PUBLIC SCHOOL
FIRE ALARM SYSTEM
GENERAL NOTES:
1 THE FIRE ALARM SYSTEM SHALL CONFORM TO ARTICLE 760, CA ELEC. CODE. WIRING
MUST BE LISTED FOR USE AS REQUIRED BY TITLE 24/CEC, ARTICLE 760.
2 WIRE USED IN WET LOCATIONS SHALL BE OF AN APPROVED TYPE IN ACCORDANCE
WITH 3-310-8, T24/CEC (I.E. THHW OR EQUAL).
3 UNDERGROUND AND EXTERIOR CONDUITS TO HAVE WATERTIGHT FITTINGS AND
WIRES APPROVED FOR WET LOCATION.
4 ALL CONDUCTORS SHALL BE ROUTED IN CONDUIT UNLESS SPECIFICALLY NOTED
OTHERWISE ON PLANS. MINIMUM CONDUIT SIZE SHALL BE 3/4."
5 THE CONDUIT AND WIRE SHOWN ON THESE PLANS ARE SHOWN DIAGRAMMATICALLY.
EXACT LOCATIONS SHALL BE DETERMINED IN THE FIELD TO SUIT FIELD CONDITIONS.
"AS-BUILT" PLANS SHALL BE MAINTAINED AND BE PROVIDED AS REQUIRED BY THE
PROJECT INSPECTOR OF RECORD.
6 PENETRATIONS OF FIRE RATED WALLS SHALL BE PROTECTED IN ACCORDANCE WITH
CALIFORNIA BUILDING CODE, CHAPTER 7, TITLE 24.
7 ALL DEVICES SHALL BE "CSFM" LISTED.
8 EXTERIOR DEVICES SHALL BE LISTED FOR EXTERIOR USE BY "CSFM."
9 AUDIBLE ALARM PRODUCED BY THE FIRE ALARM SYSTEM SHALL BE CAPABLE OF
PRODUCING A DISTINCTIVE THREE-PULSE TEMPORAL PATTERN FIRE ALARM
EVACUATION SIGNAL.
10 AUDIBLE DEVICES TO BE AT LEAST 15 DBA ABOVE THE EQUIVALENT SOUND LEVEL
BUT NOT LESS THAN 75 DBA AT 10 FEET OR MORE THAN 110 DBA IN TOTAL,
THROUGHOUT.
11 WHERE VISUAL DEVICES ARE REQUIRED, VISUAL DEVICE SHOULD NOT EXCEED 2
FLASHES PER SECOND AND SHOULD NOT BE SLOWER THAN 1 FLASH EVERY
SECOND. THE DEVICE SHALL HAVE A PULSING LIGHT SOURCE NOT LESS THAN 15
CANDELA. NO PLACE IN ANY ROOM SHALL BE MORE THAN 50 FEET FROM A DEVICE.
12 CONTRACTOR SHALL PROVIDE COPIES OF APPROVED PLANS TO THE PROJECT
INSPECTOR OF RECORD PRIOR TO BEGINNING WORK. THE CONTRACTOR SHALL
SUBMIT SUBMITTAL BOOKLET TO ENGINEER PRIOR TO PURCHASE FOR REVIEW. THE
FIRE PROTECTION SYSTEM SHALL NOT BE INSTALLED UNTIL SUBMITTAL BOOKLETS
HAVE BEEN SUBMITTED TO AND APPROVED BY THE ENGINEER OF RECORD.
13 FINAL TEST SHALL BE MADE WITH DSA INSPECTOR OF RECORD (IOR). LOCAL FIRE
AUTHORITY HAVING JURISDICTION SHALL BE NOTIFIED OF DATE AND TIME OF FIRE
ALARM TESTING AND SHALL ASSIST/WITNESS SUCH TESTING WHEN ABLE.
CONTRACTOR SHALL REPEAT TESTING AS NECESSARY UNTIL SATISFACTORY
RESULTS ARE ACHIEVED.
14 FIRE ALARM CONTRACTOR SHALL PROVIDE A "RECORD OF COMPLETION" TO THE
INSPECTOR OF RECORD (IOR)/DSA AFTER COMPLETION OF OPERATIONAL
ACCEPTANCE TESTS.
15 POWER SERVICE SHALL BE ON A DEDICATED BRANCH CIRCUIT WITH A RED MARKING
AND IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL".
16 ALL ALARM SIGNALS ARE TO BE TRANSMITTED TO AN UL APPROVED
LISTED SUPERVISING STATION AND SHALL COMPLY WITH SB 575 POLICY.
17 THE MAXIMUM SPACING OF SMOKE DETECTORS SHALL BE 30 FEET AND HEAT
DETECTORS SHALL BE 50 FEET OF SEPARATION. IN THE EVENT AN ACCESSIBLE
CEILING SPACE IS DISCOVERED DURING THE COURSE OF THE PROJECT, THE
CONTRACTOR SHALL PROVIDE ADDITIONAL HEAT DETECTORS AND ACCESS
HATCHES AS NECESSARY.
18 PROJECT INSPECTOR SHALL FIELD VERIFY CANDELA SETTING ON STROBES DUE TO
FIELD ADJUSTABILITY.
19 EACH SIGNALING LINE CIRCUIT FOR THE FACP IS CAPABLE OF SERVING A MAXIMUM
OF 159 DETECTORS AND 159 MODULES.
20 PROVIDE A PERMANENT SIGN ON THE EXTERIOR DOOR STATING "FIRE ALARM
PANEL" FOR ALL ROOMS WITH REMOTE POWER SUPPLIES OR FACP'S. CONTRACTOR
TO PROVIDE FABRICATED NAMEPLATE SIGN. PROVIDE AND OBTAIN APPROVED
STANDARDS FROM DISTRICT. PROVIDE SUBMITTALS FOR ARCHITECTS APPROVAL.
21 PROJECT INSPECTOR SHALL VERIFY THAT THERE ARE NO ACCESSIBLE CEILING
SPACES FOR THE ROOMS IN THE SCOPE OF WORK.
22 IN THE EVENT THAT THE FIRE ALARM SYSTEM IS OFFLINE DURING SCHOOL HOURS,
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A FIRE WATCH.
23 THERE SHALL BE NO SPLICING OF FIRE ALARM CONDUCTORS BETWEEN
TERMINATIONS OF FIRE ALARM DEVICES, UNLESS SPECIFICALLY NOTED OTHERWISE.
FIRE ALARM CONDUCTORS SHALL BE CONTINUOUS FROM DEVICE TO DEVICE.
SPLICES ARE PERMITTED AT THE BUILDING FIRE ALARM TERMINAL CAN. SPLICES IN
IN-GRADE PULLBOXES ARE NOT PERMITTED, NO EXCEPTIONS.
24 INSTALLATION OF THE SYSTEMS SHALL NOT BE STARTED UNTIL DETAILED DESIGN
DOCUMENTS AND SPECIFICATION, INCLUDING STATE FIRE MARSHAL LISTING
NUMBERS FOR EACH COMPONENT OF THE SYSTEM HAS BEEN APPROVED BY DSA.
25 UPON COMPLETION OF THE INSTALLATION OF THE SYSTEMS, A SATISFACTORY TEST
OF THE ENTIRE SYSTEM SHALL BE MADE IN THE PRESENCE OF A DSA PROJECT
INSPECTOR.
26 A STAMPED SET OF APPROVED FIRE ALARM DESIGN DOCUMENTS SHALL BE ON THE
JOB SITE AND USED FOR INSTALLATION.
27 ANY DISCREPANCIES BETWEEN THE DRAWINGS AND THE CODE OR RECOGNIZED
STANDARDS SHALL BE BROUGHT TO THE ATTENTION OF DSA AND THE
ARCHITECT/ENGINEER OF THE PROJECT.
28 THE CONTRACTOR SHALL ADJUST/INSTALL ALL DEVICES TO MAXIMIZE
PERFORMANCE AND TO MINIMIZE FALSE ALARMS.
29 CONTRACTOR IS RESPONSIBLE FOR PAINTING ALL EXTERIOR CONDUITS. OBTAIN
PAINT COLOR FROM DISTRICT. CONTRACTOR TO PROVIDE AND SUPPLY EXTERIOR
PAINT TO MATCH EXISTING.
30 CONTRACTOR SHALL PROVIDE AND OBTAIN AN UNDERGROUND CONDUIT LOCATER
IN AREAS WHERE NEW TRENCH OCCURS. SEE "TRENCH NOTE RESPONSIBILITY".
ABBREVIATIONS
A
ABV
AF
AFF
ARCH
AS
AT
ATS
BKR
BLDG
C
CATV
CB
CD
CKT
CL
CLG
CO
CTR
(D)
DET
DIM
DISTR
DWG
(E)
EM
EQPT
FA
FATC
FACP
(F)
FIN
FL
G , GND
HGT
HP
IC
IDF
JB
KAIC
AMPERE
ABOVE
AMP FRAME OR AMP FUSE
ABOVE FINISHED FLOOR
ARCHITECTURAL
AMP SWITCH
AMP TRIP
AUTOMATIC TRANSFER SWITCH
BREAKER
BUILDING
CONDUIT
CABLE TELEVISION
CIRCUIT BREAKER
CANDELAS
CIRCUIT
CENTER LINE
CEILING
CONDUIT ONLY
CENTER
DEMOLISH
DETAIL
DIMENSION
DISTRIBUTION
DRAWING
EXISTING
EMERGENCY
EQUIPMENT
FIRE ALARM
FIRE ALARM TERMINAL CABINET
FIRE ALARM CONTROL PANEL
FUTURE
FINISH
FLOOR
GROUND
HEIGHT
HORSEPOWER
INTERCOM
INTERMEDIATE DISTRIBUTION FRAME
JUNCTION BOX
KILOAMPERE INTERRUPTING CAPACITY
KV
KVA
KW
LTG
MCM
MDF
MECH
MH
MTD
MTG
(N)
NAC
NC
NIC
NIEC
NO
NTS
O.C.
P
PA
PB
PF
PH
PNL
(R)
REQD
REQT
RM
RSC
SHT
SW
SWBD
TC
TEL
TYP
UON
V
W
WP
XFMR
KILOVOLT
KILOVOLT AMPERES
KILOWATT
LIGHTING
THOUSAND CIRCULAR MILS
MAIN DISTRIBUTION FRAME
MECHANICAL
MANHOLE
MOUNTED
MOUNTING
NEW
NOTIFICATION APPLIANCE CIRCUIT
NORMALLY CLOSED
NOT IN CONTRACT
NOT IN ELECTRICAL CONTRACT
NUMBER/ NORMALLY OPEN
NOT TO SCALE
ON CENTER
POLE CIRCUIT BREAKER
PUBLIC ADDRESS
PULL BOX
POWER FACTOR
PHASE
PANEL
EXISTING TO BE RELOCATED
REQUIRED
REQUIREMENT(S)
ROOM
RIGID STEEL CONDUIT
SHEET
SWITCH
SWITCHBOARD
TERMINAL CABINET
TELEPHONE
TYPICAL
UNLESS OTHERWISE NOTED
VOLT
WATT
WEATHERPROOF
TRANSFORMER
SYMBOL LIST:
1
E-1
PLAN, DETAIL OR SECTION DESIGNATION.
1
SHEET REFERENCE SYMBOL - SEE ASSOCIATED
NOTE ON SAME SHEET.
WIRING & CONDUIT RUN SYMBOLS
#10
G
CONDUIT - CONCEALED IN WALLS OR CEILING.
CONDUIT - EXPOSED.
CONDUIT - UNDERGROUND OR BELOW FLOOR
EXISTING CONDUIT, CABLES OR DEVICE
EXISTING UNDERGROUND CONDUIT
CONDUIT - HOME RUN TO PANEL, TERMINAL CABINET, ETC. RUNS MARKED WITH
CROSSHATCHES INDICATE NUMBER OF #12 AWG WIRES. CROSSHATCH WITH
SUBSCRIPT "G" INDICATES GREEN GROUND WIRE. SIZE CONDUIT ACCORDING TO
SPECIFICATIONS AND APPLICABLE CODE. CROSSHATCHES WITH "#10" INDICATES
WIRE SIZE OTHER THAN #12'S.
FLEX CONDUIT WITH CONNECTION.
CONDUIT - STUB UP.
CONDUIT - STUB DOWN.
CAPPED CONDUIT.
CONDUIT CONTINUATION.
FA EQUIPMENT DEVICE
EOL
END OF LINE RESISTOR
PROJECT DESCRIPTION:
1. OCCUPANCY: E1, SCHOOL
2. TYPE OF SYSTEM: EXISTING AUTOMATIC ADDRESSABLE NON-VOICE EVACUATION
FIRE ALARM SYSTEM. UL CERTIFIED CENTRAL STATION MONITORING.
3. SCOPE OF WORK: THE SCOPE OF WORK FOR THIS PROJECT IS TO REMOVE THE
TURNBULL FIRE ALARM SYSTEM FROM THE COLLEGE PARK FIRE ALARM SYSTEM SO
THEY CAN OPERATE INDEPENDENTLY. PROVIDE A NEW NOTIFIER MAIN FIRE ALARM
CONTROL PANEL FOR TURNBULL CAMPUS. TURNBULL AND COLLEGE PARK WILL
REMAIN CONNECTED VIA FIBER OPTIC CABLE LINK NETWORK SO THAT BOTH SITES
CAN ANNUNCIATE.
4. FIRE ALARM SYSTEM SIGNALING LINE CIRCUIT IS CLASS B; INITIATION DEVICE
CIRCUIT IS CLASS B; NOTIFICATION CIRCUIT IS CLASS B.
PRETEST OF SYSTEMS:
1. PRIOR TO THE START OF CONSTRUCTION THE EXISTING NOTIFIER "NFS2-3030"
SYSTEM SHALL BE TESTED AND ALL FAULTS AND TROUBLES ON THE SYSTEM SHALL
BE NOTED AND PROVIDED IN A REPORT TO THE OWNER.
2. REPAIR ANY EXISTING NITIFIER DEVICES NOT FUNCTIONING AT THE CONCLUSION OF
THE PROJECT AND NOT NOTED IN THE PRETEST REPORT AT NO ADDITIONAL COST
TO THE OWNER.
3. FINAL TESTING SHALL BE PER NFPA AND DSA REQUIREMENTS AND SHALL BE 100%
OF EXISTING NOTIFIER DEVICES.
CABLE SCHEDULE:
A - (1) #14 UNSHIELDED TWISTED PAIR FOR SIGNALING LINE CIRCUITS.
B - (2) #12 FOR STROBE CIRCUITS
C - (1) #12 UNSHIELDED TWISTED PAIR FOR NAC TRIGGER TO RPS
D - (1) 6-STRAND SINGLE - MODE FIBER OPTIC CABLE
E - (2) 2#12 ANNUNCIATOR POWER
DRAWING INDEX
SHEET NO.
SHEET TITLE
FA0.1
FA1.0
FA1.1
FA2.1
FA3.0
FA3.1
FA3.2
FA4.1
FIRE ALARM COVER SHEET
DEMOLITION FIRE ALARM SITE PLAN
NEW FIRE ALARM SITE PLAN
NEW FIRE ALARM FLOOR PLANS
DEMOLITION FIRE ALARM RISER DIAGRAM
NEW FIRE ALARM RISER DIAGRAM
FIRE ALARM BATTERY CALCULATIONS
FIRE ALARM DETAILS
FIRE ALARM SYSTEM OPERATIONAL MATRIX
CAUSE
SMOKE DETECTOR
HEAT DETECTOR
ATTIC HEAT DETECTOR
MANUAL PULL STATION
ALARM
TROUBLE
CO DETECTOR ALARM
SUPERVISORY MISC.
ALARMEFAFTESFCEATNCDPMAOLNAIARTCOMTRSIVINIGAGTNESAATLACAUTTTDIOIVOIBANLTEESAUDIO/VISSUEANLDSTROUBSLEENSDMIGAONLNAAIRLTOMTAROSCINITGGINIVNSAATTLTHAETTEAOAIOBUCUNDTIIILBVDLIANIENTSTEGHAVECISBTUUIVAIINLALDSTTIEHNEAGSUUBDPUIEIOSLRDE/VVINNIISSDMGUOSOARUNLYPSITAEOTRRVFIINASCGOPRSYSTAHSTUIGITOCNDNLAOOLWSSTENOMAAOSSKDSSEEOOAD..CFAADTIMCERIV-APEUACENTRTIEITSVAAUTEDIVBILSEUSALS REMARKS
AC POWER FAILURE
SIGNAL SILENCE
SYSTEM RESET
FIRE ALARM TROUBLE (OPEN,
SHORTS, OR GROUNDS) ON
INITIATION OR SIGNALING CIRCUITS
PROGRAMMING & TESTING NOTES:
1: CONTRACTOR TO RE-PROGRAM ALL EQUIPMENT, INITIATING AND NOTIFICATION
DEVICES LOCATED IN THE TURNBULL SCHOOL SIDE TO OPERATE
INDEPENDENTLY IN THE TURNBULL CAMPUS.
2: CONTRACTOR TO RE-PROGRAM ALL EQUIPMENT, INITIATING AND NOTIFICATION
DEVICES LOCATED IN THE FIESTA GARDENS SCHOOL SIDE TO OPERATE
INDEPENDENTLY IN THE FIESTA GARDENS CAMPUS.
3: CONTRACTOR TO RE-PROGRAM BOTH TURNBULL CAMPUS AND FIESTA GARDENS
CAMPUS' SYSTEM SHALL BE MONITORED BY THE EXISTING U.L. LISTED CENTRAL
MONITORING STATION AT THE SAME TIME AND SEND SIGNAL VIA EXISTING
DIALER/TRANSMITTER FROM THE EXISTING FACP AT THE FIESTA GARDENS
CAMPUS SIDE TO EXISTING U.L. LISTED CENTRAL MONITORING STATION.
4: CONTRACTOR TO FINAL TEST FIRE ALARM SYSTEM WITH ALL INITIATING AND
NOTIFICATION DEVICES FOR TURNBULL SCHOOL CAMPUS. PROVIDE TEST
REPORT TO SCHOOL DISTRICT AND ENGINEER FOR RECORD.
5: CONTRACTOR TO FINAL TEST FIRE ALARM SYSTEM WITH 10% OF INITIATING AND
NOTIFICATION DEVICES IN EACH BUILDING FOR FIESTA GARDENS SCHOOL
CAMPUS. PROVIDE TEST REPORT TO SCHOOL DISTRICT AND ENGINEER FOR
RECORD.
2
APPLICABLE FIRE ALARM
CODES, STANDARDS AND GUIDES:
CODES:
1. 2022 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1,
TITLE 24 C.C.R.
2. 2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R.
3. 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R.
4. 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R.
5. 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R.
6. 2022 CALIFORNIA ENERGY CODE.
7. 2022 CALIFORNIA FIRE CODE.
8. TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.
9. ADA STANDARDS FOR ACCESSIBLE DESIGN (APPENDIX A OF 28 CFR PART 36).
STANDARDS AND GUIDES:
1. NFPA 72, NATIONAL FIRE ALARM CODE, 2022 EDITION WITH CALIFORNIA
AMENDMENTS.
EQUIPMENT SCHEDULE:
(N) FIRE ALARM: MONITOR MODULE
M
MODEL: NOTIFIER FMM-101
CSFM: 7300-0028:219
(N) FIRE ALARM: MONITOR MODULE
C
MODEL: NOTIFIER FCM-1
CSFM: 7300-0028:219
(E) FIRE ALARM: REMOTE POWER SUPPLY
RPS
MODEL: NOTIFIER FCPS-24FS8
(E) FIRE ALARM: REMOTE ANNUNCIATOR #1
ANN#1 MODEL: NOTIFIER LCD2-80
(E) FIRE ALARM: FIRE ALARM CONTROL PANEL #1
FACP#1 MODEL: NOTIFIER NFS2-3030
ANN#2
(N) FIRE ALARM: REMOTE ANNUNCIATOR #2
MODEL: NOTIFIER NCA-2 W/ ABS-1B(C) BOX
CSFM: 7165-0028:224
FACP#2
(N) FIRE ALARM: FIRE ALARM CONTROL PANEL #2
MODEL: NOTIFIER NFS2-3030
CSFM: 7165-0028:224
FIRE ALARM: REMOTE SCREEN DISPLAY
MODEL: NOTIFIER NCA-2
CSFM: 7165-0028:224
FIRE ALARM: (N) LOOP CONTROL MODULE
MODEL: NOTIFIER LCM 320
CSFM: 7165-0028:224
2
FIRE ALARM: (N) HIGH SPEED NETWORK MODULE
MODEL: NOTIFIER HS-NCM-SF
CSFM: 7300-0028:257
2
FIRE ALARM: (N) POWER SUPPLY
MODEL: NOTIFIER AMPS-24
CSFM: 7165-0028:224
FIRE ALARM: (N) SYSTEM CABINET
MODEL: NOTIFIER EQ "D4" SERIES
CSFM: 7165-0028:224
FIRE ALARM: (N) BATTERY BOX
MODEL: NOTIFIER NFS BB
CSFM: 7165-0028:224
(N) FIRE ALARM: SYSTEM RECORD DOCUMENTS CABINET
DC
MODEL: NOTIFIER SRD
CSFM: 7300-0553:110
TRENCH NOTE RESPONSIBILITY:
THE CONTRACTOR SHALL BE RESPONSIBLE FOR SITE LOCATION ALL EXISTING
UNDERGROUND SYSTEMS IN THE AREA OF NEW TRENCHING. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR REPAIRING ALL DAMAGED SYSTEMS TO OWNERS
SATISFACTION. EXTREME CARE SHALL BE MAINTAINED DURING TRENCHING AS
EXISTING SYSTEMS ARE KNOWN TO EXIST AREA. MODIFICATION TO EXISTING
SYSTEMS MAY BE REQUIRED TO ACCOMMODATE NEW SYSTEM CONFIGURATION
AND SHALL BE MADE BY THE CONTRACTOR WITHOUT EXTRA EXPANSE TO THE
OWNER THE DRAWINGS AND SPECIFICATIONS ARE FOR THE ASSISTANCE AND
GUIDANCE OF THE CONTRACTOR. EXACT LOCATIONS, DISTANCES AND ELEVATIONS
WILL BE GOVERNED BY ACTUAL CONDITIONS. THE CONTRACTOR SHALL EXAMINE
THE CONTRACT DOCUMENTS AND FIELD CONDITIONS TO DETERMINE EXACT
ROUTING AND FINAL TERMINATIONS FOR ALL NEW WORK.
2
FA0.1
POPLAR AVENUE
DCDA
(E) F.H.
PROPERTY LINE
(E) F.H.
(E) PLAY
MATTING
(E) PLAY
MATTING
(E) PARKING LOT
DSA APPLICATION #01-111614
10
10
10
10
10
10
9
9
9
9
9
9
78
78
78
78
78
78
Xref Design 401 - Elem 1008
6
6
6
6
6
6
45
45
45
45
45
45
3
3
3
3
3
3
2
2
2
2
2
2
1
1
1
1
1
1
(E) ASPHALT
D.F.
(E) WING 4 CLASSROOMS
DSA APPLICATION #: 9553, 32028, 45667, 59212,60705
(E) PLANTING
(E) ASPHALT
2
3
(E) WING 3 CLASSROOMS
RPS
DSA APPLICATION #: 9553, 15797, 32028, 45667, 59212,60705
2
(E) PLANTING
(E) CONCRETE
(E) PLANTING
(E) CONCRETE
(E) PLANTING
(E) PLANTING
(E) CONCRETE
(E) TURF
D.F.
(E) BLDG 7
DSA APPLICATION
#01-111614
2
4
(N) F.H.
YD
21 3
RPS
4
2
19 20
18
1
2
3
(E) BLDG 8A
DSA APPLICATION
#01-111614
(E) BLDG 8B
DSA APPLICATION
#01-111614
1
1
21
4
(E) ASPHALT
1
RPS
S
S
(E) PLANTING
(E) PLANTING
S
2
(E) CONCRETE
Xref Design 40EZ Kinder 2413
33
10
9
78
6
45
3
2
1
10
9
78
6
45
3
2
1
10
9
78
6
45
3
2
1
4
2 12
T
(E) ASPHALT
2
(E) WING 2 CLASSROOMS
& LIBRARY
DSA APPLICATION #: 7687, 15797, 32028, 45667, 59212, 60705
1
(E) CONCRETE
(E) PLANTING
(E) PLANTING
(E) LUNCH
2 SHELTER
DSA APPLICATION
#01-111614
2
(E) BLDG 6
5
DSA APPLICATION
#01-111614
S
1
1
TURNBULL LEARNING
CENTER PRESCHOOL
19 20 1 2 3
N.I.C.
(E) BLDG 9
(E) PNL "9A"
D.F.
(E) CONCRETE
3
RPS
DSA APPLICATION
#01-111614
$AUDIT_BAD_BLOCK
(E) PLANTING
(E) PLANTING
(E)A,B 2
(E) ASPHALT
3
4
7
FACP#1
(E) WING 1 CLASSROOMS & ADMIN.RPS
DSA APPLICATION #: 7687, 32028, 45667, 60705 4
3
(TYP.) 2
(E) PLANTING
(E) BLDG 5
DSA APPLICATION
1 (TYP.) #: 9553, 32028
1
(E) CONCRETE
(E) PARKING LOT
DSA APPLICATION #01-111614
7
11.3
12.3
(E)A,B 2 1 3
(E) PARKING LOT
DSA APPLICATION #01-111614
(E) PLANTING
(E) PLANTING
Xref TURNBULL ship 200059803
(E) BLDG 10
6
DSA APPLICATION
#01-111614
4
G
(E) F.H.
1 DEMOLITION FIRE ALARM SITE PLAN
E1.0 SCALE: 1" = 30'-0"
INDIAN AVENUE
(E) F.H.
(E) F.H.
GENERAL NOTES:
1. ALL EXISTING UNDERGROUND CONDUITS AND ROUTING SHOWN ARE BASED
ON THE AS-BUILT UNDER THE DSA APPLICATION #01-111614. CONTRACTOR
TO SITE VERIFY EXISTING FIRE ALARM ROUTING CONDITIONS AS REQUIRED.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY SAW CUTTING AND
REMOVAL OF EXISTING SURFACES TO FACILITATE UNDERGROUND SYSTEMS.
THE CONTRACTOR SHALL PATCH AND REPAIR ALL DAMAGED AND CUT
SURFACES TO MATCH ADJACENT.
3. CONTRACTOR TO SITE SURVEY EXISTING CONDITIONS AND LOCATIONS OF
EXISTING UNDERGROUND SYSTEMS, WHERE NEW TRENCH WORK OCCURS
PRIOR TO BIDDING. CONTRACTOR SHALL TAKE PROPER PRECAUTIONS TO
ENSURE EXISTING UNDERGROUND SYSTEMS/CONDUIT/PIPES ARE NOT
DAMAGED DURING INSTALLATION. CONTRACTOR IS RESPONSIBLE FOR ANY
REPAIRS REQUIRED IN THE EVENT THE EXISTING UNDERGROUND SYSTEMS
ARE DAMAGED AS A RESULT OF THE NEW ELECTRICAL TRENCH WORK.
4. SEE FIRE ALARM DEMOLITION RISER DIAGRAM FOR MORE INFORMATION.
5. ALL EXISTING FIRE ALARM DEVICES AND CABLES REMAINING FOR REUSE
ARE TO BE TESTED FOR COMPLIANCE/SATISFACTION PRIOR TO NEW WORK.
PROVIDE TEST REPORT OF THE FIRE ALARM SYSTEM'S EXISTING STATUS TO
DISTRICT/ARCHITECT/ENGINEER. ALL EXISTING CABLES, CONNECTIONS, AND
DEVICES THAT GIVE TROUBLE, ERROR, OR SUPERVISORY NOTIFICATIONS
SHALL BE NOTED. ANY EXISTING CABLES AND DEVICES THAT ARE NOT
OPERATIONAL AND/OR DAMAGED AFTER DEMOLITION THAT ARE NOT NOTED
ON THE REPORT SHALL BE REPLACED AT NO ADDITIONAL COST.
6. ALL EXISTING IN-GRADE PULL BOXES AND UNDERGROUND SHOWN ON THE
PLAN ARE TO REMAIN FOR RE-USE UNLESS OTHERWISE NOTED.
DEMOLITION SHEET NOTES:
1 DISCONNECT AND PULL EXISTING SLC FROM THE FIRST
EXISTING INITIATING DEVICE IN THE BUILDING BACK TO
EXISTING FACP AND REMOVE. EXISTING INITIATING
DEVICES ARE PROTECTED AND READY FOR
RE-CONNECT. SEE FIRE ALARM NEW SITE PLAN FOR
ADDITIONAL REQUIREMENTS.
2 DISCONNECT AND PULL EXISTING NAC FROM THE
EXISTING REMOTE POWER SUPPLY IN THE BUILDING
BACK TO EXISTING RPS#7 AND REMOVE. EXISTING RPS TO
REMAIN AND READY FOR RE-CONNECTING. SEE FIRE
ALARM NEW SITE PLAN FOR ADDITIONAL REQUIREMENTS.
3 PULL EXISTING NACs FROM EXISTING RPS#8, RPS#9 AND
RPS#10 IN DAISY CHAIN CONNECTED BACK TO RPS#7 AND
REMOVE. PROVIDE EOL AT THE EXISTING RPS#7 AND
RE-PROGRAM AS REQUIRED. SEE DEMO FIRE ALARM
RISER DIAGRAM FOR ADDITIONAL REQUIREMENTS.
SHEET NOTES:
1 EXISTING SIGNAL IN-GRADE PULL BOX TO REMAIN.
2 EXISTING SIGNAL PULL CAN TO REMAIN.
2
3 EXISTING NOTIFIER NFS2-3030 MAIN FIRE ALARM
CONTROL PANEL LOCATED IN THE CLASSROOM/ADMIN.
BUILDING TO REMAIN.
4 EXISTING NOTIFIER REMOTE POWER SUPPLY TO REMAIN.
5 EXISTING NOTIFIER REMOTE ANNUNCIATOR - LCD2-80
LOCATED IN THE BUILDING 6 TO REMAIN AND STAY
CONNECTED.
6 EXISTING NOTIFIER MANUAL PULL STATION LOCATED IN
THE ADMIN. OFFICE TO REMAIN.
CONDUIT SCHEDULE:
1 (E) (2) 2"C - FIRE ALARM
2 (E) (1) 2"C - FIRE ALARM
3 EXISTING FIRE ALARM CONDUIT
CABLE SCHEDULE:
A - (1) #14 UNSHIELDED TWISTED PAIR FOR SIGNALING LINE CIRCUITS.
B - (2) #12 FOR STROBE CIRCUITS
C - (1) #12 UNSHIELDED TWISTED PAIR FOR NAC TRIGGER TO RPS
D - (1) 6-STRAND SINGLE - MODE FIBER OPTIC CABLE
E - (2) #12 ANNUNCIATOR POWER
Pile
Pile
2
(E) F.H.
(E) F.H.
N
FA1.0
POPLAR AVENUE
DCDA
(E) F.H.
PROPERTY LINE
(E) F.H.
(E) PLAY
MATTING
(E) PLAY
MATTING
(E) PARKING LOT
DSA APPLICATION #01-111614
(E) WING 4 CLASSROOMS
DSA APPLICATION #: 9553, 32028, 45667, 59212,60705
10
10
10
10
10
10
9
9
9
9
9
9
78
78
78
78
78
78
Xref Design 401 - Elem 1008
6
6
6
6
6
6
45
45
45
45
45
45
3
3
3
3
3
3
2
2
2
2
2
2
1
1
1
1
1
1
D.F.
(E) PLANTING
(E) PLANTING
(E) ASPHALT
(E) WING 3 CLASSROOMS
RPS
DSA APPLICATION #: 9553, 15797, 32028, 45667, 59212,60705
(E) CONCRETE
(E) PLANTING
(E) CONCRETE
(E) ASPHALT
(E) PLANTING
(E) PLANTING
(E) CONCRETE
(E) TURF
D.F.
(E) BLDG 7
DSA APPLICATION
#01-111614
1
(N) F.H.
HY D
(N)A,B 3
2
(N)A 1
19 20 1 2 3
(E) PLANTING
(E) ASPHALT
(E) ASPHALT
(E) CONCRETE
(E) PLANTING
1 (N)D
(E) PLANTING
(E) CONCRETE
(E) PLANTING
S
1
RPS
Xref Design 40EZ Kinder 2413
S
S
10
9
78
6
45
3
2
1
10
9
78
6
45
3
2
1
10
9
78
6
45
3
2
1
T
(E) WING 2 CLASSROOMS
& LIBRARY
(E) LUNCH
SHELTER
1 (N)D DSA APPLICATION
(E) BLDG 6
DSA APPLICATION
#01-111614
1 (N)D
1 (N)D
DSA APPLICATION #: 7687, 15797, 32028, 45667, 59212, 60705
#01-111614
D.F.
$AUDIT_BAD_BLOCK
(E) CONCRETE
RPS
(E) PLANTING
(E) PLANTING
(E) ASPHALT
FACP#1
(E) WING 1 CLASSROOMS & ADMIN.RPS
DSA APPLICATION #: 7687, 32028, 45667, 60705
(N)D 1
(E) PLANTING
1 (N)D
(E) CONCRETE
(E) BLDG 5
DSA APPLICATION
#: 9553, 32028
(E) PARKING LOT
DSA APPLICATION #01-111614
(E) PARKING LOT
DSA APPLICATION #01-111614
(E) PLANTING
(E) PLANTING
G
1 NEW FIRE ALARM SITE PLAN
FA1.1 SCALE: 1" = 30'-0"
(E) F.H.
INDIAN AVENUE
(E) F.H.
RPS
1 (E) BLDG 8A
FA2.1
DSA APPLICATION
#01-111614
2
1 (N)A,D
(E) BLDG 8B
DSA APPLICATION
#01-111614
2
1 (N)2A,2D,E
S
TURNBULL LEARNING
CENTER PRESCHOOL
19 20 1 2
18
N.I.C.
(E) BLDG 9
DSA APPLICATION
#01-111614
2
(N)A,D,E 1
7
7
11.3
12.3
2
1 (N)2A,2D,E
2
FA2.1
134
(E) PNL "9A"
2
2 4 (N)A,D,E 3
Xref TURNBULL ship 200059803
ANN#2
(E) BLDG 10
DSA APPLICATION
#01-111614
3
FA2.1
(E) F.H.
GENERAL NOTES:
1. ALL EXISTING UNDERGROUND CONDUITS AND ROUTING SHOWN ARE BASED
ON THE AS-BUILT UNDER THE DSA APPLICATION #01-111614. CONTRACTOR
TO SITE VERIFY EXISTING FIRE ALARM ROUTING CONDITIONS AS REQUIRED.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY SAW CUTTING AND
REMOVAL OF EXISTING SURFACES TO FACILITATE UNDERGROUND SYSTEMS.
THE CONTRACTOR SHALL PATCH AND REPAIR ALL DAMAGED AND CUT
SURFACES TO MATCH ADJACENT.
3. CONTRACTOR TO SITE SURVEY EXISTING CONDITIONS AND LOCATIONS OF
EXISTING UNDERGROUND SYSTEMS, WHERE NEW TRENCH WORK OCCURS
PRIOR TO BIDDING. CONTRACTOR SHALL TAKE PROPER PRECAUTIONS TO
ENSURE EXISTING UNDERGROUND SYSTEMS/CONDUIT/PIPES ARE NOT
DAMAGED DURING INSTALLATION. CONTRACTOR IS RESPONSIBLE FOR ANY
REPAIRS REQUIRED IN THE EVENT THE EXISTING UNDERGROUND SYSTEMS
ARE DAMAGED AS A RESULT OF THE NEW ELECTRICAL TRENCH WORK.
4. SEE FIRE ALARM DEMOLITION RISER DIAGRAM FOR MORE INFORMATION.
5. ALL EXISTING FIRE ALARM DEVICES AND CABLES REMAINING FOR REUSE
ARE TO BE TESTED FOR COMPLIANCE/SATISFACTION PRIOR TO NEW WORK.
PROVIDE TEST REPORT OF THE FIRE ALARM SYSTEM'S EXISTING STATUS TO
DISTRICT/ARCHITECT/ENGINEER. ALL EXISTING CABLES, CONNECTIONS, AND
DEVICES THAT GIVE TROUBLE, ERROR, OR SUPERVISORY NOTIFICATIONS
SHALL BE NOTED. ANY EXISTING CABLES AND DEVICES THAT ARE NOT
OPERATIONAL AND/OR DAMAGED AFTER DEMOLITION THAT ARE NOT NOTED
ON THE REPORT SHALL BE REPLACED AT NO ADDITIONAL COST.
6. ALL EXISTING IN-GRADE PULL BOXES AND UNDERGROUND SHOWN ON THE
PLAN ARE TO REMAIN FOR RE-USE UNLESS OTHERWISE NOTED.
SHEET NOTES:
1 PROVIDE NEW NOTIFIER NFS-3030 MAIN FIRE ALARM
CONTROL PANEL AND DOCUMENT CABINET IN
ELECTRICAL ROOM #902 WITH EXISTING RPS IN THE
EXISTING BUILDING 9 TO RE-CONNECT ALL EXISTING
FIRE ALARM DEVICE IN TURNBULL CAMPUS. SEE FIRE
ALARM RISER DIAGRAM FOR ADDITIONAL
REQUIREMENTS.
2 PROVIDE NEW NCA-2 REMOTE ANNUNCIATOR ON THE
WALL BY THE ENTRANCE DOOR IN THE RECEPTION
AREA IN THE ADMIN. OFFICE. CONTRACTOR TO REMOVE
EXISTING FIRE EXTINGUISHER AND BULLETIN BOARD ON
THE WALL TO INSTALL NEW EQUIPMENT. RE-INSTALL
EXISTING FIRE EXTINGUISHER AND BULLETIN BOARD AS
REQUIRED. COORDINATE INSTALL LOCATION WITH
DISTRICT. CONTRACTOR TO PROVIDE ALL NECESSARY
MATERIALS TO CONNECT NEW FACP TO NEW
ANNUNCIATOR.
3 PROVIDE NEW SLCs AND NACs TO RE-CONNECT THE
EXISTING DEVICES IN BUILDING 8, 8a, 9 AND 10. SEE NEW FIRE
ALARM RISER DIAGRAM FOR ADDITIONAL REQUIREMENTS.
4 CONTRACTOR TO POST RESETTING PROCEDURES NEAR
EACH FACP AND ANNUNCIATOR AS REQUIRED. PROCEDURE
TO STATE " PRESS THE RESET BUTTON ON THE MASTER
PANEL. THE RESET WILL PROPAGATE TO THE SECOND PANEL.
IF THE SECOND PANEL IS NOT RESET, MANUALLY RESET THE
SECOND PANEL BY PRESSING ITS RESET BUTTON".
CONTRACTOR TO CONFIRM RESET PROCEDURE.
CONDUIT SCHEDULE:
1 (E) (1) 2"C - FIRE ALARM
2 NOT USED.
3 EXISTING FIRE ALARM CONDUIT
MAX % CONDUIT FILL ALLOWED: 40%
ACTUAL % CONDUIT FILL: 8.89%
ACTUAL % CONDUIT FILL IS BASED ON THE 2" CONDUIT WITH THE LARGEST
QUANTITY OF CABLES ON THIS PLAN. THIS IS THE MAXIMUM VALUE.
CABLE SCHEDULE:
A - (1) #14 UNSHIELDED TWISTED PAIR FOR SIGNALING LINE CIRCUITS.
B - (2) #12 FOR STROBE CIRCUITS
C - (1) #12 UNSHIELDED TWISTED PAIR FOR NAC TRIGGER TO RPS
D - (1) 6-STRAND SINGLE - MODE FIBER OPTIC CABLE
E - (2) #12 ANNUNCIATOR POWER
Pile
Pile
2
(E) F.H.
(E) F.H.
N
FA1.1