UPS Maintenance

Location: Washington
Posted: Apr 13, 2026
Due: Apr 14, 2026
Agency: DEPT OF DEFENSE
Type of Government: Federal
Category:
  • J - Maintenance, Repair, and Rebuilding of Equipment
Solicitation No: N6471026Q0007
Publication URL: To access bid details, please log in.
Follow
UPS Maintenance
Active
Contract Opportunity
Notice ID
N6471026Q0007
Related Notice
Department/Ind. Agency
DEPT OF DEFENSE
Sub-tier
DEPT OF THE NAVY
Major Command
SSP
Office
STRATEGIC WEAPONS FAC PAC FINANCIAL
Looking for contract opportunity help?

APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.

APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.

The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).

General Information View Changes
  • Contract Opportunity Type: Solicitation (Updated)
  • Updated Published Date: Apr 13, 2026 02:28 pm PDT
  • Original Published Date: Apr 06, 2026 01:38 pm PDT
  • Updated Date Offers Due: Apr 14, 2026 05:00 pm PDT
  • Original Date Offers Due: Apr 13, 2026 05:00 pm PDT
  • Inactive Policy: 15 days after date offers due
  • Updated Inactive Date: Apr 29, 2026
  • Original Inactive Date: Apr 28, 2026
  • Initiative:
    • None
Classification
  • Original Set Aside: Total Small Business Set-Aside (FAR 19.5)
  • Product Service Code: J061 - MAINT/REPAIR/REBUILD OF EQUIPMENT- ELECTRIC WIRE AND POWER DISTRIBUTION EQUIPMENT
  • NAICS Code:
    • 811210 - Electronic and Precision Equipment Repair and Maintenance
  • Place of Performance:
    Silverdale , WA 98315
    USA
Description

Statement Of Work



UPS Maintenance and Repair








  1. BACKGROUND



Strategic Weapons Facility Pacific (SWFPAC) requires comprehensive maintenance and repair service contract for three (3) Uninterruptible Power Supply (UPS) units located at SWFPAC facilities on Naval Base Kitsap-Bangor in Silverdale, WA.





The purpose of this contract is to ensure the reliable operation of critical power infrastructure through proactive maintenance and timely emergency support.





2. Equipment Covered:





Make



Model



Description



Serial Number



APC



SYCF40KF



Symmetra PX UPS 20kVA 40 and/or PDU



QD1633340704



APC



SYCF40KF



Symmetra PX UPS 40kVA 40 and/or PDU



QD1830240733



APC



SYCF40KF



Symmetra PX UPS 40kVA 40 and/or PDU



QD1830240729






  1. SCOPE:



The contractor shall provide all-inclusive preventative maintenance, on-site emergency repair, and remote technical support for the UPS equipment listed in paragraph 2. To ensure the manufacturer's warranty remains valid, services must be delivered by an American Power Conversion (APC)-certified or authorized service provider. All components, parts, and consumables used for maintenance or repair must be new, genuine original equipment manufacturer parts that meet APC specifications.





3.1. Technical Support



The contractor shall provide 24 hours a day, 7 days a week, 365 days a year (24/7/365) telephone and email access to a technical support center for troubleshooting and service dispatch.





3.2. On-Site Support



Emergency On-Site Response: For any critical failure resulting in a loss of redundancy or an inability to support the protected load, a qualified technician must arrive on-site within six (6) hours of the service request being logged. This six (6) hour response shall be guaranteed 24/7/365.





Standard On-Site Response: For non-critical failures where the UPS remains operational, a qualified technician must arrive on-site no later than the next business day.





Parts & Labor: This contract shall cover 100% of the costs for all replacement parts, hardware, capacitors, fans, and any other components needed to restore the UPS units listed in paragraph 2 to full operational status. All associated labor, travel, and expenses for on-site visits shall be included.





Equivalent Hardware: If a failed hardware component is no longer manufactured, it shall be replaced with an equivalent or superior component that is fully compatible.





3.3. Preventative Maintenance (PM)



The contractor shall perform one (1) scheduled on-site preventative maintenance visit during the contract period. This visit shall include all UPS units listed in paragraph 2.



The PM service must include, at a minimum, the following tasks for each UPS:




  • Visual Inspection: Check for loose connections, overheating, component discoloration, and physical defects.

  • Environmental Checks: Measure and record ambient temperature and humidity.

  • Cleaning: Clean and remove dust/debris from the interior and exterior of the UPS.

  • Electrical Checks: Perform thermal scans on electrical connections to identify potential failure points. Check and tighten all terminal connections as needed.

  • Battery Maintenance: Conduct a full battery string inspection, including voltage checks, impedance testing, and a system load test to verify battery performance and runtime.

  • System Calibration: Calibrate and verify all system alarms, setpoints, and transfer mechanisms.

  • Firmware & Software: Review installed firmware and operating system software. Install any necessary updates, patches, or security fixes after receiving approval from SWFPAC personnel.

  • Functional Test: Perform a full functional test to ensure the unit operates correctly in all modes (e.g., normal, battery, bypass).





4. DELIVERABLES



The following deliverables are required:



Field Service Report: After each preventative maintenance visit or emergency repair, the contractor shall provide a detailed electronic service report within five (5) business days. This report must document all work performed, tests conducted, parts replaced, and findings or recommendations.



Annual System Health Report: At the conclusion of the contract period, the contractor shall provide a summary report detailing the overall health of the UPS fleet, a summary of service activities for the year, and recommendations for future maintenance or upgrades.





5. CONTRACTOR & PERSONNEL REQUIREMENTS



Certification: All on-site technicians must be certified by APC to work on the specified UPS models. Proof of certification may be requested.



Security & Access: The contractor and its personnel must comply with all SWFPAC security protocols, including requirements for background checks, site access, and safety procedures. The contractor will be escorted at all times unless prior arrangements are made.



Base Access: Contractors must be able to gain access to SWFPAC on Naval Base Kitsap – Bangor,



WA. Base access may be granted using the Rapid Gate System, DBIDS System, or other approved base



access system at the Contractor’s expense. Once base access is granted, Contractors will be required to



apply for a visitor badge (BAVR request) at https://www.bavr.cnic.navy.mil/. Coordination of the visitor



badge will be through the Government Point of Contract.





Vehicle Pass: In order to drive a non-Government vehicle to the work location, the contractor must



submit a SWFPAC Vehicle Pass Request and required documents to the COR. The non-Government



vehicle must be registered in the company’s name and must have a clear logo displayed on the vehicle



indicating the company it is registered to. When entering the base, the vehicle must have the approved



vehicle pass displayed in the driver’s side windshield at all times. No Bluetooth, telephonic, or electronic



devices are allowed in secured locations on base.




Attachments/Links
Contact Information
Contracting Office Address
  • RECEIVING OFFICER 6401 SKIPJACK CIRCLE
  • SILVERDALE , WA 98315-6499
  • USA
Primary Point of Contact
Secondary Point of Contact
History

Related Document

Apr 6, 2026[Presolicitation (Original)] UPS Maintenance
Apr 6, 2026[Solicitation (Original)] UPS Maintenance
Daily notification on new contract opportunities

With GovernmentContracts, you can:

  • Find more opportunities and win more business
  • Receive daily alerts for all new bid opportunities
  • Get contract opportunities matched to your business
ONE WEEK FREE TRIAL

See also

Follow 100kW EDG Rental Active Contract Opportunity Notice ID N4523A26Q5705 Related Notice N4523A26Q5705

DEPT OF DEFENSE

Bid Due: 6/05/2026

Follow Z2DA--Flooring Renovation, Installation, and Repalcement Services SATOC/IDIQ Active Contract Opportunity Notice ID

VETERANS AFFAIRS, DEPARTMENT OF

Bid Due: 6/04/2026

Solicitation Close Date: 06/09/26 Title: DOC - WCCW - Replace Roofs Bldgs C,

State Government of Washington

Bid Due: 6/09/2026

Solicitation Close Date: 06/03/26 Title: HC - Campus Landscaping Improvements Ref #:2026-739 G(1-1)

State Government of Washington

Bid Due: 6/03/2026

* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.