Z1NE--405-23-001 | Water Tank Painting and Repair
Agency: |
VETERANS AFFAIRS, DEPARTMENT OF |
State: |
Federal |
Type of Government: |
Federal |
Category: |
- Z - Maintenance, Repair or Alteration of Real Property
|
Posted: |
Aug 31, 2023 |
Due: |
Sep 12, 2023 |
Solicitation No: |
36C24123R0112 |
Publication URL: |
To access bid details, please log in. |
Z1NE--405-23-001 | Water Tank Painting and Repair
Active
Contract Opportunity
Department/Ind. Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-tier
VETERANS AFFAIRS, DEPARTMENT OF
Office
241-NETWORK CONTRACT OFFICE 01 (36C241)
Looking for contract opportunity help?
Procurement Technical Assistance Centers (PTACs) are an official government contracting resource for small businesses.
Find your local PTAC
(opens in new window)
for free government expertise related to contract opportunities.
General Information View Changes
-
Contract Opportunity Type: Solicitation (Updated)
-
All Dates/Times are: (UTC-04:00) EASTERN STANDARD TIME, NEW YORK, USA
-
Updated Published Date: Aug 31, 2023 08:23 am EDT
-
Original Published Date: Aug 14, 2023 03:39 pm EDT
-
Updated Date Offers Due: Sep 12, 2023 01:00 pm EDT
-
Original Date Offers Due: Sep 12, 2023 01:00 pm EDT
-
Inactive Policy: Manual
-
Updated Inactive Date: Oct 12, 2023
-
Original Inactive Date:
Nov 11, 2023
-
Initiative:
Classification
-
Original Set Aside:
-
-
Product Service Code: Z1NE - MAINTENANCE OF WATER SUPPLY FACILITIES
-
NAICS Code:
-
238320 - Painting and Wall Covering Contractors
-
Place of Performance:
Description View Changes
1
NOTICE OF FOR PROPOSAL AMENDMENT
SOLICITATION NUMBER: 36C24123R0112
AMENDMENT NUMBER: 0001
DATE: August 31, 2023
PROJECT NUMBER: 405-23-001
PROJECT TITLE: Water Tank Painting and Repair
LOCATION: VA Medical Center, White River Junction, VT 05009
REASON FOR AMENDMENT: Answer RFI Questions 1 thru 2
__________________________________________________________
AMENDMENT: 0001
Question 1 SOW states Contractor shall provide two temporary water storage tanks, each holding at least 6,000 gallons. Tanks shall be piped together and tied into the water service and distribution lines. The temporary water storage tanks shall be able to hold at least 70 PSI of water pressure
Using tanks that are 6,000 gals and able to handle at least 70 psi of pressure is tall order. Those type of tanks are very expensive at that size. Is it possible to use static tanks with temporary pumps that could be triggered from the BMS?
VA Response:Â Â Yes, that would be fine. The tanks are intended to be used as a temporary tower. The 70 PSI will be maintained with the water pumps in building 2. The VA intends to have the water service flow through the tanks to keep the stored water fresh. The tanks will be wired into the BMS system at the water tower. The BMS is a Siemens Desigo Building Automation system.
Question 2 SOW states Water tanks shall be wired into the Building Management System (BMS) to communicate with the two VFD water tower supply pumps in building 2 to maintain a full condition. The water tanks will serve as a temporary water tower, providing an emergency supply of water to the campus in case of any failure by the municipal water system.
We are not quite clear on what is needed and how to integrate the tanks into the BMS.
What needs to be integrated ? Is it the pressure and / or levels?
VA Response:Â A level indicator needs to be on the tanks to be sure they remain full.
Attachments/Links
Contact Information View Changes
Contracting Office Address
-
ONE VA CENTER
-
TOGUS , ME 04330
-
USA
Secondary Point of Contact
History
Daily notification on new contract opportunities
With GovernmentContracts, you can:
- Find more opportunities and win more business
- Receive daily alerts for all new bid opportunities
- Get contract opportunities matched to your business
ONE WEEK FREE TRIAL
See also
Follow FD2030-24-00093 Active Contract Opportunity Notice ID FD2030-24-00093 Related Notice Department/Ind. Agency DEPT
Federal Agency
Bid Due: 11/13/2024
Follow QUICK ACTING AIRTIGHT DOOR Active Contract Opportunity Notice ID N0040624Q00670001 Related Notice
Federal Agency
Bid Due: 11/16/2024
Follow CustomerX Vendor Pool and Subsequent Pods (CSO HT003823SC001) Active Contract Opportunity Notice
Federal Agency
Bid Due: 10/18/2024
Follow Q402--Nursing Home Services | VISN 8 Open and Continuous Solicitation Active Contract
Federal Agency
Bid Due: 7/14/2024
* Disclaimer: Information regarding bids, requests for proposals (RFPs), or requests for qualifications (RFQs) is provided on this website only as a convenience and does not constitute official public notice. Persons wishing to respond to or inquire about bids, RFPs, or RFQs should contact the appropriate government department.