Contract Opportunity Type: Combined Synopsis/Solicitation (Updated)
-
Updated Published Date: May 20, 2025 08:53 am CDT
-
Original Published Date: May 08, 2025 04:21 pm CDT
-
Updated Date Offers Due: May 22, 2025 03:00 pm CDT
-
Original Date Offers Due: May 20, 2025 09:00 am CDT
-
Inactive Policy: Manual
-
Updated Inactive Date: Jul 21, 2025
-
Original Inactive Date:
Jul 19, 2025
-
Initiative:
Classification View Changes
-
Original Set Aside: Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14)
-
-
Product Service Code: N063 - INSTALLATION OF EQUIPMENT- ALARM, SIGNAL, AND SECURITY DETECTION SYSTEMS
-
NAICS Code:
-
238290 - Other Building Equipment Contractors
-
Place of Performance:
,
Description View Changes
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the
offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR
ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY
is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not,
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES
SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter
or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to
the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243
(Type or print)
(Type or print)
(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code)
(If other than Item 6)
(Specify type of modification and authority)
(such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign)
(Signature of Contracting Officer)
1
3
0001
05-20-2025
10N16
Department of Veterans Affairs
Network Contracting Office 16
715 S Pear Orchard
Plaza 1
Ridgeland MS 39157
10N16
Department of Veterans Affairs
G.V. (Sonny) Montgomery VAMC
A&MM Service (90C)
715 South Pear Orchard Road
Ridgeland MS 39157
To all Offerors/Bidders
36C25625Q0838
05-20-2025
X
X
X
1
** HOUR & DATE for Receipt of Offers is EXTENDED to: 05-22-2025 15:00 CDT
X
(1) One
The purpose of this amendment is to extend the solicitation due date for submission of quotes and to
provide responses to questions that were received.
A. The updated hour and date specified for receipt of offers is extended to 05/22/2025 at 3:00 PM (CST).
B. Questions and Answers (Q&A) are provided on the following pages.
Note: Contractor must acknowledge this amendment by signing in box 15b and submit with quote before the solicitation due
date. If not acknowledged, contractor may be ineligible for award at the discretion of the Contracting Officer.
Page 3 of 3
Med Gas Alarm Panel Install Questions and Answers
The contract requires a 5-year manufacturer warranty, the standard warranty is 1 or 2 years, we are not positive this requirement can be met. Please verify.
Yes, we want the 5-year warranty
SOW F (2) should list 6030 not 6020. Must be Verified, not inspected.
This is correct a 6030 is what would be needed not the 6020.
Can you provide the most recent annual medical gas inspection report for the facility?
No
The primary location for the master alarm panel is not suitable; it is behind doors that normally open/close. Alternate location is in the hallway but requires clarification from AHJ if the proposed location meets NFPA 5.1.9.2.1 (1). One master alarm panel shall be located in the office or workspace of the on-site individual responsible for the maintenance of the medical gas and vacuum piping systems . Is this within visual/audible range of the person/shop responsible for the system?
The primary location is within 6ft of their workstation and the door to the area remains open while the person is at work. This location also allows the maximum exposure to the panel for other staff members and the supervisor who would serve as a backup for repairs.
Where is the current master alarm panel? Is it in an area of continuous observation per NFPA 5.1.9.2.1 (2)?
The current master alarm panel is monitored 24 hr a day and is located in the emergency department. See attached drawing
Can you provide a picture of the current master alarm panel?
See attached photo
If the current master alarm panel is not Amico, it might have to be retrofitted. Panel manufactures need to match or you can have an issue due to the power supply voltage loop through the switches. Verify existing panel manufacturer.
See attached photo
Is the current master alarm panel wiring up to code? NFPA 5.1.9.2.3.1 (A):(D)
The panel is up to code and has passed the annual inspection.
If the current master alarm panel does not meet NFPA 5.1.9.2.3.1 (A):(D), will it be required to be brought to current code?
No, only to install the Med Gas panel in building 37 in a manner that meets code.
Can you provide floor plans for the facility that shows the locations of the source equipment? Oxygen, Medical Air, Medical Vacuum, Nitrous Oxide Manifold, Nitrogen Manifold, etc. We would also need the locations of the main line pressure switches shown on the plans. Needs to be noted on the plans to estimate distance for conduit and LV wire.
See attached floor plan
Are the existing main line pressure switches fully functional? Do they have gas specific demand checks and gauges?
To our knowledge they are fully functional.
The new master alarm panel is required to be 120VAC e-power. Has a spare breaker been identified for the new circuit? If so, can you show the location of the breaker on plans?
There is no emergency power located in building 37 and no circuit has been Identified. A electrical panel is located with in 20 feet of the primary and alternate location of the proposed med gas panel
Is there a chase, tunnel, or anything connecting the hospital to Bldg 37? If not, this would require digging to install conduit connecting the two buildings.
There is not a chase or tunnel. There is buried conduit connecting building 1 to building 37. There is no drawing of the path of the conduit.
Are we integrating the new master alarm panel with the BMS?
No, it will not be integrated with the Building management system.