win more business
  • Receive daily alerts for all new bid opportunities
  • Get contract opportunities matched to your business
ONE WEEK FREE TRIAL

See also

opportunity date posted date due commodity type download Maintenance & Testing of Electrical

Hudson County

Bid Due: 6/04/2026

Project: Architectural & Engineering Services Qualified Pool Ref. #: RFQ 26-27 Q-1757 Type:

Ocean County College

Bid Due: 6/11/2026

F-110-2026 Click here to download the project's Specification, Clarifications, Addenda, ect. SUPPLY NATURAL

Monmouth County

Bid Due: 6/10/2026

Upcoming Purchases & Bid Solicitations Upcoming Purchases and Bid Solicitations Request For Qualifications

Delaware River Port Authority

Bid Due: 6/09/2026

* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.