FCC HAZELTON - WATER HEATING SYSTEM PRODUCT ONLY

Agency: JUSTICE, DEPARTMENT OF
State: West Virginia
Type of Government: Federal
Category:
  • 45 - Plumbing, Heating, and Sanitation Equipment
Posted: Apr 24, 2024
Due: Apr 29, 2024
Solicitation No: 15B12124Q00000016
Publication URL: To access bid details, please log in.
Follow
FCC HAZELTON - WATER HEATING SYSTEM PRODUCT ONLY
Active
Contract Opportunity
Notice ID
15B12124Q00000016
Related Notice
Department/Ind. Agency
JUSTICE, DEPARTMENT OF
Sub-tier
FEDERAL PRISON SYSTEM / BUREAU OF PRISONS
Office
USP HAZELTON
Looking for contract opportunity help?

APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.

APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.

The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).

General Information
  • Contract Opportunity Type: Combined Synopsis/Solicitation (Original)
  • All Dates/Times are: (UTC-04:00) EASTERN STANDARD TIME, NEW YORK, USA
  • Original Published Date: Apr 24, 2024 12:09 pm EDT
  • Original Date Offers Due: Apr 29, 2024 02:00 pm EDT
  • Inactive Policy: 15 days after date offers due
  • Original Inactive Date: May 14, 2024
  • Initiative:
    • None
Classification
  • Original Set Aside:
  • Product Service Code: 4520 - SPACE AND WATER HEATING EQUIPMENT
  • NAICS Code:
    • 238220 - Plumbing, Heating, and Air-Conditioning Contractors
  • Place of Performance:
    WV 26525
    USA
Description

FCC Hazelton requires a quantity of 9 each indirect plate and frame water heater plus 9 each pumps to accompany the water heaters. Vendors are required to have active SAM.Gov registration and to provide their UEI. A signed SF1449 must be submitted to be considered received. This requirement is for product ONLY. All quotes and bids are required to be submitted to Kelly Brown, Supervisory Contract Specialist with FCC Hazelton at k1roberts@bop.gov (Note: that is a number one(1) after the K) AND HAX-ProcurementProp-S@bop.gov. Quotes must be valid for at least 30 days after close of bids on April 29, 2024 at 2 PM EDT. Specific product requirements below and example spec sheets attached.



Indirect Plate And Frame Water Heater: (9)

Dimensions cannot Exceed: 63” Height Max; 22” Width max; 61” Base Length – MUST FIT THROUGH STANDARD 36” door. Product should not exceed 1200 lbs – Lite Weight Preferred

FEATURES:

ASME DOUBLE WALL HEAT EXCHANGER

• 316L Stainless Steel

• 150 psi Working Pressure

DIGITAL DISPLAY

• DHW Set Point Range 90°F to 180°F

ADVANCED TEMPERATURE CONTROL

MODULATING CONTROL VALVE

SCALE REDUCING PUMP

AUTOMATIC AIR VENT

ASME TEMPERATURE & PRESSURE RELIEF VALVE

• 210°F and 150 psi

ADJUSTABLE HIGH LIMIT

WYE STRAINERS - DOMESTIC PIPING AND

BOILER PIPING

ISOLATION VALVES - DOMESTIC PIPING AND BOILER PIPING

MODBUS COMMUNICATION



WARRANTY

• 5-Year limited warranty/1-Year limited parts

• Warranty for product only without services requirement



SUGGESTED SPECIFICATION

The Indirect Plate and Frame shall be constructed of a 316 stainless steel plate with EPDM gaskets. Maximum unit dimensions shall be: Length ___61_inches, Width ___22___inches and Height __63______ inches.

The Indirect Plate and Frame shall be a double wall. The plate and frame shall be constructed in accordance with the ASME Boiler and Pressure Vessel Code requirements, stamped and registered with the National Board of Boiler and Pressure Vessel Inspectors

The Indirect Plate and Frame shall have a 150 psi working pressure and be supplied with an ASME temperature and pressure relief valve. Standard equipment shall include Wye Strainers, Isolation Valves, Automatic Air Vent, Scale Reduction Pump, Adjustable High Limit and drain valve

The temperature control shall provide + or – 4 degrees Fahrenheit accuracy with up to a 50% change in load. Setpoint range between 90 and 180 F. Modbus communication shall be standard equipment. The modulating valve shall have a 1000 to 1 turndown. The Indirect Plate and Frame shall be suitable for use with polypropylene glycol, up to 50% concentration. The de-rate associated with the glycol will vary per glycol manufacturer.



Pump: (9) Specifications must meet all below requirements for pump with system control and monitoring key

Conditions of Service



Flow: 130 US GPM



Head: 32 ft

Efficiency: 68.6 %

Liquid: Water

Temperature: 60 °C

NPSH required: ft

Pump Data

Specific Gravity: 0.985

Maximum operating pressure: 12 bar

Liquid temperature range: -10 .. 110 °C

Maximum ambient temperature: 40 °C

Flange standard: GF

Pipe connection: GF65

Product number: On request

Motor Data

P1 max: 29 .. 1385 W

Mains frequency: 60 Hz

Enclosure class: X4D

Insulation class: F



ADDITIONAL INFORMATION: Domestic inlet temp Set point. DHW set point 90 to 180 degrees. GPH for all units together or for each if separated. GPH is for each unit. Each system will supply at minimum hot water to 64-cells, 10-showers, 2-mop closet and 1-staff restroom. Boiler water entering temp 160-180 degrees. Boiler water Leaving temp 120-140 degrees BTU I am looking for specifics on this. -These units are in use 24/7-365 if that helps.

For singled cell showers, 10 to be used at a time with a maximum of up to 128.


Attachments/Links
Contact Information
Contracting Office Address
  • 1460 SKY VIEW DRIVE PO BOX 450
  • BRUCETON MILLS , WV 26525
  • USA
Primary Point of Contact
Secondary Point of Contact
History
  • Apr 24, 2024 12:09 pm EDTCombined Synopsis/Solicitation (Original)
Daily notification on new contract opportunities

With GovernmentContracts, you can:

  • Find more opportunities and win more business
  • Receive daily alerts for all new bid opportunities
  • Get contract opportunities matched to your business
ONE WEEK FREE TRIAL

See also

...05240248- heat pump systems for I-81 Headquarters DIVISION OF HIGHWAYS John W Estep ...

State of West Virginia

Bid Due: 5/21/2024

...Sprinkler, Waterflow, Backflow, Dry, & Fire Pump Inspection GENERAL SERVICES DIVISION Melissa...

State of West Virginia

Bid Due: 5/15/2024

...05240249-heat pump systems & hanging heaters for Knobley Sub DIVISION OF HIGHWAYS Dusty ...

State of West Virginia

Bid Due: 5/21/2024

...blast room. The existing vacuum pump that penetrates the roof, shall be removed ...

DEPT OF DEFENSE

Bid Due: 5/07/2024

* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only as a convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.