Z1DA--36C242-26-AP-0767 | 528-26-1-8386-0003 528A8-22-851 Upgrade BMS Network Construction (VA-26-00016299)
| Location: |
Federal |
| Posted: |
Feb 27, 2026 |
| Due: |
Feb 27, 2026 |
| Agency: |
VETERANS AFFAIRS, DEPARTMENT OF |
| Type of Government: |
Federal |
| Category: |
- Z - Maintenance, Repair or Alteration of Real Property
|
| Solicitation No: |
36C24226B0025 |
| Publication URL: |
To access bid details, please log in. |
Z1DA--36C242-26-AP-0767 | 528-26-1-8386-0003 528A8-22-851 Upgrade BMS Network Construction (VA-26-00016299)
Active
Contract Opportunity
Department/Ind. Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-tier
VETERANS AFFAIRS, DEPARTMENT OF
Office
242-NETWORK CONTRACT OFFICE 02 (36C242)
Looking for contract opportunity help?
General Information View Changes
-
Contract Opportunity Type: Solicitation (Updated)
-
Updated Published Date: Feb 27, 2026 08:56 am EST
-
Original Published Date: Feb 04, 2026 12:57 pm EST
-
Updated Date Offers Due: Feb 27, 2026 01:00 pm EST
-
Original Date Offers Due: Feb 27, 2026 01:00 pm EST
-
Inactive Policy: Manual
-
Updated Inactive Date: Mar 29, 2026
-
Original Inactive Date:
May 28, 2026
-
Initiative:
Classification
-
Original Set Aside:
-
-
Product Service Code: Z1DA - MAINTENANCE OF HOSPITALS AND INFIRMARIES
-
NAICS Code:
-
236220 - Commercial and Institutional Building Construction
-
Place of Performance:
Description View Changes
FYI Submission from AE for 528A8-22-851 Upgrade VA Albany BMS Backbone
The project specs do not indicate a fiber type or strand count for new cabling, please clarify.
Response:
See attached spec section 27 15 00 COMMUNICATIONS STRUCTURED CABLING.
2/1-DA-102: The drawings imply no ceiling, but the field condition is plaster and lathe. Please confirm if this is to be demolished.
Response:
The existing plaster and lathe ceiling shall remain. In spaces with plaster and lathe ceiling, install new conduits and devices below ceiling.
Dumbwaiter Vestibules: We suspect double ceilings, original plaster and lathe above the visible drop ceilings in these rooms. Please confirm if present.
Response:
When Fellenzer was on-site we checked above the 6th and 9th floor ACT and found no plaster layer above those ceilings. Fellenzer did not check floors 2-5, 7-8, or 10.
Given the plaster and lathe in 2/1-DA-102 area and potentially above the vestibule drop ceilings, please advise if any testing has been performed for lead or asbestos.
Response:
Assume plaster and lathe to have ACM and lead. Contractor shall include hazardous material testing and abatement in the bid price. If ACM is not found in certain areas, credit back to owner for abatement of those areas.
Attachments/Links
Contact Information View Changes
Contracting Office Address
-
113 HOLLAND AVE
-
ALBANY , NY 12208
-
USA
Secondary Point of Contact
History
Daily notification on new contract opportunities
With GovernmentContracts, you can:
- Find more opportunities and win more business
- Receive daily alerts for all new bid opportunities
- Get contract opportunities matched to your business
ONE WEEK FREE TRIAL
See also
...entry), GPS antenna, power adapters and additional cabling. XM103 APGMS: The XM103 APGMS ...
DEPT OF DEFENSE
Bid Due: 6/25/2026
* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only for convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.