5950--NRM-CONST 528A5-24-516 - Replace 5MV Transformer
| Location: |
Federal |
| Posted: |
Jul 11, 2025 |
| Due: |
Jul 23, 2025 |
| Agency: |
VETERANS AFFAIRS, DEPARTMENT OF |
| Type of Government: |
Federal |
| Category: |
- 59 - Electrical and Electronic Equipment Components
|
| Solicitation No: |
36C24225B0028 |
| Publication URL: |
To access bid details, please log in. |
5950--NRM-CONST 528A5-24-516 - Replace 5MV Transformer
Active
Contract Opportunity
Department/Ind. Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-tier
VETERANS AFFAIRS, DEPARTMENT OF
Office
242-NETWORK CONTRACT OFFICE 02 (36C242)
Looking for contract opportunity help?
General Information View Changes
-
Contract Opportunity Type: Solicitation (Updated)
-
Updated Published Date: Jul 11, 2025 09:48 am EDT
-
Original Published Date: Jun 18, 2025 12:40 pm EDT
-
Updated Date Offers Due: Jul 23, 2025 12:30 pm EDT
-
Original Date Offers Due: Jul 16, 2025 12:30 pm EDT
-
Inactive Policy: Manual
-
Updated Inactive Date: Aug 22, 2025
-
Original Inactive Date:
Sep 14, 2025
-
Initiative:
Classification
-
Original Set Aside:
-
-
Product Service Code: 5950 - COILS AND TRANSFORMERS
-
NAICS Code:
-
238210 - Electrical Contractors and Other Wiring Installation Contractors
-
Place of Performance:
Description View Changes
Does the acceptance testing of the new transformer need to be completed by NETA certified technicians?
Yes
Is the transformer to be replaced currently de-energized and only being used for backup?
The transformer is currently out of service pending repairs scheduled to be completed during Summer 2025. The bidding contractors shall assume the transformer will need to be de-energized prior to work start.
Is there a preferred day of the week and time of day for the transformer replacement?
There is no preference, coordination with facilities will be required to minimize impact.
What is the maximum duration for the redundant transformer to be unavailable during replacement?
1 week maximum.
Please provide specific details on how the existing transformer being replaced will be turned over. (set to the side of the yard or transported to a designated location?)
The transformer can be set to the side within the secure fence in a location to not impede access to other equipment.
Does the facility have one-line drawings, as-builts, or design drawings of any kind for the current primary switchgear, transformer, and secondary switchgear?
Refer to Attachment B _ ES107 _ Electrical Site Plan This attachment is from the original design at time of award. Actual installation of the transformer may vary slightly.
Does the facility know the correct lockout locations to isolate the transformer being replaced?
Lockout locations are in the adjacent switchgear within the secure fence area.
Please confirm no testing or new terminations are required for the existing MV cables.
Testing of new terminations is not required as the existing terminations are to be re-used. Testing may be required if the existing terminations are damaged during construction and need to be replaced.
Do you have pictures of the Medium Voltage and Low Voltage connection compartments. Just would like to see the conduit arrangement and the connections.
Refer to Attachment A _ Pictures
Are transformers in the basis of design memo what was originally purchased?Â
Yes
Is the VA looking for a direct replacement of the failed one?
Yes. Approved equal would be considered.
Is the VA looking for a direct replacement of the failed one?
Yes. Approved equal would be considered.
If Yes then in the specifications that were sent out the installation instructions 3.1.A, B, C, D.1,.2, .3 would have already been done by the initial installer of the transformer
Concrete pad, anchors, and grounding rods are all existing. The new transformer shall be mounted to the existing concrete pad using existing anchors to secure the unit. Contractor is responsible for any additional anchors that may be required to for proper installation.
3.4 - Spare parts are they required as part of this bid?
Yes
3.5 - Instruction - is this still required?
Not Needed
Q13. A previous notice described a transformer in Bath, NY as well? Is this a part of this project?
The Bath transformer was able to be replaced in-house and is not a part of this project.
Attachments/Links
Contact Information
Contracting Office Address
-
113 HOLLAND AVE
-
ALBANY , NY 12208
-
USA
Secondary Point of Contact
History
Daily notification on new contract opportunities
With GovernmentContracts, you can:
- Find more opportunities and win more business
- Receive daily alerts for all new bid opportunities
- Get contract opportunities matched to your business
ONE WEEK FREE TRIAL
See also
Follow Y--VOYA 335009 N191 REHAB RAINY AND ASH Active Contract Opportunity Notice ID
INTERIOR, DEPARTMENT OF THE
Bid Due: 6/09/2026
Follow 20--CYLINDER,DUPLEX Active Contract Opportunity Notice ID N0010426QYA76 Related Notice Department/Ind. Agency DEPT
DEPT OF DEFENSE
Bid Due: 7/31/2026
Follow F--Snake River Area Office Weed Control Active Contract Opportunity Notice ID 140R1726Q0025
INTERIOR, DEPARTMENT OF THE
Bid Due: 6/12/2026
Follow Z1DA--646-21-101 UD SPS AHU & RO Upgrade (VA-26-00036217) Active Contract Opportunity Notice
VETERANS AFFAIRS, DEPARTMENT OF
Bid Due: 6/11/2026
* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.