Control System Replacement for Stamford Hurricane Barrier, Stamford, CT

Location: Connecticut
Posted: Sep 17, 2026
Due: Oct 2, 2026
Agency: DEPT OF DEFENSE
Type of Government: Federal
Category:
  • 63 - Alarm, Signal, and Detection Systems
  • R - Professional, Administrative and Management Support Services
Publication URL: To access bid details, please log in.
Follow
Control System Replacement for Stamford Hurricane Barrier, Stamford, CT
Active
Contract Opportunity
Notice ID
Related Notice
W912WJ27X1C6U
Department/Ind. Agency
DEPT OF DEFENSE
Sub-tier
DEPT OF THE ARMY
Major Command
US ARMY CORPS OF ENGINEERS
Sub Command
ENGINEER DIVISION NORTH ATLANTIC
Sub Command 2
ENDIST NEW ENGLAND
Office
W2SD ENDIST NEW ENGLAND
General Information
  • Contract Opportunity Type: Special Notice (Original)
  • Original Published Date: Sep 17, 2026 11:19 am EDT
  • Original Response Date: Oct 02, 2026 01:00 pm EDT
  • Inactive Policy: 15 days after response date
  • Original Inactive Date: Oct 17, 2026
  • Initiative:
    • None
Classification
  • Original Set Aside:
  • Product Service Code:
  • NAICS Code:
    • 238210 - Electrical Contractors and Other Wiring Installation Contractors
  • Place of Performance:
    Stamford , CT
    USA
Description

Notice of Intent for Stamford Hurricane Barrier – Control Systems Replacement – Mechanical & Hydraulic Components





Under the authority of RFO 6.103-1, the U.S. Army Corps of Engineers (USACE), New England District (NAE) intends to require, on a brand-name basis, the purchase and installation of highly specialized hydraulic and electronic components for the upcoming Stamford Hurricane Barrier Control System Replacement project in Stamford, Connecticut.





The Stamford Hurricane Barrier is a critical life-safety public infrastructure asset providing immediate tidal flood and storm surge protection to the City of Stamford and surrounding communities. The brand-name components specified herein are manufactured by:






  1. Bosch Rexroth

  2. HYDAC

  3. Des-Case

  4. Honeywell (Sensotec)

  5. Dwyer Omega

  6. Lisle Corporation





These components are required for the rehabilitation, modernization, and control integration of the existing main Hydraulic Power Units (HPUs) and hydraulic manifold assemblies.





The use of these brand-name components is essential to meet the Government’s strict safety, compatibility, and performance requirements for the following reasons:






  1. The project requires direct integration with the existing HPU structures and manifolds, which were originally designed and manufactured by Rexroth. The new components must be fully compatible with the existing proprietary hydraulic flow paths, mechanical port configurations, and pressure curves.

  2. The barrier's two massive gate cylinders must operate in perfect synchronization to prevent twisting, binding, and potential catastrophic mechanical failure. The specified Bosch Rexroth proportional and counterbalance valves possess proprietary flow-gain curves and spool alignments that are essential to ensure this synchronized movement. Using any other manufacturer's valves would introduce a mismatch, inducing severe structural stress on the barrier.

  3. The existing manifolds are machined with proprietary Rexroth cavity and mounting standards. Generic commercial valves and filters will not seat properly without custom adapters, which would introduce leak paths and degrade system reliability. The specified components ensure a precise physical fit within the existing infrastructure.









Schedule of Intended Brand-Name Components





To afford industry full visibility to review and provide feedback, the intended schedule of brand-name components is itemized below by contract drawing schedules:






  1. HPU Replacement Parts



Quantities reflect the complete project scope across both East and West Abutment HPUs (2 HPUs total).



Tech Pos



Description / Function



Manufacturer



Specified Model / Part Number



Qty / HPU



Total Project Qty



12



3/4" Square-Head Magnetic Trap Plug



Lisle Corporation



Part No. 4054121



2



4



20



Float Level Switch Assembly



Bosch Rexroth



Model 800PUA31-05 3 SW (Part No. R978835263)



2



4



25



Reservoir Filler Connection / Cap



Bosch Rexroth



Model F/ELF5-10-2.0 PUA42-11 (Part No. 97884631)



2



4



30



Desiccant Breather & Mounting Adapter



Des-Case



Breather DC/CS-4 & Adapter DC-12 (Part Nos. R978839894 / R978840030)



2



4



35



Temperature Switch



Bosch Rexroth



Model TEMP SW PUA31-30B E55-14103 (Part No. 97888127)



2



4



40



Bulbwell Steel (11.44" Long)



Bosch Rexroth



Model BULBWELL 11.44 LG PUA31-22 (Part No. R978802575)



2



4



43



Temperature Transducer (RTD)



Dwyer Omega



Model PR-12-2-100-1/4-12-E



2



4



44



Bulbwell for Temperature Transducer



Dwyer Omega



Model 3/4-260S-U10



2



4



45



Bimetal Thermometer



Bosch Rexroth



Model BIMET PUA31-14 WIKA 33X0278 (Part No. 978804856)



2



4



50



Bulbwell Steel (5.25" Long)



Bosch Rexroth



Model BULBWELL 5.25 LG PUA31-22 (Part No. 978804619)



2



4



75



High-Pressure Filter Assembly



HYDAC



Model DF BH/HC 330 T F 10 D 1.0 /-L110-B6 (Part No. 1250576)



2



4



77



Return Line Filter Assembly



HYDAC



Model RF BN/HC 30 B B 10 D 1.0 /-L110 (Part No. 1266488)



2



4



80



3/4" Check Valve (0.5 bar cracking)



Bosch Rexroth



Model S15A05-1X/420/12



4



8



85



1-1/2" Check Valve (0.5 bar cracking)



Bosch Rexroth



Model S30A05-1X/420/12 (Part No. R901454196)



4



8



93



Low-Pressure Gauge Assembly



Bosch Rexroth



Model GSA 4/400PUA31-10A (Part No. 978837831)



2



4



95



High-Pressure Gauge Assembly



Bosch Rexroth



Model GSA 4/3000PUA31-10A (Part No. 978837833)



2



4



110



Direct-Operated Relief Valve



Bosch Rexroth



Model DBDS15G1X/50-12 (Part No. 900534613)



2



4



120



Pilot-Operated Relief Valve



Bosch Rexroth



Model DBW15BG2-5X/315-6EW110N9K4/12 (Part No. 978917231)



2



4








  1. Manifold Wearable Components



Quantities reflect the complete project schedule for the dual-cylinder manifold assemblies.



Item / Tech Pos



Description / Function



Manufacturer



Specified Model / Part Number



Manifold Schedule Qty



201.1



High-Pressure Transducer (0–2000 psi)



Honeywell (Sensotec)



Model Sensotec AP415DL (Part No. 60-F499-01)



6



203.1



Low-Pressure Transducer (0–500 psi)



Honeywell (Sensotec)



Model Sensotec AP415CR (Part No. 60-F441-01)



2



219



Directional Valve



Bosch Rexroth



Model 4WE6D5X/AW120-60NDA/5 (Proportional directional valve w/ OBE)



2



220



Proportional Directional Valve



Bosch Rexroth



Model 4WRZ16-15005X/6A24N9TD3/M-116 (Proportional directional valve w/ OBE)



2



223



Pressure Compensator



Bosch Rexroth



Model ZDC16P-2X/M (Part No. R900489668)



2



225



Counterbalance Valve



Bosch Rexroth



Model FD25KA2X/B04/12 (Part No. R900518087)



2



Salient Characteristics and Technical Rationales



The use of the specified brand-name components is essential to meet the Government’s strict life-safety, mechanical synchronization, fluid cleanliness, and physical compatibility requirements.






  1. Bosch Rexroth (Hydraulic Valves, Controls, and Switches):

    • The existing HPUs and distribution manifold blocks were originally engineered and machined to proprietary Rexroth cavity and porting standards. Replacement valves must drop directly into existing cavities without adapter plates, which introduce leak paths and structural compliance issues.

    • The barrier gate is actuated by two massive hydraulic cylinders on opposite sides of the navigational opening. These cylinders must operate in strict displacement and velocity synchronization to prevent mechanical twisting, binding, and structural failure. Rexroth proportional (Item 220) and counterbalance valves (Item 225) possess proprietary flow-gain curves, matched spool alignments, and factory-calibrated on-board electronics (OBE) essential to maintaining synchronized motion.



  2. HYDAC (Pressure and Return Line Filtration):

    • The close-tolerance proportional valves require hydraulic fluid (Mobil DTE 10 Excel 32) maintained strictly at ISO 4406 cleanliness rating 17/15/12. HYDAC Betamicron filter elements provide the validated single-pass Beta ratio (β10(c) ​≥1000) required to prevent spool erosion and sticking.

    • The filter assemblies match existing piping brackets and incorporate integral clogging indicators (110V/B6 signal outputs) that wire directly into the PLC input modules.



  3. Des-Case (Desiccant Breathers & Adapters):

    • In a harsh marine environment, humid and salt-laden air entering the reservoir causes rapid oil emulsification and valve corrosion. Des-Case DC/CS-4 breathers utilize high-efficiency silica gel media coupled with 3-micron particulate filtration and bi-directional internal check valves.

    • The DC-12 quick-flange adapter interfaces directly with existing reservoir cover plates, providing a hermetic, vibration-proof seal without field drilling or hot-work near oil reservoirs.



  4. Honeywell Sensotec (Precision Pressure Transducers):

    • The automated control system monitors real-time cylinder pressure to balance load sharing and detect hydraulic stalls. Honeywell Sensotec AP415DL and AP415CR transducers are electrically matched to the scaling tables and signal registers programmed into the PLC analog cards.

    • Feature high-pressure flush-diaphragm threaded connections engineered to seal into existing Rexroth manifold sensor cavities without pipe-thread adapters.



  5. Dwyer Omega (Temperature Transducers / RTDs):

    • Cold hydraulic oil degrades proportional valve response time. The Dwyer Omega PR-12E RTD temperature sensor monitors reservoir fluid temperature to manage immersion heaters and prevent barrier deployment when fluid viscosity exceeds safe operating thresholds.

    • Features 1/4" NPT threads and probe immersion dimensions matching existing reservoir thermowells.



  6. Lisle Corporation (Magnetic Reservoir Trap Plugs):

    • Captures recirculating microscopic ferrous wear particles that escape surface filters, protecting high-pressure pump pistons and valve spools.

    • Engineered with heavy-duty 3/4" square-head profiles that seat into existing tank cleanout ports and resist stripping during routine maintenance.







Submission of Capabilities:



THIS IS A NOTICE OF INTENT, NOT A REQUEST FOR COMPETITIVE PROPOSALS OR A SOLICITATION. A solicitation will be issued at a later date.



However, any firm that believes it can provide alternative components that meet all the critical salient characteristics (e.g., mechanical footprint, flow-gain curves, porting, sensor scaling) and can demonstrate how using such components would not compromise the operational safety and synchronization of the Stamford Hurricane Barrier may submit a capability statement.



This notice is a market research tool being used to determine the availability of other qualified sources that can meet the requirements identified above. The Government is not obligated to and will not pay for any information received because of this notice. All responses received within 15 days of the posting of this notice will be considered by the Government. A determination by the Government to require the specified brand names is solely within the discretion of the Government.



Submit responses within 15 days of the posting of this notice of intent via email to: Distephano.Marcellus@usace.army.mil (list “W912WJ27BA001 – Stamford Hurricane Barrier Mechanical Components” in the subject line of the email).




Attachments/Links
Contact Information
Contracting Office Address
  • KO CONTRACTING DIVISION 696 VIRGINIA ROAD
  • CONCORD , MA 01742-2751
  • USA
Primary Point of Contact
Secondary Point of Contact


History
Daily notification on new contract opportunities

With GovernmentContracts, you can:

  • Find more opportunities and win more business
  • Receive daily alerts for all new bid opportunities
  • Get contract opportunities matched to your business
ONE WEEK FREE TRIAL

See also

...and experiences routine flooding during storm events. The primary portion of the Dry ...

Town of Manchester

Bid Due: 11/10/2026

...consultants to develop and standardize the Town's municipal separate storm sewer system data ...

State Government of Connecticut

Bid Due: 10/20/2026

...the winter season, based on weather conditions, storm severity, and the operational needs...

City of New Haven

Bid Due: 10/27/2026

...consultants to develop and standardize the Town's municipal separate storm sewer system data ...

Town of Plainfield

Bid Due: 10/20/2026

* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.