| Project Title: | SOUTH CAMPUS BUILDINGS S201 AND S203 ELEVATOR UPGRADES |
| Description: | The work shall consist of modernization of two (2) existing hydraulic 3-stop elevators – one installed in Building S201, and one installed in Building S203. Upgrades shall mean that the elevator and its components shall be brought into compliance with the 2019 Edition of the North Carolina Elevator and Escalator Code, as well as other applicable Codes. The General Contractor shall be the Prime Contractor for this single-prime contract. The Prime Contractor shall hire Owner approved sub-contractors to provide all necessary support work to provide a turnkey installation, without additional funding by the Owner. |
| Opening Date: | 5/5/2026 3:00 PM |
| Posted Date: | 4/23/2026 |
| Status: | Open |
| Department: | ROWAN-CABARRUS COMMUNITY COLLEGE |
|
Solicitation Number
*
121-042326JVC
|
Department
ROWAN-CABARRUS COMMUNITY COLLEGE
|
Status Reason
Open
|
|
|
Opening Date
2026-05-05T15:00:00.0000000
|
Posted Date
*
2026-04-23T12:50:05.0000000Z
|
Primary Commodity Code
Building and facility maintenance and repair services
|
|
|
Mandatory Conference/Site Visit
—
—
|
Special Instructions
Electronic Submissions Only
|
Solicitation Type
*
Select RFP IFB RFI
|
|
|
Owner
Ronda Holland
|
|||
|
Description
The work shall consist of modernization of two (2) existing hydraulic 3-stop elevators – one installed in Building S201, and one installed in Building S203. Upgrades shall mean that the elevator and its components shall be brought into compliance with the 2019 Edition of the North Carolina Elevator and Escalator Code, as well as other applicable Codes. The General Contractor shall be the Prime Contractor for this single-prime contract. The Prime Contractor shall hire Owner approved sub-contractors to provide all necessary support work to provide a turnkey installation, without additional funding by the Owner.
|
|||
IFB # 121-0042326JVC
SOUTH CAMPUS BUILDINGS S201 AND S203 ELEVATOR UPGRADES
ROWAN-CABARRUS COMMUNITY COLLEGE
1531 Trinity Church Road
Concord, NC 28027
INVITATION TO BID
NOTICE TO BID
Sealed bids for construction of the Rowan-Cabarrus Community College, South Campus Buildings S201 and
S203 Elevator Upgrades Project will be received via email (PDF format only) at collegeenvironment@rccc.edu
until, but no later than 3:00 pm, local prevailing time, May 5, 2026, and then publicly opened and read
immediately thereafter via ZOOM. Bidders are encouraged to view the bid opening in real time via a ZOOM link
that follows.
The bid name and IFB # 121-042326JVC shall be referenced in the subject line of the email.
Bidders shall be General Contractors, licensed in North Carolina, with elevator modernization experience and
Owner approved sub-contractors as required. Bidders will receive an email receipt notification that their
bids have been received.
HUB certified contractors are encouraged to bid on this project.
Bids received after the announced time and date for submittal will be rejected. Bidders are responsible for
ensuring their bid is received before the deadline indicated. All firms must be registered with the North Carolina
Electronic Vendor Portal (eVP and Purchase Orders) prior to presenting a proposal. Failure to register may result
in disqualification. North Carolina Electronic Vendor Portal may be found at https://evp.nc.gov/
Contractual Requirement: All bidders must agree to execute a contract that incorporates and adheres to the
State of North Carolina's General Terms and Conditions. These terms are available for review
at: https://www.doa.nc.gov/north-carolina-general-terms-and-conditions-5-2025/open.
The work shall consist of modernization of two (2) existing hydraulic 3-stop elevators - one installed in Building
S201, and one installed in Building S203. Upgrades shall mean that the elevator and its components shall be
brought into compliance with the 2019 Edition of the North Carolina Elevator and Escalator Code, as well as
other applicable Codes. The General Contractor shall be the Prime Contractor for this single-prime contract.
The Prime Contractor shall hire Owner approved sub-contractors to provide all necessary support work to
provide a turnkey installation, without additional funding by the Owner.
Beginning on April 23, 2026, Bidders may obtain electronic Bidding Documents by contacting the Engineer at
baengineers@aol.com
ZOOM BID OPENING LINK
Join Zoom Meeting
https://rccc-edu.zoom.us/j/91382312799
Meeting ID: 913 8231 2799
One tap mobile
+13126266799,,91382312799# US (Chicago)
+16465588656,,91382312799# US (New York)
Join instructions
https://rccc-
edu.zoom.us/meetings/91382312799/invitations?signature=1FCDF8BErPmEQ3_0PsmG9pmfRBMW9Gx
YaDTxdXB05-g
END OF NOTICE TO BID
Rowan-
0
340 20
GENERAL NOTES:
3 2 0 N 4 0
Bullard Associates
0
6
0
THE FOLLOWING NOTES ARE TO PROVIDE ADDITIONAL CLARIFICATION AND REITERATION OF THE SPECIFICATIONS: 3 0 Engineers
Cabarrus
0 1 Water Thrush Road
SCHEDULE OF WORK: 8
8
2 0 Lake Wylie, SC 29710
W E
Telephone: 803-701-7151
THE BUILDINGS WILL BE OCCUPIED DURING PART OF THE CONSTRUCTION PERIOD. THE ELEVATORS CANNOT BE SHUT-DOWN UNTIL JULY 21, 2026, WHEN 0 1 Mobile: 704-604-9609
6 0
2 0 baengineers@aol.com
THE COLLEGE HAS A SUMMER BREAK. DURING THE OCCUPIED TIME, WORK SHALL BE SCHEDULED WITH THE PROJECT MANAGER SO THAT NORMAL
NCBELS Licence #F-1515
OPERATION OF THE FACILITIES IS NOT DISTURBED. THIS MAY REQUIRED NIGHT, WEEKEND OR HOLIDAY WORK. ALTHOUGH THE ELEVATOR WORK 0 1
4 2
2 0
CANNOT BE DONE UNTIL THE SHUT-DOWN OCCURS, THERE IS OTHER WORK THAT CAN BE DONE. THE INSTALLATION OF THE MINI-SPLIT HVAC SYSTEMS Rowan-
340 0 20
320 40
FOR THE ELEVATOR MACHINE ROOMS CAN BE DONE DURING THE OCCUPIED STAGES OF THE PROJECT. 0 2 S 4 1 300 60
C O M M U N I T Y C O L L E G E 2 0 Cabarrus 280 80
002 061 062 001
081 042 021
CONTRACT REQUIREMENTS:
COM MU N I TY COL LEGE
022
002 081 061
041
1. CONTRACTOR SHALL MODIFY, RETROFIT OR REPLACE EXISTING LIGHTING FIXTURES, AND/OR LAMPS AS DESCRIBED ON THE DRAWINGS. HYDRAULIC ELEVATOR
MODERNIZATION
2. SUBMIT COMPLETE DATA ON ALL MATERIALS BEING FURNISHED, EXPEDITE DELIVERY OF MATERIALS.
BUILDINGS S201 + S203
HYDRAULIC ELEVATOR
3. CONTRACTOR SHALL SCHEDULE HIS WORK WITH THE OWNER -- NORMAL OPERATION OF THE BUILDING CANNOT BE INTERRUPTED.
SOUTH CAMPUS
4. CONTRACTOR SHALL TAKE CARE NOT TO DAMAGE CEILING TILE OR BUILDING SURFACES. ANY DAMAGE TO THE FACILITY SHALL BE
MODERNIZATION
REPAIRED BY THE CONTRACTOR AT HIS EXPENSE. DAMAGED CEILING TILES SHALL BE REPLACED -- SOME TILES WILL NEED TO REPLACED WHERE
RECESSED DOWNLIGHTS ARE BEING REPLACED: TILE REQUIRED = ARMSTRONG 895 (2' by 4') or ARMSTRONG 896 (2' by 2') (VERIFY WITH THE OWNER
PRIOR TO ORDERING).
SOUTH CAMPUS
BUILDINGS S201 + S203
1531 Trinity Church Road
5. See PROJECT MANUAL FOR ADDITIONAL REQUIREMENTS.
Concord, NC 28027
DIVISION OF WORK:
SOUTH CAMPUS
H CARO
GENERAL CONTRACTOR (PRIME CONTRACTOR): R T L I
O N
N F
ESSIO
A
O N
R A
1. GENERAL CONTRACTOR SHALL ACT AS PROJECT EXPEDITER. 1531 Trinity Church Road P SEAL L
3934
E R D
Concord, NC 28027 J . N GINE E A R
C L
2. INCLUDE ALL WORK SHOWN IN PRIME CONTRACT. 0 L
NN0R B U
03/26/2026
3. PROVIDE AND INCLUDE IN THE PRIME CONTRACT ALL NECESSARY QUALIFIED SUB-CONTRACTORS
REQUIRED FOR WORK THAT THE PRIME CONTRACTOR IS NOT QUALIFIED TO PERFORM.
4. See PROJECT MANUAL FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
SUB-CONTRACTORS AS REQUIRED:
1. PRIME CONTRACTOR SHALL PROVIDE ANY AND ALL SUB-CONTRACTORS NECESSARY TO COMPLETE THE PROJECT. ALL CONTRACTORS SHALL BE
LICENSED IN THE STATE OF NORTH CAROLINA AND HAVE HAD A MINIMUM OF 5 YEARS EXPERIENCE WITH WORK OF THIS NATURE. LISTED BELOW
ARE ''OWNER PREFERRED'' SUB-CONTRACTORS. THESE ARE CONTRACTORS THAT ARE DOING WORK, OR HAVE DONE WORK FOR THE COLLEGE
BEFORE. THE PRIME CONTRACTOR IS NOT REQUIRED TO USE THESE CONTRACTORS, AND MAY SUBMIT OTHER QUALIFIED FIRMS FOR CON-
SIDERATION -- COMPLETE REFERENCE AND EXPERIENCE DATA MUST BE SUBMITTED TWO WEEKS PRIOR TO THE BID OPENING. AN ADDENDUM
WILL BE ISSUED SEVEN (7) DAYS PRIOR TO BIDDING STATING WHETHER THE PROPOSED SUB-CONTRACTORS ARE ACCEPTABLE OR NOT.
THE ''OWNER PREFERRED'' CONTRACTORS ARE:
ELEVATOR: CHARTER ELEVATOR
Keith Desmond
Keith.Desmond@charterelevator.com
Office: 877-632-4278
Mobile: 919-441-3416
SUPERIOR MECHANICAL SYSTEMS OF CHARLOTTE, INC.
HVAC:
bwyke@superiorsinc.com
Phone: 704-309-9212
ELECTRICAL: MULTI-ELECTRICAL SERVICES, INC.
Bob McVay
mcvayb@multielectrical.com
Office: 704-932-4650
Mobile: 704-791-5213
DATA: MODERN EDGE TECHNOLOGY SOLUTIONS, INC.
Jason White
jason@modernedgetechnology.com
Office: 336-308-8020x1001
Mobile: 336-460-4355
FIRE ALARM: KNC TECHNOLOGIES
Nick Long
nickl@knctech.us
Office: 336-760-5512
Mobile: 336-575-5767
OWNER'S PROJECT MANAGER: OWNER'S FACILITIES SUPERVISOR:
PARTIAL SITE/LOCATION PLAN
1
JOHN COLE RON EURY
Office: 704-216-7222 Office: 704-216-7610 1'' = 600'-0'' REVISIONS
Mobile: 704-640-1852 Mobile: 980-622-4233
NO. DATE DESCRIPTION
john.cole@rccc.edu ron.eury@rccc.edu
SCHEDULING OF WORK AND BUILDING ACCESS SHALL BE COORDINATED WITH THE PROJECT MANAGER.
COVER SHEET
INDEX OF DRAWINGS
EL000 COVER SHEET
EL100 BUILDING S201 PLAN - EXISTING CONDITIONS/DEMOLITION SHEET TITLE
EL101 BUILDING S201 PLAN - EXISTING CONDITIONS/DEMOLITION
EL102 BUILDING S203 PLAN - EXISTING CONDITIONS/DEMOLITION
26010.00
EL200 BUILDING S201 PLAN - NEW WORK
EL201 BUILDING S203 PLAN - NEW WORK PROJECT NUMBER
EL300 HVAC SPLIT-SYSTEM CONNECTIONS/DETAILS EL000
1Program Files\AutoCAD R14\26010.00 - HYDRAULIC ELEVATOR MODERNIZATION - S201 + S203/EL000 - Cover Sheet.dwg EL400 ELEVATOR BASE BID + ALTERNATES BUILDING S201 03.26.2026
Thursday, March 26, 2026 4:54 am
EL401 ELEVATOR BASE BID + ALTERNATES BUILDING S203
EL500 MISCELLANEOUS DETAILS
RELEASE DATE
SHEET OF
302S
GNIDLIUB
B
U
I
L
D
I
N
G
S
2
0
1
| STAIR 190 |
| LE | ||
|---|---|---|
| LC | ||
| ELEV. MACH. 184 |
| REMOVE EXISTING ELEVATOR DISCONNECT | |||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| EXISTING CAR LIGHT SWITCH TO REMAIN | |||||||||||||||||||||||||||||
| EXISTING LIGHT SWITCH See NOTE #4 EXISTING CAR COMM BOX See NOTE #5 | |||||||||||||||||||||||||||||
| REMOVE THERMOSTAT/PATCH WALL | |||||||||||||||||||||||||||||
| REMOVE RECEPTACLE | |||||||||||||||||||||||||||||
| EXISTING TROUGH TO REMAIN | |||||||||||||||||||||||||||||
| LE | ||
| LC |
See DETAIL 5/EL100
See DETAIL 6/EL100
EXISTING CONDUIT
NEW 3/4''C
ABOVE CEILING
PULL BOX J
EXISTING PANEL ''1P'' (208GrY120V)
EXISTING PANEL ''1L'' (480GrY277V)
See DETAIL 2/EL100
See DETAIL 4/EL100
REMOVE EXISTING RECEPTACLE
REMOVE EXISTING LIGHTING FIXTURE
CONDUIT EXTENDS TO EXISTING CONDUIT
EXISTNG PANEL ''1P'',
RE-ROUTE CONDUIT TO
EXISTING PANEL ''EMP''
CONDUIT TURNS UP
C
T
LE
LC
See ELEVATION FOR DETAILS
SUBMERSIBLE POWER UNIT
(REMOVE) ELEVATOR POWER DISCONNECT
COMM PULL BOX
HYDRAULIC MUFFLER
(REMOVE)
HYDRAULIC CONTROLLER
CAR LIGHTS DISCONNECT 3
(REMOVE)
EL100
THERMOSTAT
TROUGH
C
T
LE
LC
EXISTING SMOKE DETECTOR TO REMAIN
RELOCATE TO NEW CEILING
S REMOVE EXISTING
SMOKE DETECTOR
(OUT OF SERVICE)
S
R
R
R
PULL BOX J
FIRESTOP -- See DETAIL 1/EL400
EXISTING FIRE ALARM
CONTROL RELAYS EXISTING PANEL ''1P'' (208GrY120V)
TO REMAIN EXISTING PANEL ''1L'' (480GrY277V)
See DETAIL 2/EL100
See DETAIL 4/EL100
EXISTING PANEL ''EML'' (480GrY277V) [EMERGENCY]
EXISTING 9KVA TRANSFORMER [EMERGENCY]
EXISTING PANEL ''EMP'' (208GrY120V) [EMERGENCY]
REMOVE EXISTING ELEVATOR DISCONNECT
EXISTING ''SWBD'' (480GrY277V)
EXISTING CAR LIGHT SWITCH TO REMAIN RUN 3/4''C TO EXISTING CONDUIT AT ELEVATOR PIT -- See 5/EL100
REMOVE THERMOSTAT/PATCH WALL
REMOVE RECEPTACLE
EXISTING LIGHT
EXISTING TROUGH TO REMAIN
SWITCH
See NOTE #4
EXISTING CAR
COMM BOX
See NOTE #5
S
DEMOLITION NOTES:
1. See SHEET EL000 AND THE PROJECT MANUAL FOR ADDITONAL INFORMATION ON THE ELEVATOR SYSTEM DEMOLITION.
Bullard Associates
2. REMOVE DUCT PENETRATIONS, SEAL AND PAINT WALL. PATCHED AREA SHALL HAVE SAME FIRE RATING AS WALL = 1-HOUR.
Engineers
3. CUT DUCT AS REQUIRED -- BLANK OFF EXISTING DUCT. SYSTEM SHALL BE RE-BALANCED, IF NECESSARY.
1 Water Thrush Road
Lake Wylie, SC 29710
4. REMOVE EXISTING SWITCH, PLATE AND CIRCUIT. NEW SWITCH, PLATE & CIRCUIT WILL BE PROVIDE UNDER NEW WORK -- See SHEET EL102.
Telephone: 803-701-7151
5. EXISTING BOX AND CONDUIT FOR COMMUNICATIONS SHALL REMAIN. EXISTING CONDUIT HAS TELEPHONE WIRING (TO REMAIN). NEW CAT6 DATA DROP WILL BE Mobile: 704-604-9609
baengineers@aol.com
PROVIDED UNDER NEW WORK -- See SHEET EL102. REMOVE EXISTING REMOVE EXISTING SWITCH AND
NCBELS Licence #F-1515
FLUORESCENT TROFFER PLATE -- NEW SWITCH AND PLATE
6. REMOVE EXISTING THERMOSTAT AND WIRING -- PATCH AND PAINT WALL -- 1-HOUR FIRE RATING. TO BE PROVIDED UNDER NEW WORK.
Rowan-
See SHEET EL101. 320 340 0 20 40
REMOVE EXISTING 300 60
Cabarrus 280 80
CEILING GRID & TILES 062 001
042 021
COM MU N I TY COL LEGE
022
002 081 061
041
REMOVE EXISTING HYDRAULIC ELEVATOR
DISCONNECT & PULL OUT
FLUORESCENT TROFFER
MODERNIZATION
EXISTING LIGHTING CIRCUIT
ELEV.
ELEV. (NEW CIRCUIT TO BE BUILDINGS S201 + S203 191
PROVIDED UNDER NEW WORK)
MACH.
See SHEET EL101.
184 SOUTH CAMPUS
SOUTH CAMPUS
1531 Trinity Church Road
Concord, NC 28027
STAIR
190
ELEV.
MACH.
H CARO
184 R T L I
O N
STORAGE PLAN: ELEVATOR MACHINE ROOM LIGHTING - DEMOLITION N F ESSIO A
O N
101A 5 R A
SEAL
P L
3934
1/2'' = 1' - 0'' E R D
J . N GINE E A R
C L
0 L
NN0R B U
ELEC. 03/26/2026
185
CORRIDOR
100
PLAN: ELEVATOR MACHINE ROOM FIRE ALARM - DEMOLITION
2
WOMEN
1/2'' = 1' - 0''
MEN
112
113
ELEV.
MACH.
184
JAN.
114
MECHANICAL
180
CORRIDOR
114A
PARTIAL PLAN: BUILDING S201 - DEMOLITION
1
1/4'' = 1' - 0''
ELEVATION: MACHINE ROOM [184] WALL - DEMOLITION
ELEV.
3
191
See DETAIL 2/EL100
3/4'' = 1' - 0''
REMOVE EXISTING LIGHT REPLACE EXISTING OIL SHUTOFF VALVE
REVISIONS
REPLACE 'GFIC' RECEPTACLE See SPECIFICATIONS
NO. DATE DESCRIPTION
ELEV.
NEW JACK PACKING
MACH.
PLAN: ELEVATOR PIT [191] - DEMOLITION
184 5
1/2'' = 1' - 0''
BUILDING S201 PLAN -
CLEAN & REPAINT PIT STEEL & FLOOR EXISTING CONDITIONS/
REPLACE PIT CAN DEMOLITION
ELEVATOR PIT: BUILDING S201
SHEET TITLE
6
PLAN: ELEVATOR MACHINE ROOM [184] - DEMOLITION
DEMOLITION
Not To Scale 4
26010.00
1/2'' = 1' - 0''
PROJECT NUMBER
BUILDING S201 EL100
1Program Files\AutoCAD R14\26010.00 - HYDRAULIC ELEVATOR MODERNIZATION - S201 + S203/EL100 - S201 Plan - Existing Conditions - Demolition.dwg 03.26.2026
Thursday, March 26, 2026 4:55 am
RELEASE DATE
SHEET OF
| 184 |
|---|
See NOTE #2
EXISTING DUCT TO REMAIN
See NOTE #3
EXISTING DUCT TO REMAIN
TCUD
GNITSIXE
EVOMER
REMOVE EXISTING
TERMINAL BOX
REMOVE EXISTING
DUCT
REMOVE EXISTING
DIFFUSER
See NOTE #2
4#
ETON
eeS
CORRIDOR
100 Bullard Associates
Engineers
1 Water Thrush Road
Lake Wylie, SC 29710
Telephone: 803-701-7151
Mobile: 704-604-9609
CLEAN AND REPAINT CMU WALL baengineers@aol.com
USE SAME TYPE PAINT NCBELS Licence #F-1515
REMOVE EXISTING GWB FROM EXISTING CONCRETE Rowan-
340 0 20
WALLS. CLEAN AND PATCH EXISTING WALLS, INSTALL
320 40
300 60
1/2'' MOISTURE & MOLD RESISTANT ''PURPLE'' BOARD Cabarrus 280 80
MOUNTED ON SUITABLE 7/8'' FURRING CHANNELS. MEN 062 001
MACHINE PAINT WITH LOW-VOC PAINT -- OWNER TO SELECT COLOR. 113
COM MU N I TY COL LEGE
042
022
002 081 061
041
021
ROOM
184 HYDRAULIC ELEVATOR
CLEAN AND REPAINT CMU WALL
USE SAME TYPE PAINT
MODERNIZATION
BUILDINGS S201 + S203
CLEAN AND PREP EXISTING CONCRETE FLOOR
PAINT FLOOR WITH ''SLIP-RESISTANT'' LOW-VOC
ELEVATOR SOUTH CAMPUS
PAINT -- OWNER TO SELECT COLOR.
MACHINE ROOM
184
4 SOUTH CAMPUS
1531 Trinity Church Road
NOTE: JANITOR
Concord, NC 28027
WORK TO BE DONE
114
AFTER EXISTING ELEVATOR
EQUIPMENT HAS BEEN REMOVED
AND BEFORE NEW ELEVATOR T H CARO L
R I
O N
EQUIPMENT HAS BEEN INSTALLED. N F ESSIO A
CORRIDOR O N
R A
SEAL
P L
114A 3934
E R D
J . N GINE E A R
C L
0 L
NN0R B U
PLAN: ELEVATOR MACHINE ROOM PLAN: ELEVATOR MACHINE ROOM - HVAC - DEMOLITION
2 1 03/26/2026
1/2'' = 1' - 0'' WALL/FLOOR REFINISH 1/2'' = 1' - 0''
NOTES:
1. See SHEET EL000 AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. REMOVE EXISTING DUCTWORK THROUGH EXISTING RATED WALLS, PATCH WALL TO MATCH FIRE RATING AND PAINT AS DIRECTED.
3. CUT OFF AND REMOVE EXISTING DUCTWORK, CAP REMAINING DUCTWORK AIRTIGHT.
4. REMOVE EXISTING THERMOSTAT & BOX -- PATCH WALL AND PAINT AS DIRECTED.
REVISIONS
NO. DATE DESCRIPTION
4 04/14/2026 ADDED ROOM FINISH DETAILS
FOR MACHINE ROOM [184]
BUILDING S201 PLAN -
EXISTING CONDITIONS/
DEMOLITION
SHEET TITLE
26010.00
PROJECT NUMBER
BUILDING S201 EL101
1Program Files\AutoCAD R14\26010.00 - HYDRAULIC ELEVATOR MODERNIZATION - S201 + S203/EL101-R4- S201 Plan - Existing Conditions - Demolition.dwg 03.26.2026
Tuesday, April 14, 2026 6:10 am
RELEASE DATE
SHEET OF
| ELEVATOR 191 ELEV. MACH. |
| S H ELEV. 191 H |
| ELEVATOR 191 |
| T | |||
CORRIDOR CORRIDOR
CORRIDOR
101 101
101
Bullard Associates
S H
Engineers
1 Water Thrush Road
SS HH
Lake Wylie, SC 29710
ELEVATOR ELEV. Telephone: 803-701-7151
191 Mobile: 704-604-9609
191 STAIR S STAIR
baengineers@aol.com
190 190
NCBELS Licence #F-1515
Rowan-
340 0 20
320 40
ELEV. ELEV. H 300 60
MACH. Cabarrus 280 80
S
191 181 062 001
042 021
COM MU N I TY COL LEGE
022
002 081 061
041
ELEV.
MACH.
HYDRAULIC ELEVATOR
181
MODERNIZATION
STAIR
BUILDINGS S201 + S203
190
STORAGE
103 STORAGE
SOUTH CAMPUS
103
SOUTH CAMPUS
1531 Trinity Church Road
ELEV.
PARTIAL PLAN: BUILDING S203 - CEILING PARTIAL PLAN: BUILDING S203 - FIRE ALARM
Concord, NC 28027
MACH. 2 1
181 1/4'' = 1' - 0'' DEMOLITION 1/4'' = 1' - 0'' DEMOLITION
H CARO
T L
R I
O N
N F ESSIO A
O N
R A
SEAL
P L
3934
E R D
J . N GINE E A R
C L
0 L
NN0R B U
03/26/2026
CORRIDOR
101
STORAGE
REMOVE DIFFUSERS
103
AND DUCTWORK
ELEVATOR
191 STAIRS
190
ELEV.
MACH.
181
T
PARTIAL PLAN: BUILDING S203 - EQUIPMENT - DEMOLITION
3
1/2'' = 1' - 0''
STORAGE
103
PARTIAL PLAN: BUILDING S203 - HVAC
5
1/4'' = 1' - 0'' DEMOLITION
REVISIONS
NO. DATE DESCRIPTION
BUILDING S203 PLAN -
EXISTING CONDITIONS/
DEMOLITION
SHEET TITLE
26010.00
PROJECT NUMBER
EL102
1Program Files\AutoCAD R14\26010.00 - HYDRAULIC ELEVATOR MODERNIZATION - S201 + S203/EL102 - S203 Plan - Existing Conditions - Demolition.dwg 03.26.2026
Thursday, March 26, 2026 6:28 am
RELEASE DATE
SHEET OF
2#
ETON
eeS
2#
ETON
eeS
EXISTING DUCTS TO REMAIN
BLANK OFF DUCT WHERE DUCT WAS REMOVED
4#
ETON
eeS
SREPMAD
ERIF
EVOMER
3#
ETON
eeS
-
LLAW
HCTAP
See NOTE #6
REMOVE EXISTING
GWB CEILING,
INCLUDING ALL
SUPPORTS, ETC.
See NOTE #5
See NOTE #7
EXISTING RECEPTACLE TO REMAIN
See NOTE #8
EXISTING BOXES & DEVICES TO REMAIN
See NOTE #9
01#
EON
eeS
DEVICES TO REMAIN
See NOTE #11
See NOTE #12
SPRINKLER HEAT TO BE
MODIFIED BY OWNER
See NOTE #12
DEMOLITION NOTES:
1. See SHEET EL000 AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. EXISTING HVAC DEVICES TO REMAIN.
3. REMOVE FIRE DAMPERS AND PATCH 1-HOUR RATED WALL.
4. See SECTION 5/EL500 FOR ADDITIONAL INFORMATION.
5. REMOVE EXISTING HVAC AIR DEVICES.
6. EXISTING SPRINKLER HEAT TO BE MODIFIED BY THE OWNER.
7. REMOVE EXISTING SUBMERSIBLE POWER UNIT & HYDRAULIC CONTROLLER.
8. REMOVE EXISTING ELEVATOR DISCONNECT SWITCH.
9. EXISTING DISCONNECT FOR CAR LIGHTS TO REMAIN.
10. REMOVE WIRING BETWEEN DISCONNECT AND CONTROLLER -- MODIFY CONDUIT.
11. EXISTING RECEPTACLES IN PIT SHALL REMAIN.
12. CEILING IN THIS ROOM TO BE REMOVED & REPLACED. RELOCATED FIRE ALARM
DEVICES TO NEW CEILING. EXISTING CONDUIT FEEDING THESE DEVICES IS
CURRENTLY RUN EXPOSED ON EXISTING CEILING -- RELOCATE TO ABOVE
NEW CEILING.
BUILDING S203
| See DETAIL 5/EL100 See DETAIL 6/EL100 | |||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| EML-11 | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| S | S | ||||||||||||
| See NOTE #2 See NOTE #3 See NOTE #4 | |||||||||||||||||||||||||||||
| See NOTE #5 | |||||||||||||||||||||||||||||
| See NOTE #6 | |||||||||||||||||||||||||||||
| See NOTE #7 | |||||||||||||||||||||||||||||
| EXISTING TROUGH | |||||||||||||||||||||||||||||
| 'I-102-SS' ELEV. TINU MACH. 184 CAVH |
| JAN. 114 |
| See NOTE #10 J See NOTE #10 |
|---|
| LE | ||
|---|---|---|
See DETAIL 5/EL100
See DETAIL 6/EL100
EXISTING CONDUIT
NEW 3/4''C
ABOVE CEILING
J
FIRESTOP -- See DETAIL 4/EL500
EXISTING PANEL ''1P'' (208GrY120V)
EXISTING PANEL ''1L'' (480GrY277V)
See DETAIL 2/EL100
See DETAIL 4/EL100
EXISTING PANEL ''EML'' (480GrY277V) [EMERGENCY]
EXISTING 9KVA TRANSFORMER [EMERGENCY]
EXISTING PANEL ''EMP'' (208GrY120V) [EMERGENCY]
HVAC UNIT 'SS-201-O'
RUN 3/4''C TO EXISTING CONDUIT AT ELEVATOR PIT -- See 5/EL100
'I-102-SS'
TINU
CAVH
3#
ETON
eeS
--
'P1'
LENAP
OT
See NOTE #X
PICK UP EXISTING CONDUIT
PULL BOX ABOVE CEILING
FIRESTOP -- See DETAIL 4/EL500
See NOTE #8
S
e e FIRESTOP -- See DETAIL 4/EL500
D
fo
r
M
E
T A
IL
O
R 2 E / E
D L
E 3
T 0
A 0
IL
WINDOW ABOVE (TYPICAL)
See ELEVATION FOR DETAILS
SUBMERSIBLE POWER UNIT
NEW -- See SPECIFICATIONS
REPLACE HYDRAULIC MUFFLER
HYDRAULIC CONTROLLER
NEW -- See SPECIFICATIONS 4
EL200
C
LE
LC
CONDUIT TURNS UP
J
NEW SPECIFIED GRID
AND TILES -- See SPECIFICATIONS
S
S
NEW EMERGENCY CIRCUIT
EML-11
NEW SWITCH & PLATE
NEW LIGHT:
See NOTE #2
AR
Bullard Associates
Engineers
1 Water Thrush Road
Lake Wylie, SC 29710
Telephone: 803-701-7151
ELEV.
Mobile: 704-604-9609
191
baengineers@aol.com
NCBELS Licence #F-1515
Rowan-
340 0 20
320 40
300 60
Cabarrus 280 80
062 001
042 021
COM MU N I TY CO L LEGE
022
002 081 061
041
See NOTE #2
HYDRAULIC ELEVATOR
STAIR
190 MODERNIZATION
BUILDINGS S201 + S203
STORAGE
101A SOUTH CAMPUS
ELEC.
SOUTH CAMPUS
185
1531 Trinity Church Road
PLAN: ELEVATOR MACHINE ROOM [184] - LIGHTING - NEW WORK
3 Concord, NC 28027
See NOTE #9
CORRIDOR
1/2'' = 1' - 0''
100
H CARO
T L
R I
O N
N F
ESSIO
A
O N
NEW HVAC R A
SEAL
P L
3934
E R D
See SPECIFICATIONS
MEN J .
C
N GINE E
L
A R
113 0 L
NN0R B U
See NOTE #5
ELEV.
03/26/2026
MACH.
184
See NOTE #2
See NOTE #6
JAN.
114
See NOTE #3
See NOTE #7
EXISTING TROUGH
See NOTE #4
CORRIDOR
114A
ELEVATION: WALL - NEW WORK
4
Not To Scale
NOTES:
1. See SHEET EL000 AND THE PROJECT MANUAL FOR ADDITONAL INFORMATION ON THE ELEVATOR SYSTEM.
2. FURNISH & INSTALL NEW ELEVATOR DISCONNECT: PROVIDE A NEW EATON #DH363FGK, or EQUAL, 100A/600V/3P/4W/
HD/NEMA 1 ENCLOSURE. PROVIDE EATON #DS200EK1 AUXILIARY
CONTACT. PROVIDE LABELING AS NOTED. REWORK CONDUIT AS PARTIAL PLAN: BUILDING S201
REQUIRED IF NEW SWITCH IS LARGER THAN EXISTING SWITCH. LABEL 1
SWITCH AS DIRECTED. REPLACE CONDUCTORS FROM SWITCH TO
1/4'' = 1' - 0''
NEW ELEVATOR CONTROLLER AS SHOWN IN 5/EL201.
3. REPLACE EXISTING LIGHT SWITCH AND PLATE: HUBBELL #1221GY WITH 302 BRUSHED STAINLESS STEEL PLATE.
NEW LIGHT FIXTURE SHALL BE COLUMBIA #NBT24-35LO70G-A12125F-ED1U, or EQUAL
4. EXISTING DATA BOX TO REMAIN -- INSTALL NEW CAT6 DROP -- RUN TO SERVER ROOM [208] AND PUNCH DOWN AS DIRECTED BY RCCC IT DEPARTMENT.
5. EXISTING ELEVATOR LIGHT CIRCUIT DISCONNECT TO REMAIN.
6. REMOVE EXISTING THERMOSTAT AND FILL OPENING.
7. REPLACE EXISTING RECEPTACLE WITH 20A 'GFCI' TYPE -- HUBBELL #GFR20GRY, or EQUAL.
8. USE EXISTING 'SPARE' 20A BREAKER EMP-11 TO FEED ELEVATOR PIT.
9. INSTALL NEW 20A/2P BREAKER IN EXISTING SPACES ONLY 34,36 IN EXISTING PANEL ''1P.'' USE EXISTING 20A/1P BREAKER
IN POSITION 40 TO FEED NEW GFCI RECEPTACLE.
10. PROVIDE TWO (2) NEW LIGHTS FOR ELEVATOR PIT -- INSTALL ON CAST BOX AND RUN CONDUIT TO NEW CAST BOX LOCATED
WHERE THE EXISTING LIGHT WAS REMOVED. CONNECT NEW LIGHTS TO EXISTING PIT LIGHT CIRCUIT & SWITCH.
NEW LIGHTING FIXTURES SHALL BE RAB #VXBRLED26NDG, or EQUAL. VERIFY EXACT LOCATIONS.
11. NEW LAY-IN CEILING THE EXISTING LAY-IN CEILING IN MACHINE ROOM [184] SHALL BE REMOVED -- A NEW 2' by 2' LAY-IN
CEILING SHALL BE INSTALLED WITH STANDARD TEES AND CEILING TILES SPECIFIED ON SHEET EL000. TEES SHALL BE EQUAL TO
ARMSTRONG:
PRELUDE ML MAIN BEAM
PRELUDE ML CROSS TEE
7/8'' HEMMED ANGLE MOLDING
REVISIONS
LAY-OUT AS SHOWN ON THE DRAWINGS, INSTALLATION PER MANUFACTURER'S INSTRUCTIONS.
NO. DATE DESCRIPTION
REMOVE EXISTING LIGHT REPLACE EXISTING OIL SHUTOFF VALVE
'GFIC' RECEPTACLE See SPECIFICATIONS
PLAN: ELEVATOR PIT - NEW WORK
6
1/2'' = 1' - 0''
NEW JACK PACKING
BUILDING S201 PLAN -
NEW WORK
PLAN: ELEVATOR MACHINE ROOM [184] - NEW WORK
5
REPAINT PIT STEEL & FLOOR
1/2'' = 1' - 0''
REPLACE PIT CAN
SHEET TITLE
26010.00
ELEVATOR PIT: BUILDING S201 See SHEET EL400 for BASE BID & ALTERNATES DETAILS
2
PROJECT NUMBER
NEW WORK
Not To Scale BUILDING S201 EL200
1Program Files\AutoCAD R14\26010.00 - HYDRAULIC ELEVATOR MODERNIZATION - S201 + S203/EL200 - S201 Plan - New Work.dwg 03.26.2026
Thursday, March 26, 2026 6:29 am
RELEASE DATE
SHEET OF
TIUDNOC
GNITSIXE
PROVIDE NEW 'GFCI' RECEPTACLE
CONNECT TO NEW CIRCUIT EMP-1
See
NOTE #10
INSTALL NEW CAST BOX
WHERE EXISTING LIGHT
WAS REMOVED
See
NOTE #10
CONDUIT EXTENDS TO
EXISTNG PANEL ''1P'',
RE-ROUTE CONDUIT TO
EXISTING PANEL ''EMP''
| ELEV. 191 EP-2 S | |||
| RA S |
| ELEV. 191 |
| ELEV. MACH. 181 |
| HVAC PIPING SET | |
|---|---|
| STORAGE 103 See DETAIL 1/EL500 |
| ELEV. 191 |
| S T ELEV. 191 | |
|---|---|
| Se | e DETAIL 5/EL500 | |||||
|---|---|---|---|---|---|---|
| 71# ETON eeS | ||||||
| EXISTING DUCT See NOTE #20 | EXISTING DUCT NEW LIGHT | |||||
| NEW ''SS-203-I'' GNILIEC 201LE/2 ROOD GNTSIXE LIATED GNITSIXE eeS EVOMER | See NOTE #21 EXISTING 1-H MASONRY W STORAGE 103 | |||||
| ROOD GNITSIXE | ||||||
| OUR ALL | ||||||
S
J
EP-2
S
RA
6
EL201
EXISTING EXTERIOR WALL
12''
NEW HVAC UNIT
''SS-203-O''
EXISTING GRADE
(VERIFY)
EXISTING DUCT
4'' THICK CONCRETE PAD
VERIFY SIZE
HVAC LINES IN SUITABLY
SIZED PVC CONDUIT
NEW ''SS-203-I''
EXISTING CEILING
to REMAIN
to REMAIN
MASONRY WALL
GNILIEC
GNTSIXE
EVOMER
201LE/2
LIATED
eeS
ROOD
GNITSIXE
See NOTE #22 (TYPICAL)
See DETAIL 5/EL500
EXISTING DUCT
See NOTE #20
See NOTE #19
EXISTING DUCTS
See NOTE #21
71#
ETON
eeS
81#
ETON
eeS
NEW 1-HOUR GWB CEILING
USE TWO 45-DEGREE FITTINGS
EXISTING 1-HOUR
YLETAMIXORPPA
EDARG
WOLEB
TEEF
6
YFIREV
OT
ROTCARTNOC
32#
ETON
eeS
CORRIDOR CORRIDOR
101 101
CORRIDOR
101
Bullard Associates
ELEV. Engineers
191
ELEV.
1 Water Thrush Road
191
Lake Wylie, SC 29710
Telephone: 803-701-7151
Mobile: 704-604-9609
S T STAIR STAIR
baengineers@aol.com
190 190
NCBELS Licence #F-1515
EXISTING ELEVATOR PIT THERMAL DETECTOR
Rowan- to REMAIN -- See NOTE #6 340 0 20
320 40
300 60
EXISTING ELEVATOR PIT THERMAL DETECTOR Cabarrus 280 80
to REMAIN -- See NOTE #6 062 001
042 021
See NOTE #12 M
EL
A
E
C
V
H
.
. COM MU N I TY COL LEGE
022
002 081 061
041
181
ELEV.
HYDRAULIC ELEVATOR
191
MODERNIZATION
S EXISTING ELEVATOR RECALL
ELEV. BUILDINGS S201 + S203
to REMAIN -- See NOTE #6
MACH.
181
SOUTH CAMPUS
STORAGE
103 STORAGE
103
SOUTH CAMPUS
1531 Trinity Church Road
NEW SUBMERSIBLE POWER UNIT -- See SPECS.
PARTIAL PLAN: CEILING - NEW WORK
NEW HYDRAULIC CONTROLLER -- See SPECS. Concord, NC 28027
2
1/4'' = 1' - 0''
PARTIAL PLAN: HVAC - NEW WORK H CARO
T L
1 R I
O N
N F
ESSIO
A
O N
1/4'' = 1' - 0'' R SEAL A
ELEV. See NOTE #14 CORRIDOR P L
3934
MACH. 101 J . E N GINE E R A R D
C L
0 L
181 NN0R B U
CORRIDOR
101 03/26/2026
S T
ELEV.
EXISTING FIRE ALARM CONTROL RELAY to REMAIN
191
ELEV.
EXISTING FIRE ALARM JUNCTION BOX to REMAIN
STAIR
191
EXISTING CAR LIGHT DISCONNECT to REMAIN 190
NEW ELEVATOR POWER DISCONNECT -- See NOTE #15
S STAIR
190
STORAGE
103
ELEV. S T
MACH.
181
S
ELEV.
EXISTING JUNCTION BOX
MACH.
FOR ELEVATOR CAR
181
STORAGE COMMUNICATIONS WIRING
103 See NOTE #11
PARTIAL PLAN: ELEVATOR EQUIPMENT - NEW WORK
5
STORAGE
1/2'' = 1' - 0''
103
PARTIAL PLAN: COMM - NEW WORK
4
1/4'' = 1' - 0''
PARTIAL PLAN: FIRE ALARM - NEW WORK
3
1/4'' = 1' - 0''
NEW WORK NOTES: NEW WORK NOTES:
1. See SHEET EL000 AND THE PROJECT MANUAL FOR ADDITONAL INFORMATION ON THE ELEVATOR SYSTEM. 16. NEW WIRELESS HVAC CONTROL: See SPECIFICATIONS, LOCATE AS DIRECTED.
2. RUN CONDUIT CONTAINING POWER FOR ''SS-203-O'' & EXTERIOR 'GFCI' RECEPTACLE NEAR OUTDOOR HVAC UNIT -- See 1/EL3OO. 17. NEW HVAC LINE SET: ROUTING OF HVAC LINE SET IS SHOWN FOR INTENT.
CONTRACTOR SHALL VERIFY ROUTE TO AVOID
3. SEAL AROUND CONDUIT, FIRE STOPPING NOT REQUIRED. CONFLICTS WITH EXISTING DUCTWORK AND
OTHER ITEMS. LINE SET SHALL BE PROTECTED
4. EXISTING LIGHTS, SWITCH & WIRING SHALL REMAIN. REPLACE LAMPS IN LIGHT FIXTURES WITH GE #93129366 LAMP. AND SUPPORTED PROPERLY.
5. PROVIDE NEW FIXTURE WITH NEW SWITCH & PLATE: LIGHT = COLUMBIA #NBT24-35LO70G-A12125F-ED1U, or EQUAL - USE EXISTING CIRCUIT EP-2. 18. DISCONNECT & SERVICE RECEPTACLE: See DRAWING DETAILS FOR OUTDOOR UNIT
HUBBELL #1221-GY SWITCH WITH MATCHING 302 STAINLESS STEEL PLATE. DISCONNECT AND SERVICE RECEPTACLE.
6. FIRE ALARM SUB-CONTRACTOR SHALL VERIFY THAT THE DEVICES ARE FUNCTIONING PROPERLY WITH THE NEW ELEVATOR SYSTEM. 19. EXTERIOR WALL PENETRATION: See DETAILS 1/EL500 AND 2/EL500 for
SEALING AROUND LINES IN EXTERIOR WALLS.
7. SAME AS NOTE 6. EXCEPT DEVICES SHALL BE BE RELOCATED FROM GWB CEILING BEING REMOVED TO THE NEW LAY-IN CEILING.
NEW LIGHT
20. NEW LAY-IN CEILING: See DRAWING DETAILS & SPECIFICATIONS.
8. EXISTING SPRINKLER HEAD WILL BE RELOCATED TO NEW CEILING BY OWNER.
21. FIRE-RATED WALL PENETRATIONS: See DETAILS 3/EL500 (HVAC LINE SET) &
9. FIRE ALARM SUB-CONTRACTOR SHALL VERIFY THAT THIS SMOKE DETECTOR IS INACTIVE, IF SO, HE SHALL REMOVE IT COMPLETELY. 4/EL500 (ELECTRICAL).
REVISIONS
10. WIRING CONNECTION TO NEW CONTROLLER: RE-ROUTE EXISTING COMMUNICATION CONDUIT TO NEW ELEVATOR CON- 22. EXISTNG DUCTWORK: LOCATIONS AND SIZES OF EXISTING DUCTWORK NO. DATE DESCRIPTION
TROLLER -- PULL IN EXISTING & NEW CONDUCTORS SHOWN ARE BASED ON AVAILABLE RECORD
DOCUMENTS -- CONTRACTOR SHALL VERIFY
11. EXISTING CAR COMMUNICATIONS BOX: EXISTING BOX CURRENTLY CONTAINS TELEPHONE CABLE. LEAVE EXISTING
SIZES AND LOCATIONS. HE SHALL ADJUST HIS
CABLE AND FURNISH & INSTALL TWO (2) CAT6 DATA CABLES FROM RACK
LAYOUTS TO SUIT THE ACTUAL DUCTWORK
IN MDF [208B] -- VERIFY CONNECTION POINT WITH RCCC IT DEPARTMENT.
LOCATIONS AND SIZES.
STORAGE
12. EXISTING ELEVATOR PIT RECEPTACLES: RECEPTACLES SHALL REMAIN IN SERVICE.
23. EXCAVATION/BACKFILL AN APPROXIMATE 6 FOOT DEEP EXCAVATION 103
WILL BE NEEDED TO INSTALL ELECTRICAL
13. EXISTING ELEVATOR PIT RECEPTACLE: EXISTING RECEPTACLE FEEDING EXISTING SUMP PUMP -- VERIFY THAT PUMP
CONDUIT AND HVAC LINE SET THROUGH
IS OPERATING PROPERLY, CLEAN PUMP AND PIT.
EXISTING CONCRETE WALL. THIS SHALL BE
ELEV.
DONE BY AN EXPERIENCE CONTRACTOR AND
14. EXISTING MACHINE ROOM RECEPTACLE: REPLACE: HUBBELL #GFR20GYB RECEPTACLE WITH MATCHING 302 STAINLESS STEEL
MACH.
PLATE. MODIFY WIRING AS REQUIRED FOR GROUND-FAULT PROTECTION. LABEL PLATE SHALL COMPLY WITH OSHA AND OTHER 181 BUILDING S203 PLAN -
APPLICABLE REGULATIONS. BACKFILL SHALL
PER DRAWING DETAIL. NEW WORK
BE INSTALLED PER SPECIFICATIONS.
15. FURNISH & INSTALL NEW ELEVATOR DISCONNECT: PROVIDE A NEW EATON #DH363FGK, or EQUAL, 100A/600V/3P/4W/
HD/NEMA 1 ENCLOSURE. PROVIDE EATON #DS200EK1 AUXILIARY 24. NEW LAY-IN CEILING XTHE GWB CEILING IN MACHINE ROOM [181]
CONTACT. PROVIDE LABELING AS MOTED. REWORK CONDUIT AS SHALL BE REMOVED -- A NEW 2' by 2' LAY-IN SECTION: NEW WORK
REQUIRED IF NEW SWITCH IS LARGER THAN EXISTING SWITCH. LABEL CEILING SHALL BE INSTALLED WITH STANDARD 6
SHEET TITLE
SWITCH AS DIRECTED. REPLACE CONDUCTORS FROM SWITCH TO TEES AND CEILING TILES SPECIFIED ON
1/4'' = 1' - 0''
NEW ELEVATOR CONTROLLER AS SHOWN IN 5/EL201. SHEET EL000. TEES SHALL BE EQUAL TO
ARMSTRONG:
26010.00
PRELUDE ML MAIN BEAM
PRELUDE ML CROSS TEE
PROJECT NUMBER
7/8'' HEMMED ANGLE MOLDING
EL201
LAY-OUT AS SHOWN ON THE DRAWINGS,
1Program Files\AutoCAD R14\26010.00 - HYDRAULIC ELEVATOR MODERNIZATION - S201 + S203/EL201 - S203 Plan - New Work.dwg INSTALLATION PER MANUFACTURER'S 03.26.2026
Thursday, March 26, 2026 7:56 am
INSTRUCTIONS.
RELEASE DATE
SHEET OF
TINU
CAVH
WEN
''I-302-SS''
HVAC PIPING SET
See DETAIL 2/EL500
NEW DISCONNECT & DUPLEX RECEPTACLE
EXISTING DUCTS
See SECTION NEW HVAC UNIT ''SS-203-O''
GNIRIW
LACIRTCELE
2#
ETON
eeS
003LE/1
LIATED
&
NOITAUNITNOC
rof
GNILIEC
NI-YAL
EVOBA
PULL BOX(ES) AS REQUIRED
EXISTING LIGHTS, SWITCH
& WIRING SHALL REMAIN
See NOTE #4
EXISTING SWITCH
to REMAIN
RELOCATED SPRINKLER
NEW LIGHT & SWITCH
See NOTE #5
NEW LAY-IN CEILING
See DETAIL 3/EL500 See NOTE #24
See NOTE #13
See DETAIL 1/EL500
See NOTE #16
EXISTING CAR PHONE BOX -- See NOTE #11 EXISTING SMOKE &
HEAT DETECTORS
SHALL REMAIN
IN OPERATION
See NOTE #6
NEW ELEVATOR
See NOTE #7
CONTROLLER
EXISTING SPRINKLER
See NOTE #10
NEAD TO BE RE-
LOCATED TO NEW
CEILING - See NOTE #8
See NOTE #9
NEW LIGHTING & CEILING
See DETAIL 2/EL201
3#
ETON
eeS
See SHEET EL401 for BASE BID & ALTERNATES DETAILS
BUILDING S203
| )-/+( ''2 -'8 ''0-'9 YLETAMIXORPPA ELEVATOR MACHINE ROOM 181 EXISTING FLOOR | ||||
|---|---|---|---|---|
| LEVATOR HINE ROOM ELEVATOR 181 191 See DETAIL 4/EL500 for LINE SET | |
|---|---|
| STORAGE See DETAIL 5/EL500 for CONDENSATE 103 DRAIN See DETAIL 4/EL500 CONDENSATE LINE DRAIN INTO EXISTING SINK |
| E JANITOR 103 | |
|---|---|
'DTD' 'DT' 'SDP'
'PE'
'LE''STA'
'L1' 'P1'
'DPDS'
'PDM'
'P' 'LS'
Bullard Associates
ELEC.
180A
Engineers
1 Water Thrush Road
Lake Wylie, SC 29710
Telephone: 803-701-7151
EXISTING PANEL
Mobile: 704-604-9609
baengineers@aol.com
NCBELS Licence #F-1515
MECHANICAL
180 Rowan-
340 0 20
320 40
300 60
Cabarrus 280 80
062 001
042 021
COM MU N I TY COL LEGE
022
002 081 061
041
HYDRAULIC ELEVATOR
MODERNIZATION
BUILDINGS S201 + S203
SOUTH CAMPUS
SOUTH CAMPUS
1531 Trinity Church Road
Concord, NC 28027
H CARO
T L
R I
O N
J N O F
ESSIO
N A
R A
SEAL P L
3934
E R D
J
J .
C
N GINE E
L
A R
0 L
NN0R B U
03/26/2026
R
O
D
EXISTING PANEL ''1P'' O R RI 1 1 5
208GrY120V C REVISIONS
NO. DATE DESCRIPTION
ELEV.
191
ELEV.
MACH.
184
HVAC SPLIT-SYSTEM
CONNECTIONS
SHEET TITLE
PARTIAL SITE PLAN 26010.00
1
PROJECT NUMBER
3/32'' = 1' - 0''
EL300
1Program Files\AutoCAD R14\26010.00 - HYDRAULIC ELEVATOR MODERNIZATION - S201 + S203/EL300 - Split-System Connections.dwg 03.26.2026
Thursday, March 26, 2026 7:00 am
RELEASE DATE
SHEET OF
005LE/4
LIATED
eeS
--
TIUDNOC
GNUORA
POTSEREIF
See NOTE #4
3
EL301
MEN
104
'SS-203-O'
WINDOW ABOVE (TYPICAL) ELEVATOR
MACHINE ROOM ELEVATOR ELEV.
181 191 MACH.
181
EXISTING SHRUB TO BE REMOVE/RELOCATED BY OWNER
REMOVE EXISTING
ELEVATOR
JANITOR
GWB CEILING 191
103
EXISTING TREE TO REMAIN
See DETAIL 4/EL500 for LINE SET
STORAGE See DETAIL 5/EL500 for CONDENSATE
103 DRAIN
'SS-203-O'
See DETAIL 4/EL500
See DETAILS 1/EL500 & 2/EL500
CONDENSATE LINE
DRAIN INTO EXISTING SINK
(EXISTING)
EXISTING
FLOOR
SECTION: ROOM [181] PARTIAL PLAN: BUILDING S203
4 3
1/2'' = 1' - 0'' 3/32'' = 1' - 0''
WINDOW ABOVE (TYPICAL)
SHRUB TO BE REMOVED/RELOCATED BY OWNER
POWER DISCONNECT
& GFCI RECEPTACLE
NOTES:
OUTDOOR UNIT 'SS-201-O'
1. THE LAYOUTS AND DETAILS SHOWN ON THIS DRAWING COVER THE INSTALLATION OF THE SPLIT-SYSTEM HVAC SYSTEMS
SHRUB TO BE REMOVED/RELOCATED BY OWNER REQUIRED. ADDITIONAL INFORMATION IS CONTAINED ON OTHER DRAWINGS IN THIS SET.
2. AT BUILDING S201, THERE ARE CONFLICTS WITH THE OUTDOOR UNIT AND EXISTING PLANTING. OWNER WILL REMOVE
AND/OR RELOCATE THE PLANTING -- GC SHALL COORDINATE.
ELEVATOR
3. AT BUILDING S203, THERE MAY BE CONFLICTS WITH THE OUTDOOR UNIT AND EXISTING PLANTING. OWNER WILL REMOVE
MACHINE ROOM
3 AND/OR RELOCATE THE PLANTING -- GC SHALL COORDINATE. 184
EL301
0 4. PROVIDE NEW BREAKERS IN EXISTING PANEL ''SL'' TO FEED NEW SPLIT-SYSTEM AND THE SERVICE RECEPTACLE.
'SS-201-I' 0
2 EXISTING PANEL: EATON TYPE 'PRL2a' INSTALLED IN 2018, PROVIDE THE FOLLOWING CIRCUIT BREAKERS:
L
E
/
1 CIRCUIT SL-42, 20A/1P to FEED SERVICE RECEPTACLE
L
AI
CIRCUIT SL-38,40, 20A/2P to FEED ''SS-203-0'' CONDENSING UNIT
0 T
0 E
5 D
E
L
NEW SPLIT-SYSTEM INDOOR UNIT ''SS-201-I'' e
POSITIONS SHOWN ARE ''SPACES ONLY,'' SO NEW BREAKERS NEED TO BE FURNISHED -- NEW BREAKERS SHALL MATCH
/ e
L
4 S EXISTING.
AI EXISTING WINDOW ABOVE
LARGE SHRUB TO REMAIN E T
D
e CONFLICTING 5. PROVIDE 'GFCI' 20A DUPLEX RECEPTACLE IN A CAST BOX WITH 'IN-USE' WEATHER PROOF COVER NEAR THE OUTDOOR
e
S
TREE & SHRUBBERY CONDENSING UNIT -- SEE DRAWING FOR LOCATION. BOX = BELL #5346-0
See NOTE #2 COVER = HUBBELL-TAYMAC #MX7280S
See DETAILS 1/EL500 & 2/EL500 NEW ''SS-201-O'' UNIT RECEPTACLE = HUBBELL #GFTW20GY
CENTER BETWEEN WINDOWS ABOVE
6. 2#12 + 1#12 (e.g.) in 3/4'' GRC.
EXISTING WINDOW ABOVE
7. 2#10 + 1#10 (e.g.) in 3/4'' GRC.
See DETAIL 1/EL200 for CONTINUATION
8. 4#10 + 1#10 (e.g.) in 3/4'' GRC.
PARTIAL PLAN: BUILDING S201
2
3/32'' = 1' - 0''
)-/+(
''2
-'8
YLETAMIXORPPA
''0-'9
20 GA. 3-5/8'' STEEL STUDS
16'' ON CENTERS
4
EL300
1-HOUR GYPSUM BOARD MEMBRANE SECTION
UL DESIGN i504
3 LAYERS OF 5/8'' FIRE-SHIELD
GYPSUM BOARD
NEW 2' by 2' LAY-IN CEILING
NOT RATED
See SPECIFICATIONS
ELEVATOR
MACHINE ROOM
181
1-HOUR RATED CMU WALL
| UNIT DESIGNATION | MODEL NUMBER | LOCATION |
|---|---|---|
| ''SS-201-O'' | DAIKIN #RX18XVJU | BUILDING S201, EXTERIOR |
| ''SS-201-I'' | DAIKIN #FTX18AXVJU | BUILDING S201, ROOM 184. ELEVATOR MACHINE ROOM |
| ''SS-203-O'' | DAIKIN #RX18XVJU | BUILDING S203, EXTERIOR |
| ''SS-203-I'' | DAIKIN #FTX18AXVJU | BUILDING S203, ROOM 181. ELEVATOR MACHINE ROOM |
MOUNT ON EXISTING WALL NOTES:
'GFCI' WEATHER PROOF RECEPTACLE
See NOTE #5 1. THE LAYOUTS AND DETAILS SHOWN ON THIS DRAWING COVER THE INSTALLATION OF THE SPLIT-SYSTEM HVAC SYSTEMS
ELECTRICAL LINE REQUIRED. ADDITIONAL INFORMATION IS CONTAINED ON OTHER DRAWINGS IN THIS SET.
Bullard Associates
2. AT BUILDING S201, THERE ARE CONFLICTS WITH THE OUTDOOR UNIT AND EXISTING PLANTING. OWNER WILL REMOVE
SPLIT-SYSTEM HEAT SPLIT-SYSTEM HEAT AND/OR RELOCATE THE PLANTING -- GC SHALL COORDINATE. Engineers
MIDWEST #U065P, OR EQUAL, MIDWEST #U065P, OR EQUAL,
PUMP OUTDOOR UNIT PUMP OUTDOOR UNIT
DISCONNECT DISCONNECT
See SPECIFICATIONS See NOTE #6 See SPECIFICATIONS See NOTE #6 3. AT BUILDING S203, THERE MAY BE CONFLICTS WITH THE OUTDOOR UNIT AND EXISTING PLANTING. OWNER WILL REMOVE 1 Water Thrush Road
'SS-203-O'' 'SS-201-O'' Lake Wylie, SC 29710
See NOTE #7 See NOTE #8 See NOTE #8 AND/OR RELOCATE THE PLANTING -- GC SHALL COORDINATE.
Telephone: 803-701-7151
4. PROVIDE NEW BREAKERS IN EXISTING PANEL ''SL'' TO FEED NEW SPLIT-SYSTEM AND THE SERVICE RECEPTACLE. Mobile: 704-604-9609
baengineers@aol.com
EXISTING PANEL: EATON TYPE 'PRL2a' INSTALLED IN 2018, PROVIDE THE FOLLOWING CIRCUIT BREAKERS:
NCBELS Licence #F-1515
LINE LINE
4'' CONCRETE PAD 4'' CONCRETE PAD CIRCUIT SL-42, 20A/1P to FEED SERVICE RECEPTACLE
SET SET
FINISHED GRADE FINISHED GRADE CIRCUIT SL-38,40, 20A/2P to FEED ''SS-203-0'' CONDENSING UNIT
Rowan-
340 0 20
POSITIONS SHOWN ARE ''SPACES ONLY,'' SO NEW BREAKERS NEED TO BE FURNISHED -- NEW BREAKERS SHALL MATCH 320 40
300 60
EXISTING. Cabarrus 280 80
062 001
CONDUIT or SLEEVE TO PROTECT THE LINE SET CONDUIT or SLEEVE TO PROTECT THE LINE SET
042 021
5. PROVIDE 'GFCI' 20A DUPLEX RECEPTACLE IN A CAST BOX WITH 'IN-USE' WEATHER PROOF COVER NEAR THE OUTDOOR
COM MU N I TY COL LEGE
022
002 081 061
041
CONDENSING UNIT -- SEE DRAWING FOR LOCATION. BOX = BELL #5346-0
COVER = HUBBELL-TAYMAC #MX7280S
HYDRAULIC ELEVATOR
RECEPTACLE = HUBBELL #GFTW20GY
MODERNIZATION
6. 2#12 + 1#12 (e.g.) in 3/4'' GRC.
BUILDINGS S201 + S203
7. 2#10 + 1#10 (e.g.) in 3/4'' GRC.
SOUTH CAMPUS
8. 4#10 + 1#10 (e.g.) in 3/4'' GRC.
FRONT FRONT
INTER-UNIT WIRE
DETAIL: EXTERIOR HVAC UNIT ('SS-203-O') DETAIL: EXTERIOR HVAC UNIT ('SS-201-O')
3 2
GAS PIPE LIQUID PIPE
SOUTH CAMPUS
1'' = 1' - 0'' 1'' = 1' - 0''
1531 Trinity Church Road
Concord, NC 28027
GAS PIPE INSULATION LIQUID PIPE INSULATION
EXISTING PANEL '1P' LOCATED IN ELECTRICAL [185] EXISTING PANEL 'SL' LOCATED IN MECHANICAL [180]
FINISHING TAPE
PROVIDE THE FOLLOWING NEW CIRCUIT BREAKERS: PROVIDE THE FOLLOWING NEW CIRCUIT BREAKERS:
DRAIN HOSE
FOR SPLIT-SYSTEM: POSITION 1P-40,42; 20A/2P/120/240V/10KAIC FOR SPLIT-SYSTEM: POSITION SL-38,40; 20A/2P/120/240V/10KAIC H CARO
MIDWEST 3U065P, or EQUAL MIDWEST 3U065P, or EQUAL R T L I
FOR SITE RECEPTACLEP:OSITION 1P-38; 20A/1P/120V/10KAIC FOR SITE RECEPTACLE: POSITION SL-42; 20A/1P/120V/10KAIC
N
O
F
ESSIO N
A
O N
See NOTE #5 EXISTING PANEL IS GE MODEL XX, NEW BREAKERS SHALL BE See NOTE #5 EXISTING PANEL IS EATON TYPE PRL2a, NEW BREAKERS SHALL BE R A
SEAL
PANEL COMPATIBLE WITH THIS PANEL -- PROVIDE ALL MOUNTING HARD- PANEL COMPATIBLE WITH THIS PANEL -- PROVIDE ALL MOUNTING HARD- WRAP INSULATED PIPE WITH FINISHING P L
2#10 + 1#10(e.g.) in 3/4''C [CKT. 1P-38] 2#10 + 1#10(e.g.) in 3/4''C [CKT. SL-42] 3934
'SS-201-O' '1P' WARE AND TRIM PIECES -- LABEL AS DIRECTED. 'SS-201-O' 'SL' WARE AND TRIM PIECES -- LABEL AS DIRECTED. CONDENSING UNIT TAPE FROM ONE END TO THE OTHER J . C E N GINE E R L A R D
0 L
See SPECIFICATIONS NN0R B U
EXISTING EXISTING
MAXIMUM LENGTH BETWEEN INDOOR AND
U U
03/26/2026
208GrY120V 208GrY120V OUTDOOR UNIT = 98.4 FEET
SPLIT-SYSTEM 4#10 + 1#10(e.g.) in 3/4''C in 3/4'C SPLIT-SYSTEM 4#10 + 1#10(e.g.) in 3/4''C in 3/4'C
HEAT PUMP HEAT PUMP
OUTDOOR UNIT OUTDOOR UNIT
NOTE: NOTE:
RISER DIAGRAM IS SCHEMATIC, See SHEET EL200 FOR ACTUAL RISER DIAGRAM IS SCHEMATIC, See SHEET EL201 FOR ACTUAL
RIGHT SIDE PLATE
INSTALLATION DETAILS. INSTALLATION DETAILS.
FINISHED GRADE FINISHED GRADE
2#10 + 1#10(e.g.) [CKT. 1P-40,42] in 3/4''C 2#10 + 1#10(e.g.) [CKT. SL-38,40] in 3/4''C
INCOMING ELECTRICAL SERVICE
POWER RISER DIAGRAM (BUILDING S201) POWER RISER DIAGRAM (BUILDING S203)
PROVIDE MOUNTING FRAME or PREFABRICATED BASE
5 4
NOTE:
Not To Scale Not To Scale
See SPECIFICATIONS FOR INFORMATION ABOUT THE MINI-SPLIT SYSTEM. INSTALLATION SHALL BE
IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTION AND ALL APPICABLE CODES AND ORDINANCES.
SUB-CONTRACTOR SHALL BE AN APPROVED MECHANICAL CONTRACTOR LICENSED IN THE STATE
OF NORTH CAROLINA.
See DRAWINGS FOR ACTUAL DETAILS.
SPLIT-SYSTEM HVAC SYSTEM LEGEND:
UNIT DESIGNATION MODEL NUMBER LOCATION COMMENTS
TYPICAL OUTDOOR HVAC UNIT DETAILS
''SS-201-O'' DAIKIN #RX18XVJU BUILDING S201, EXTERIOR See SPECIFICATIONS 6
''SS-201-I'' DAIKIN #FTX18AXVJU BUILDING S201, ROOM 184. ELEVATOR MACHINE ROOM See SPECIFICATIONS
Not To Scale
''SS-203-O'' DAIKIN #RX18XVJU BUILDING S203, EXTERIOR See SPECIFICATIONS
''SS-203-I'' DAIKIN #FTX18AXVJU BUILDING S203, ROOM 181. ELEVATOR MACHINE ROOM See SPECIFICATIONS
REVISIONS
NO. DATE DESCRIPTION
HVAC SPLIT-SYSTEM
DETAILS
SHEET TITLE
26010.00
PROJECT NUMBER
EL301
1Program Files\AutoCAD R14\26010.00 - HYDRAULIC ELEVATOR MODERNIZATION - S201 + S203/EL301 - Split-System Details.dwg 03.26.2026
Thursday, March 26, 2026 8:00 am
RELEASE DATE
SHEET OF
24-LS
.TKC
ALIGN TOP OF DISCONNECT
WITH TOP OF CONDENSING 'GFCI' WEATHER PROOF RECEPTACLE
UNIT See NOTE #5
ELECTRICAL LINE
PVC COVERED FLEX PVC COVERED FLEX
CKT. SL-38,40 CKTS. SL-38,40,42
4'' (TYPICAL)
04-P1
.TKC
MOUNT ON EXISTING WALL
ALIGN TOP OF DISCONNECT
WITH TOP OF CONDENSING
UNIT
See NOTE #7
CKT. 1P-34,36 CKTS. 1P-34,36,40

With GovernmentContracts, you can:
Follow Multiple Building Fire Exhaust Systems Repairs Active Contract Opportunity Notice ID N4008526R9059
DEPT OF DEFENSE
Bid Due: 8/05/2026
Follow 43d Air Mobility Squadron_ Request for Proposal_FA445226R0012_B753 Kitchen Renovation Active Contract Opportunity
DEPT OF DEFENSE
Bid Due: 8/05/2026
Follow Multiple Base-wide Location Fencing Repairs Active Contract Opportunity Notice ID N4008524R9072 Related
DEPT OF DEFENSE
Bid Due: 8/20/2026
Project: Federal Pipe Video Contracts Ref. #: 269- 2026-235 Department: City Procurement Type:
City of Charlotte
Bid Due: 8/24/2026