Columbia County School District
Weight Room Equipment Install
Bid Amendment 1, Request HC-03-31-26A
Responses to questions.
1)Do you have a CAD file or rendering of the rooms with the dimensions? Included
2) Is the equipment listed for each school or is the total on the equipment both schools (for example 5 racks will
go to Evans and 5 to Lakeside?) or 10 benches for each school or is it 20 per school? For example, item #3
quantity 20 – landmine is for one school. Please provide the price for one set of quantity 20 landmine. The
description of quantity 20 landmine is for one school. Installation total is two schools.
3) will both schools be ready for install at the same time or do they have different time frames? As early in the
summer as possible
4) can I submit more than 1 Proposal? yes
5) Can I deliver quotes in person? yes
6) can you provide school logos for customization? Logos can be found on school websites and some have
been included.
https://evanshs.ccboe.net/
https://lakesidehs.ccboe.net/
7) Line item #1 . What gauge of steel is being specked? 12 gauge.
8) line # 11-15 . Are these plates going to have logos or no logos? yes
9) Line item 18 > are these the soft med ball styles or the old school hard med balls or some other type? I would
assume the soft med ball style . soft
10) line item # 20 - Are these hex dumbbells? not specified
11) line item 19 - can I substitute (2) 4 tier med ball / kettle bell rack for (4 ) two tier racks? As long as it holds
the materials, please note alternate
12) line item # 20 - Can i substitute a 25lb pair of lifting Chains or a 40 lb instead of 28lb? yes, clearly label all
changes that very from original specifications
First is there current equipment that needs to be removed or moved from the room? If so are they
willing to remove and move on their own or would the installers need to include that as well?
Room will be empty
1. When can customer receive? (you do not want equipment showing up before school can receive
or before room is done) –We do not want the equipment being delivered with no one to unload,
place in designated locations and assemble. The equipment is to be set up in the room. As
early in the summer as possible
2. Is room ground level? – Yes
3. Does room have double door access? – Yes
4. Is room close to a parking lot? – Yes
5. Are there any stairs leading to room indoor or outdoor? – No. There is a curb.
If room is not ground level is there an elevator? What is the size/ weight limit? Yes, it is ground level.
1. Can you clarify any details regarding the rack specification desired? We have multiple options and would
like to align our specs with the expectations of the school.
1. 3’’x3’’ 11 gauge tube with 1’’holes/hardware vs. 4’’x3’’-5’’x3.5’’ wrap 7 gauge with ?’’
hardware Didnt know there was a difference. The 4 companies I talked to said everyone uses the
same
2. Double storage post or single storage post preferred?
3. Height of rack preferred (8’, 8.5’, 9’) Didnt know there was a difference. The 4 companies I talked to
said everyone uses the same
2
Columbia County School District
Weight Room Equipment Install
Bid Amendment 1, Request HC-03-31-26A
4. Extended base or short base (will these units be bolted down and if so, do you want the installation
team to account for doing this?) These will not be bolted down
2. Due to our many variations and options for product, are we able to submit multiple bid options to showcase
the variety of range and options for product? Yes, just make sure the item # the options reference are clearly
labeled.
3. Is there a layout that this request is based on that can be provided to assist with quoting the appropriate
racks and storage units? Room is 64x64 square will have 5 double racks down one side 5 double racks
down the other
4. Is there an estimated date/timeline for the installs? As early in the summer as possible
5. Specifications for type of Dumbbell requested? No. Have got some for hex or just round. Whichever is
cost effective
6. Are you looking for any attachments for the bridge rack connectors or just the holes for future options for
attachments? Holes for future options
7. Do you have a description of preferred color schemes and logos to be used on product? Logos for the first
two schools attached
1. What products will the custom logos be applied to, and where on each product will the logo be placed?
Logos on the racks, the benches and plates if possible
2. Please provide the logo in vector file format. Logos attached. Not in a vector file. Will have to get those but
logos attached for colors
3. What is the required delivery date for each school? As early in the summer as possible
4. Additionally, can we revise the pricing document to include both the unit price and the extended price so
the total cost for all quantities is clearly shown? Yes that will work fine
For example, item #3 quantity 20 – landmine is for one school. Please provide the price for one set of
quantity 20 landmine. The description of quantity 20 landmine is for one school. Installation total is
two schools.
Are both weight rooms on the first floor?
Yes
Is there a single or double door for entry to the weight room (3' or 6')
Double door
Is a layout of the rooms available, or dimensions of the rooms?
Drawings included
Is existing equipment being removed or is this new construction?
Rooms will be empty
Vendors are to clearly state estimated delivery based on days after award
3
E
D
C
B
A
AREA K
AREA J
2" EXP. JOINT W/ COVER PLATE; FILL
GAP W/ 2-HOUR FIRE RATED
COMPRESSED JOINT FILLER UL #2079
8M7N
12M0N
8M0N
4'-8"
7201.4
1'-4"
9'-4"
3'-4"
A1
_____________________________________________________________
A-420 _____
8M5N
5'-2"
2'-4"
12'-2"
3
7209A
4M7N
2'-4" 5'-4"
B3 A-717 B1
9'-4"
COACH
7210
4
7210
8M5N
ARCHITECTURAL JOINT
SYSTEM COVER PLATE
AT WALLS AND CEILING, TYP.
A1
_____________________
A-392
4
2" EXP. JOINT W/ COVER PLATE; FILL
GAP W/ 2-HOUR FIRE RATED
COMPRESSED JOINT FILLER UL #2079
A3
_____________________________________________________________
A-504 _____
5
2'-0"
2" EXP. JT.
W/ COVER PLATE
AT 2 HR. FIRE WALL(S)
12" ALUM.HEAVY DUTY
THRESHOLD EXP. JOINT
COVER AT FLOOR
iSF25
8M5N
7200C
1'-4"
6
VEST.
6360
7200D
10'-4"
1
SF 14
W 1.1
A2
_____________________
A-392
AREA K
A1
_____________________________________________________________
A-401 _____
AREA J
8M7N
CORRIDOR
7200
1'-4"
1'-4"
8M0N
8M7N
7'-4"
7209B
7208A
12M0N
7302A
UP
29'-4"
12M1N
STAIR
7208
7208B
W 1.1
3
_____________________
A-385
8M9N
10'-0"AFF
1'-4"
1'-4"
VISTOR MEN'S LOCKER
1'-8"
12'-0"
3'-4"
7209
8M7N
4M7N
15'-3"
8M7N
7'-3"
10'-1"
22.3
8M5N
8M7N
5'-4"
HM2
8M5N
JAN
7301
7301
C
C
1
7211
6M5N
COACH
7211
22.3
8M5N
9'-4"
7'-3"
8'-1"
2'-4"
8M7N
8M7N
HM2
8M7N
WEIGHT ROOM
7302
WALL MOUNTED
SCOREBOARD
7212A
7'-8"
VISTOR WOMEN'S LOCKER
7212
17'-0"
CORRIDOR
7300
7212B
12M0N
SIM
C5
_____________________________________________________________
A-502 _____
2'-8"
2'-0"
SF6
8M5N
2'-0"
HOME BOYS LOCKER
7213
A5
_____________________________________________________________
A-419 _____
7213
7'-8"
2'-4"
26.4
8M5N
8M7N COACH
7214
9'-4"
A4
_____________________
A-383
7214
8M5N
7'-8"
5'-4"
8M5N
7213.1A
JAN. / STOR.
22.1
7213.1
8M5N
14'-8"
2'-0"
8M7N
8M7N
10'-0"
8M7N
22.3
8M5N
8M0N
22.1
8M0N
A5
_____________________
A-383
C1 A-707 D1
7302B
7304A
12M0N
HM2
4
7215
COACH
7215
6M5N
22.3
9'-4"
6'-0"
9'-5"
4'-0 1/8"
3
A3 A-717 A1
2'-8"
8M7N
HM2
8M7N
8M7N
8M7N
2'-0"
7216
8M7N
A6
_____________________
A-396
4
11'-6 3/8"
7'-8"
HOME GIRLS LOCKER
7216
12M0N
5'-2"
7201.2
12M5N
12'-2"
17'-4"
2'-0"
3
8M7N
SF20 1
7217A
8M5N
STAIR
7217
UP
32'-0"
2'-0"
8M7N
1 12M0N
SF18
7304B
4'-0"
10'-4 3/8"
A1
_____________________________________________________________
A-505 _____
SF6
7217B
12M5N
D1
_____________________
A-302
MULTIPURPOSE ROOM
7304
W 1.1
1'-7"
4
2'-0"
1'-4"
1'-4"
8M9N
10'-0"AFF
W 1.1
SF5
5'-5"
A4
_____________________
A-384
SF5
1'-4"
1'-4"
8M9N
8M9N
2'-0"
10'-0"AFF 10'-0"AFF
31'-8"
2
_____________________
A-385
A3
_____________________
A-396
2
SF5
A4
_____________________________________________________________
A-401 _____
1
_____________________
A-385
A1
FLOOR PLAN- PARTIAL- LEVEL 1- AREA J
1/8" = 1'-0"
47
49 50
51
52 52.1
53
54
55
56
1
2
3
GEORGIA REGISTRATION INFORMATION: Neil A. Dawson [RA009731], James M. Hubbard [RA014155], John T. Hughes [RA013037], Laura L. McLeod [RA011330], Lisa K. Pinyan [ID000516], John P. Works [RA010038], Bryan D. Harder [RA012564], Dylan J. Towe [RA015218], Melissa A. Watness [RA012309], Prescott D. May, III [RA014912], Nathan C. Daniel [RA015598], April W. Mundy [RA013003], Brian Bresg [RA015706], Katherine A. Schuff [RA015681], LeRoy A. Selvidge, Jr. [RA015989]
4
H21.1
H21
H20
H19
H18
PARTITION GRAPHICS
GRAPHIC SAMPLE:
8M2N
2 HOUR RATED CMU FIRE BARRIER:
SEE PARTITION TYPE SCHEDULE ON SHEET A-003 FOR
HEIGHT CONDITION, FIRE/SMOKE PROTECTION TYPE, AND
COMPLETE PARTITION INFORMATION
HATCH PATTERN LEGEND
CONCRETE MASONRY CONSTRUCTION
METAL STUD PARTITION
EXISTING TO REMAIN
Evans High
School
FACILITY CODE: 636-4050
GENERAL NOTES
A. ALL INTERIOR WALLS SHALL EXTEND AND BE SEALED TO THE UNDERSIDE OF DECK ABOVE, U.N.O. REFER TO STRUCTURAL FOR
REQUIRED TOP OF WALL BRACING.
B. EXTERIOR WALL DIMENSIONS ARE TO THE FACE OF CMU OR BRICK VENEER, U.N.O.
C. INTERIOR WALL DIMENSIONS ARE TO FACE OF CMU OR METAL STUD, U.N.O.
D. LOCATE ALL METAL STUD WALL DOOR OPENINGS 4" FROM NEAREST PERPENDICULAR WALL U.N.O.
E. LOCATE ALL CMU WALL DOOR OPENINGS 8" FROM NEAREST PERPENDICULAR WALL U.N.O.
F. AT INTERIOR MASONRY PARTITIONS, PROVIDE BULLNOSE MASONRY UNITS FOR OUTSIDE VERTICAL CORNERS AND HORIZONTAL
WINDOW STOOLS, EXCEPT AT FIRST COURSE AT FINISHED FLOOR, TOP COURSE AT CEILING, AND WHERE INDICATED
OTHERWISE.
G. ALL GWB SHALL BE ABUSE-RESISTANT TO 8'-0" AFF (U.N.O). GWB ABOVE 8'-0" MAY BE REGULAR OR ABUSE-RESISTANT AT
CONTRACTOR'S OPTION. REFER TO SECTION 09255 FOR COMPREHENSIVE MATERIAL SPECIFICATIONS.
H. FIRE AND SOUND RATED WALLS/PARTITIONS TO BE CONSTRUCTED TIGHT TO STRUCTURE, PIPING, DUCTWORK AND OTHER
PENETRATIONS. ALL WORK IS TO BE BRACED TO STRUCTURE ABOVE.
I. PATCH CLEAN AND PAINT ALL EXISTING CMU WALLS.
J. WHERE PARTITIONS OF DIFFERENT FIRE RATINGS INTERSECT, THE HIGHEST RATED PARTITION SHALL CONTINUE THROUGH.
MAINTAIN PARTITION FIRE RATING BEHIND RECESSED FIRE EXTINGUISHER CABINETS.
K. INSTALL BLOCKING IN METAL STUD PARTITIONS FOR CASEWORK, WALL MOUNTED EQUIPMENT, TRIM AND RELATED
CONSTRUCTION AS INDICATED IN THE SPECIFICATIONS.
L. SEE SHEET A-001 FOR CONSTRUCTION SUBSYSTEMS.
M. SEE A-200 SERIES ELEVATION DRAWINGS FOR LOCATION OF EXTERIOR MASONRY CONTROL JOINTS.
N. SEE A-600 SERIES SHEETS FOR DOOR, LOUVER, AND WINDOW & GLAZING TYPES.
O. SEE SHEETS A-700-SERIES SHEETS FOR INTERIOR FINISH SCHEDULES.
P. SEE SHEETS A-SG-1 FOR SIGNAGE SCHEDULE, ELEVATIONS, AND DETAILS.
Q. SEE CIVIL DRAWINGS FOR EXTERIOR SIDEWALKS, U.N.O.
R. SEE STRUCTURAL DRAWINGS FOR EXTENTS OF SLAB DEPRESSIONS AND CUTOUTS, U.N.O.
S. FURNITURE & EQUIPMENT (TABLES, CHAIRS & COMPUTERS) IS F.F.E. - O.F.O.I. (OWNER FURNISHED OWNER INSTALLED).
T. RATED WALLS/ PARTITION PENETRATIONS AND TERMINAL JOINTS ARE TO BE INSTALLED AS SHOWN IN APPLICABLE UL JOINT OR
PENETRATION DETAIL.
U. FIELD VERIFY LOCATION OF INTERIOR WALL & CEILING CONTROL JOINTS REQUIRED IN THE SPECIFICATION WITH ARCHITECT
PRIOR TO INSTALLATION.
V. WALLS INCLUDING GYP.BD. AT THE PERIMETER OF ROOMS/ SPACES WITHOUT CEILINGS, i.e. EXPOSED STRUCTURE, SHALL
EXTEND TO STRUCTURE ABOVE.
321 WEST CONGRESS STREET SUITE 301
SAVANNAH, GEORGIA 31401
TEL. 912.695.2111
WWW.LS3P.COM
H16
FLOOR PLAN NOTES BY NUMBER
NUMBER
NOTE
1.1 REFER TO SHEET A-421 FOR TYPICAL CLASSROOM LAYOUT AND CONDITIONS.
COPYRIGHT 2022 ALL RIGHTS RESERVED. PRINTED OR
ELECTRONIC DRAWINGS AND DOCUMENTATION MAY
NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN
PERMISSION FROM LS3P ASSOCIATES LTD.
2.1 PATCH AND REPAIR EXISTING CMU WALL TO REMAIN AS REQUIRED FOR PARTITION DEMOLITION. REFER
H14
TO DEMO PLANS.
2.2 CONTRACTOR TO COORDINATE EXISTING WELDING EQUIPMENT TO REMAIN WITH OWNER. COORDINATE
INSTALLATION OF NEW EQUIPMENT WITH OWNER AS REQUIRED. COORDINATE MECHANICAL AND
ELECTRICAL INFRASTRUCTURE REQUIREMENTS WITH OWNER.
2.3 CONTRACTOR TO COORDINATE EXISTING AUTO COLLISION LAB EQUIPMENT TO REMAIN IN PLACE.
COORDINATE INSTALLATION OF NEW EQUIPMENT WITH OWNER AS REQUIRED. COORDINATE MECHANICAL
AND ELECTRICAL INFRASTRUCTURE REQUIREMENTS WITH OWNER.
2.4 EXISTING CONDITIONS TO REMAIN AND BE PROTECTED IN PLACE BY CONTRACTOR.
2.5 EXISTING DEPRESSED SLAB TO BE FILLED TO FLUSH OUT WITH EXISTING ADJACENT SLAB TO REMAIN.
REFER TO DEMOLITION PLANS.
H13
3.1 CONTRACTOR TO INSTALL NEW CONCRETE PAD FOR NEW EQUIPMENT. REFER TO MECHANICAL AND
ELECTRICAL DRAWINGS.
4.1 INFILL EXISTING MASONRY WALL EXTENTS TO MATCH ADJACENT IN CONSTRUCTION MATERIALS AND
FINISH. ALIGN AND PATCH/REPAIR ADJACENT EXISTING WALLS TO REMAIN AS REQUIRED. PATCH AND
REPAIR EXISTING SLAB AND FLOOR FINISH TO REMAIN.
4.2 EXTEND EXISTING MASONRY WALL TO DECK FOR 1 HOUR RATED WALL ASSEMBLY. REFER TO PARTITION
TYPE HEAD DETAILS FOR SEALANT REQUIREMENTS. PATCH AND REPAIR EXISTING CONDITIONS TO
REMAIN AS REQUIRED.
4.3 EXTEND EXISTING MASONRY WALL TO DECK FOR SMOKE RATED WALL ASSEMBLY. REFER TO PARTITION
TYPE HEAD DETAILS FOR SEALANT REQUIREMENTS. PATCH AND REPAIR EXISTING CONDITIONS TO
H12
REMAIN AS REQUIRED.
4.4 INFILL EXISTING MASONRY WALL TO MATCH ADJACENT IN CONSTRUCTION MATERIALS AND FINISH.
4.5 INFILL EXISTING STUD WALL EXTENTS AS INDICATED. ALIGN AND PATCH/REPAIR ADJACENT EXISTING
WALLS TO REMAIN AS REQUIRED. PATCH AND REPAIR EXISTING SLAB AND FLOOR FINISH TO REMAIN.
5.1 NEW METAL ROOF LADDER, REFER TO SPEC FOR PRODUCT AND ANY ASSOCIATED ACCESSORIES.
8.1 MECHANICAL LOUVER, REFER TO SPEC. SEE SECTION FOR VERTICAL LOCATION IN WALL. SEE MECH FOR
SIZING.
H11
8.2 FIRE RATED WON DOOR, REFER TO SPECS.
10.1 EXISTING LOCKERS TO REMAIN TO BE PROTECTED IN PLACE BY CONTRACTOR. WHERE DEMOLITION
EXTENTS IMPACT LOCKER LAYOUTS, CONTRACTOR TO REMOVE EXISTING LOCKERS, PROTECT AND
STORE FOR PROJECT REINSTALLATION AS INDICATED ON PLANS. TURN UNUSED REMAINING LOCKERS
OVER TO OWNER.
10.2 NEW 2-TIER LOCKERS.
10.3 PROVIDE LOCKER MANUFACTURER'S END CLOSURE PANEL TO COVER EXPOSED ENDS OF LOCKERS TO
REMAIN, FINISH TO MATCH ADJACENT LOCKERS.
10.4 COMBINATION OF NEW 2-TIER AND 3-TIERLOCKERS. REFER TO ELEVATION.
11.1 WASHER/DRYER BY OWNER. REFER TO MECHANICAL, ELECTRICAL AND PLUMBING.
11.2 DISPLAY MONITORS. PROVIDE BLOCKING IN METAL STUD FRAMED WALLS. COORDINATE POWER AND
DATA WITH MONITOR MOUNTING HEIGHTS.
11.3 DUMPSTER LOCATION. REFER TO CIVIL.
H9
11.4 REFER TO FOOD SERVICE DRAWINGS FOR FOOD SERVICE EQUIPMENT LAYOUT AND COORDINATION
REQUIREMENTS.
11.5 CONTRACTOR TO COORDINATE SPECIALITY EQUIPMENT FOR NEW SCIENCE LABS WITH LEONARD
PETERSON.
12.1 ACOUSTIC WALL TREATMENT, TYPICAL.
12.2 CASEWORK, REFER TO FINISHES.
∆ DATE
DESCRIPTION
12.3 ATHLETIC SAFETY WALL PAD TO WRAP COLUMN, REFER TO SPECS.
1 07/18/2024 Conformance Set
12.4 REMOVE EXISTING PAPER TOWEL DISPENSER AND RECEPTACLE. REPLACE WITH NEW PAPER TOWEL
2 10/11/2024 ASI 1
HOLDER AND RECEPTACLE. REFER TO SPEC.
3 11/26/2024 ASI 2
12.5 REMOVE EXISTING STALL PARTITION AND REPLACE WITH NEW STALL PARTITION, SEE ENLARGED PLANS
4 12/16/2024 ASI 3
FOR DIMENSIONS. REFER TO SPEC.
5 01/30/2025 ASI 4
12.6 REMOVE EXISTING MIRROR AND REPLACE WITH NEW MIRROR. REFER TO SPEC.
6 03/19/2025 ASI 5
H7
13.1 CONTRACTOR TO COORDINATE PAINT BOOTH SELECTION AND INSTALLATION FROM OWNER.
COORDINATE MECHANICAL AND ELECTRICAL INFRASTRUCTURE REQUIREMENTS WITH OWNER.
13.2 CONTRACTOR TO COORDINATE 20'X 40' AREA FOR FIRING SIMULATION SELECTION AND INSTALLATION
WITH OWNER. COORDINATE MECHANICAL AND ELECTRICAL INFRASTRUCTURE REQUIREMENTS WITH
OWNER.
13.3 REFER TO KITCHEN EQUIPMENT DRAWINGS FOR CULINARY LAB EQUIPMENT LAYOUT AND COORDINATION
REQUIREMENTS.
14.1 FUTURE ADA LIFT BY OWNER. PROVIDE POWER AND REMOVABLE SECTION OF GUARDRAIL.
22.1 INSTALL NEW ACCESSIBLE WATER COOLER. NEW WATER COOLER TO REPLACE SINGLE WATER COOLERS
AT EXISTING CONDITIONS, REFER TO SHEET A-005 FOR ACCESSIBILITY REQUIREMENTS. REFER TO
PLUMBING DRAWINGS AND SPECS.
22.2 REFER TO SHEET A-005 FOR PLUMBING ACCESSIBILITY REQUIREMENTS. REFER TO PLUMBING DRAWINGS,
TYPICAL.
22.3 NEW FLOOR DRAIN, REFER TO PLUMBING DRAWINGS.
KEY PLAN:
22.4 PLUMBING CHASE, REFER TO PLUMBING DRAWINGS.
H5
22.5 EXISTING SCUPPERS TO RECEIVE NEW LEADER HEAD AND DOWNSPOUTS. CONNECT TO UNDERGROUND
STORMWATER, REFER TO CIVIL.
H4
22.6 CATCH BASIN AND DOWNSPOUT - TIE TO STORM WATER SYSTEM.
23.1 UNIT HEATER, REFER TO MECHANICAL.
23.2 MECHANICAL SHAFT, REFER TO MECHANICAL FOR DUCT SIZING.
23.3 CONDENSER, REFER TO MECHANICAL.
23.4 CHILLER, REFER TO MECHANICAL.
P
N M LK
A
CD E
B
F GH J
26.1 ELECTRICAL PANELS, REFER TO ELECTRICAL.
26.2 ELECTRICAL TRANSFORMER, REFER TO ELECTRICAL.
26.3 ELECTRICAL DISCONNECT SWITCH, REFER TO ELECTRICAL.
26.4 KEY SWITCHES, DOUBLE GANG.
H2
32.1 INSTALL NEW BOLLARDS, GROUT SOLID, TYPICAL. REFER TO ARCHITECTURAL SHEET DETAIL D6/A- 521.
32.2 PATCH CMU WALL AND CONCRETE SLAB, PREP FOR NEW FINISHES.
SHEET NAME:
FLOOR PLAN-
LEVEL 1- AREA J
ORIG
SUBMISSION:
04/30/2024
TRUE PROJECT
NORTH NORTH
SHEET:
A-101J
5
6
GMP SET / GA DOE FINAL SET