4520--Lyons VAMC Water Heater Replacement Brand Specific to ensure hookups are compatible no additional piping being considered
| Location: |
New Jersey |
| Posted: |
May 4, 2026 |
| Due: |
May 11, 2026 |
| Agency: |
VETERANS AFFAIRS, DEPARTMENT OF |
| Type of Government: |
Federal |
| Category: |
- 45 - Plumbing, Heating, and Sanitation Equipment
|
| Solicitation No: |
36C24226Q0588 |
| Publication URL: |
To access bid details, please log in. |
4520--Lyons VAMC Water Heater Replacement Brand Specific to ensure hookups are compatible no additional piping being considered
Active
Contract Opportunity
Department/Ind. Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-tier
VETERANS AFFAIRS, DEPARTMENT OF
Office
242-NETWORK CONTRACT OFFICE 02 (36C242)
Looking for contract opportunity help?
General Information
-
Contract Opportunity Type: Sources Sought (Original)
-
Original Published Date: May 04, 2026 12:54 pm EDT
-
Original Response Date: May 11, 2026 04:00 pm EDT
-
Inactive Policy: Manual
-
Original Inactive Date:
Aug 18, 2026
-
Initiative:
Classification
Description
Qty 1 Patterson-Kelley Model PK-08D Semi-Instantaneous Water Heater rated to
provide 27 GPM of Domestic Hot Water from 40-120F when supplied with 25 psig Inlet
Steam and 5 psig in the Coil @ 1122#/hr. Heater to be furnished with the following
features and controls to meet the specified demand:
- Solid Copper Nickel Pressure Vessel rated for 150 psi ASME working
pressure.
- Factory Insulation.
- 90/10 Double Wall Copper Nickel Tube Bundle rated for 150 psi ASME
working pressure and 210F test pressure.
- All bronze circulator pump, 1/6HP, NYC Trim Package, 115v/1ph/60Hz,
with isolation valves, ball and check valves, and venturi tees.
- 1 ½ Spence Pilot Operated, Self-Contained Steam Control Valve.
- 1 ½ Wye Strainer.
- ¾ ASME Temperature & Pressure Relief Valve at 150 psi.
- ¾ ASME Pressure Only Relief Valve (Shipped Loose).
- 1 ½ Float & Thermostatic Condensate Steam Trap & Strainer (Shipped
Loose).
- ½ Auxiliary Drip Tap (Shipped Loose).
- ¾ Drain Valve Factory Installed.
- Double Solenoid High Temperature Limit System with pre-wired control
box.
- Vertical Stand suitable for removal of heating section without
disconnection of domestic water lines.
- ¾ Vacuum Breaker Factory Installed.
- 3 ½ Dial Thermometer & Bundle Steam Pressure Gauge.
- Operation & Maintenance Manuals in electronic form.
- Factory Authorized Start-Up & Training
Tags: 276458 (WH-2)
Qty 1 Patterson-Kelley Model PK-10D Semi-Instantaneous Water Heater rated to
provide 65 GPM of Domestic Hot Water from 40-140F when supplied with 40 psig Inlet
Steam and 25 psig in the Coil @ 3469#/hr. Heater to be furnished with the following
features and controls to meet the specified demand:
- Solid Copper Nickel Pressure Vessel rated for 150 psi ASME working
pressure.
- Factory Insulation.
- 90/10 Double Wall Copper Nickel Tube Bundle rated for 150 psi ASME
working pressure and 210F test pressure.
- All bronze circulator pump, 1/6HP, NYC Trim Package, 115v/1ph/60Hz,
with isolation valves, ball and check valves, and venturi tees.
- 2 ½ Spence Pilot Operated, Self-Contained Steam Control Valve.
- 2 ½ Wye Strainer.
- 1 ASME Temperature & Pressure Relief Valve at 150 psi.
- 1 ½ ASME Pressure Only Relief Valve (Shipped Loose).
- 1 ½ Float & Thermostatic Condensate Steam Trap & Strainer (Shipped
Loose).
- ½ Auxiliary Drip Tap (Shipped Loose).
- ¾ Drain Valve Factory Installed.
- Double Solenoid High Temperature Limit System with pre-wired control
box.
- Vertical Stand suitable for removal of heating section without
disconnection of domestic water lines.
- ¾ Vacuum Breaker Factory Installed.
- 3 ½ Dial Thermometer & Bundle Steam Pressure Gauge
.
Attachments/Links
Contact Information
Contracting Office Address
-
113 HOLLAND AVE
-
ALBANY , NY 12208
-
USA
Secondary Point of Contact
History
-
May 04, 2026 12:54 pm EDTSources Sought (Original)
Daily notification on new contract opportunities
With GovernmentContracts, you can:
- Find more opportunities and win more business
- Receive daily alerts for all new bid opportunities
- Get contract opportunities matched to your business
ONE WEEK FREE TRIAL
See also
...Bid Number: RDE-26-2 Bid Title: 2026 Road Paving Program Category: Bid Postings Status: ...
Township of Jefferson
Bid Due: 6/16/2026
...Bid Number: RDE-26-1 Bid Title: Weldon Road Improvements Phase 2 Bid Category: Bid ...
Township of Jefferson
Bid Due: 6/10/2026
..., particularly for vulnerable road users such as pedestrians. The supplemental planning activities... ...
City of Camden
Bid Due: 6/04/2026
...and discharge piping, valves and fittings, the installation of a new state-of-the-art iron ...
Beachwood borough
Bid Due: 6/23/2026
* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.