J059--Newington Replacement Breakers
| Location: |
Virginia |
| Posted: |
Aug 18, 2025 |
| Due: |
Aug 25, 2025 |
| Agency: |
VETERANS AFFAIRS, DEPARTMENT OF |
| Type of Government: |
Federal |
| Category: |
- J - Maintenance, Repair, and Rebuilding of Equipment
|
| Solicitation No: |
36C24125Q0602 |
| Publication URL: |
To access bid details, please log in. |
J059--Newington Replacement Breakers
Active
Contract Opportunity
Department/Ind. Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-tier
VETERANS AFFAIRS, DEPARTMENT OF
Office
241-NETWORK CONTRACT OFFICE 01 (36C241)
Looking for contract opportunity help?
General Information View Changes
-
Contract Opportunity Type: Combined Synopsis/Solicitation (Updated)
-
Updated Published Date: Aug 18, 2025 11:33 am EDT
-
Original Published Date: Jul 02, 2025 11:19 am EDT
-
Updated Date Offers Due: Aug 25, 2025 05:00 pm EDT
-
Original Date Offers Due: Jul 15, 2025 05:00 pm EDT
-
Inactive Policy: Manual
-
Updated Inactive Date: Sep 24, 2025
-
Original Inactive Date:
Sep 13, 2025
-
Initiative:
Classification View Changes
Description View Changes
36C241-25-AP-4384 Newington Replacement Breakers Q and A
Can you please advise part # of breaker needed / pictures of existing breaker?
There are 2 breakers noted in the solicitation. The first of which cannot be racked out for information due to the support bracket being damaged. This is the breaker that needs to be replaced. Here is the information I have available to me:
MFR: EATON
Catalog # MDN4083XEA0552N
Frame Type: K600-AR-600NM
Frame Size: 800
Voltage Rating: 480
Trip Unit: DIGITRIP 520
Trip Rating: 250
Can you please send us the catalog number for this breaker and information on the trip unit? If you have any pictures, that would help.
The second breaker failed a trip test and will need the trip unit replaced. Here is the information I have available from the second breaker.
MFR: EATON
Catalog # MDN4083XEA0552N
Frame Type: K600-AR-600NM
Frame Size: 800
Voltage Rating: 480
Trip Unit: DIGITRIP 520
Trip Rating: NA (This will need to be dialed in as best you can)
Please note as stated in the SOW, this breaker will need a temporary unit for use until the trip unit is rebuilt, and the breaker can be racked back in. This unit supports the hospital s CT scanners and downtime is not acceptable.
Please also note that each breaker will require a testing report via secondary injection testing to verify functionality.
Attachments/Links
Contact Information
Contracting Office Address
-
ONE VA CENTER
-
TOGUS , ME 04330
-
USA
Secondary Point of Contact
History
Daily notification on new contract opportunities
With GovernmentContracts, you can:
- Find more opportunities and win more business
- Receive daily alerts for all new bid opportunities
- Get contract opportunities matched to your business
ONE WEEK FREE TRIAL
See also
...scanners, extended-use tanks, loader options, tube racks, CST beads, buffers, cleaning solutions, assay... ...
VETERANS AFFAIRS, DEPARTMENT OF
Bid Due: 6/16/2026
* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.